10
| P36-10 Zero Clearance Direct Vent Gas Fireplace
|
10
installation
WARNING: Fire hazard is an extreme risk if these clearances are not adhered to.
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fireplace and vent system be installed only in accordance with these instructions.
Clearance to Combustibles from:
Back
0"
(0mm)
Side
0"
(0mm)
Floor
0"
(0mm)
NOTE: The minimum floor clearance must be maintained from the top surface of the carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Ceiling
from top of unit.
32"
(1016mm)
Side Wall Clearances
6"*
(152mm)
* Measured from edge of unit.
Horizontal Vent Clearances:
Top
2"
(51mm)
Side
1-1/2" (38mm)
Bottom
1-1/2" (38mm)
Vertical Vent Clearances
1-1/4" (32mm)
Alcove Clearances**:
Max. Depth
36"
(914mm)
Min. Width
48"
(1219mm)
Min. Height
72"
(1829mm)
The
HeatWave
Duct Kit and the Heat
Release Kit have different clearance
and framing requirements, check the
HeatWave
and Heat Release manual
for details.
Heat Release Kit
CLEARANCES