In case the actuator will have to be removed, it is recommended to
electrically open the valve for easier removal. Thereafter reverse the
procedure (3) and turn the snap ring clockwise until the actuator is
loosened and (4) lift the actuator up. No additional tools are needed.

4

3

NB! Do not remove the cover from actuator. Opening the cover will
void warranty.

Upside down installation is allowed (although not recommended) along
with the standard horizontal and vertical installation.

When the power is turned on, the actuator will automatically calibrate
to determine closing point of the valve. At first start-up, please enter the
programming menu to set actuator settings.

Start-up sequence

When the power is turned on, the actuator will automatically calibrate
to determine the closing point of the valve. Calibration can take up to 10

minutes depending on the valve's position at the start up. During the
calibration, the actuator display will show "

CAL

". Thereafter it will

proceed to normal operation mode (according to control signal).

If no control signal is detected, flush is started if enabled in the
programming menu (enabled by default), opening the valve to 5/6 of
fully open. Actuator display will show "

FLUSH

" until the control signal is

detected.

At first start up please enter the programming menu to set actuator
settings. See Settings sections for more information.

Pressure reading for verifications

P1 - P2

Figure 3 P1 = H pressure port; P2 = L pressure port

Q

CONST

Q

=

CONST

Q

P1 - P2

A

kPa

Figure 4 If P1-P2 > Start up pressure (A), then the valve is within the working range
(see section Technical data).

Wiring

If feedback signal is not required, leave the green wire detached.

Actuator 0(2)-10V modulating

1

24V AC/DC

3

4

e

f

2

Actuator 2-position, Normally Open

1

24V AC/DC

a

4

2

5

c

3

d

Actuator 2-position, Normally Closed

1

24V AC/DC

4

a

2

5

c

3

d

Actuator 3-point floating, Normally
Open

1

24V AC/DC

a

4

5

2

c

3

b

d

Actuator 3-point floating, Normally
Closed

1

24V AC/DC

a

4

5

2

c

3

b

d

Number

Wiring colour

Letter

Description

1

Black

a

Open

2

Blue

b

Stop

3

Green

c

Close

4

White

d

Feedback signal

PCMTV DN50-250

2

Summary of Contents for PCMTV DN50-250

Page 1: ...te value and to maintain it stable Since flow rate is the only parameter to be considered choosing the suitable valve is easy and fast Technical data valve Pressure class PN40 Connection Flanged accor...

Page 2: ...after it will proceed to normal operation mode according to control signal If no control signal is detected flush is started if enabled in the programming menu enabled by default opening the valve to...

Page 3: ...igital Choose 2 10VDC for VDC 4 20 mA for mA Digital for 2 position or 3 point floating 6 Select minimum control value scrolling top SET MINIMUM LIMIT Volt default 2 Options from 0 7 Increment 0 1 mA...

Page 4: ...inutes If over torque condi tion disappear er ror will convert to error code 02 02 BLINKING Actuator has reached its torque limit in the past Actuator is func tioning To reset the alarm simulta neousl...

Page 5: ...sgew hlt werden Technische Daten Ventil Druckklasse PN40 Anschluss Mit Flansch gem EN 1092 Universalflansche zwei oder mehr Rohr Nennweiten k nnen an denselben Ven tilflansch passen Max Differenzdruck...

Page 6: ...enn sie im Programmiermen aktiviert ist standardm ig aktiviert wodurch das Ventil zu 5 6 ge ffnet wird Das Display des Stellantriebs zeigt FLUSH Sp len an bis das Stellsignal erkannt wird Bitte rufen...

Page 7: ...V DC Optionen 2 10 V DC oder 4 20 mA oder digital Zur Auswahl 2 10 V DC f r VDC 4 20 mA f r mA Digital f r 2 Punkt oder 3 Punkt 6 Auswahl Min Stellsignal Scrollbalken oben UNTERGRENZE EINSTELLEN Volt...

Page 8: ...ert Schritt 11 Standardm ig deakti viert Passwort 3569266 Code Symbol Beschreibung Details 01 FULL ON Ventil Stellantrieb ist berdreht Der Betrieb wird angehalten Der Antrieb wiederholt alle 4 Minuten...

Page 9: ...n pour un d bit sp cifique et permettent un contr le modulant Les caract ristiques de d bit de la vanne lin aire ou pourcentage gal peuvent tre d finies partir de l actionneur Il est galement possible...

Page 10: ...e sous tension est effectu e l actionneur calibre automatiquement sa course pour d terminer les positions Ouvert Ferm L talonnage peut prendre jusqu 10 minutes d pendant de la position initiale du la...

Page 11: ...lement haut SELECT FLUSH MODE Par d faut Activer Options Activer ou D sactiver Quand aucun signal analo gique n est d tect au d mar rage le mode rin age est d marr 5 6 totalement ou vert Il sera arr t...

Page 12: ...me 01 04 05 avec fonction s curit 07 sans s curit l icone clignote Si l actionneur est l arr t code d alarme 01 03 05 avec fonction s curit 08 sans s curit l icone est statique Les codes d erreur sont...

Page 13: ...gler la position de la vanne ind pendamment des r glages et du signal de commande D connecter l alimentation de l actionneur et le d saccoupler de la vanne Tourner la tige de vanne dans le sens des a...

Reviews: