Regency P42-3 Zero Clearance Direct Vent Gas Fireplace
16
The P42 is approved for a 23 ft. (7.0m) vertical, with a maximum 12 ft (3.7m) horizontal offset
using two 90
o
elbows (two 45
o
elbows equal one 90
o
elbow) with rigid pipe vent systems for
Propane and Natural Gas, as per the diagram below.
•
No Vent restrictor is required.
•
Vent must be supported at offsets
The P42 is approved for a 37 ft. (11.3m) straight
vertical, with rigid pipe vent systems for
Propane and Natural Gas, as per the diagram
below.
•
Vent restrictor #6 must be used
Diagram 3
Diagram 4
Note: Regency Direct Vent System (Flex) is only approved for
horizontal terminations.