Regin AQUA24TF Instructions Manual Download Page 4

2355D APR 

13

AQUA24TF

Box 116   428 22  KÅLLERED    SWEDEN

Tel +46 (0)31 720 02 00  Fax +46 (0)31 720 02 50

INSTRUCTION

INSTRUCTION

Fig 3

Fig 4

Fig 5

Fig 6

Fig 7

Fig 8

Relays are drawn in alarm position
All neutrals internally connected

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

Sensor neutral

Main sensor

Sensor neutral

Limiting sensor

Sensor neutral

Frost protection sensor

Night setback

Supply voltage 24 V AC

System neutral

Run mode indication

Run mode indication

Actuator, Common pole

Actuator, Increase heat

Actuator, Reduce heat

Alarm relay 1

2 A 240 V AC

Alarm relay 2

2 A 24 V AC

Shut down mode

AQUA24TF/D has an input (terminals 15-16) which is wired to a 
potential-free contact in the fan motor relay. The contact should 
be closed when the fan is running. When the fan is stopped the 
AQUA24TF/D will switch to shut-down mode which means that the 
temperature at the frost protection sensor is held at 25°C.

Night setback
A potential free closure between terminals 6 and 12 will give a fi xed 
night setback of 3K.

Settings

AQUA24TF/D is on delivery set to values suitable as starting values 
for balancing the system.
Final settings must be tried out when the system is commissioned. 
Factory settings FS in brackets.

Setpoint  0 - 30°C. Setpoint for the main controller. (FS = 20°C).
CF 

1 - 15. Cascade factor. (FS = 1). The value signifi es the 
immediate change in the duct controller setpoint for a 
1K step change in room temperature. (Cascade control 
only).

Min 

0 - 30°C. Minimum duct temperature. (FS = 15°C). (Cas-
cade control only).

N.B. 

When running single sensor temperature control (not cas-
cade control) CF must be set to 1 in order to get stable 
control. 
Min is inactive.

EMC emissions & immunity standards

This product conforms with the requirements of European EMC 
standards CENELEC EN 50081-1 and EN 50082-1 and carries the 
CE mark.

LVD

This product conforms with the requirements of European LVD stan-
dards IEC 669-1 and IEC669-2-1.

RoHS

This product conforms to the Directive 2011/65/EU of the European 
Parliament and of the Council.