installation
Grandview
®
G800C-1 Gas Fireplace | 23
Cool Wall Installation - Framing
Framing Dimensions
Description
Cool Wall
Cool Wall
with Finishing Trim or Faceplate
M
Framing Width
36-1/2" (927mm)
37-1/2" (952mm)
N*
Framing Height
43" (940 mm)
O
Framing Depth
16-7/8" (427 mm)
P
Corner Facing Wall Width
42-1/2" (1035 mm)
Q
Corner Facing Wall Width
60" (1524 mm)
R
Framed Chase Ceiling Enclosure
80" (2032 mm)
S (Rear Vent)
Vent Centerline Height - Rear
29" (737 mm)
S (Top Vent)
Vent Centerline Height - Top
44" (1118 mm)
T
Gas Connection Height
1-1/2" (38 mm)
U
Gas Connection Inset
6-3/8" (162 mm)
V
Gas Connection Width
3" (76 mm)
W
Clearance to Corner of Unit
2-3/4" (70 mm)
* Important: Framing height requires consideration of the hearth height. Dimension N = N + the thickness of the installed hearth.
Q
P
R
M
N
O
S
S
U
T
V
Combustible header
Top Vent
Rear Vent
W
Corner=Top Vent Only
IMPORTANT: Corner applications are vented from the top
only - rear venting cannot be used.
Note: The 2 standoffs at the rear of the appliance may be removed as these are not required in this application. Ensure that any screws that are
removed are reinstalled. The 2 standoffs can eb recycled/discarded.
**The framing depth/width does not take into account dry wall/wood or similar materials against the back /side wall. The framing depth
will need to change based on the thickness of the material
(example: M - 36-1/2" framing width + 1/2" drywall = 37")
(example: M Outside finish with finishing trim/faceplate - 37-1/2" framing width + 1/2" drywall = 38")
(example: O - 16-7/8" framing depth + 1/2" drywall = 17-3/8")
**
**