14
Regency GF900L-1 Gas Fireplace
installation
COMBUSTIBLE REQUIREMENTS
FRAMING & FINISHING
Note:
Depending on the material used for finishing, the nailing
strips must be set accordingly so that the finished material
is always at the 38mm edge of the flange.
NOTE: A minimum thickness
of 12mm non combustible
facing is required.
Note:
•
The siding nailing strips are factory set at 12mm. The
top nailing strip is fixed during transit to the rear of the
appliance.
•
Do not place any reinforcement in front of header and
behind finishing material.
•
The nailing strip must be used. It is fixed during transit
to the rear of the unit.
NOTE:
The appliance must be installed
on a flat, solid continuous surface,
For example., a wood, metal or
concrete floor or in a raised (on
the wall) application. The appli-
ance must be installed on a metal
or wood base extending the full
width and depth of the appliance.
NOTE:
If raising the unit, then the minimum
height measurement (A) on page
11 of the framing dimensions must
be adhered to. For example., Unit
raised 300mm then A+ 300mm =
1389mm.
11
08
m
m
83mm
606mm
502mm
1165mm
Non-combustible
Material
Non-combustible
Non-combustible
Non-combustible
Header
on edge
Timber Stud
Timber Stud
15
6m
m
451mm
Combustible
Material
Finished
Material
Nailing Strip
Position
12mm
25mm
25mm
12mm
38mm
0mm (flush)
Unit
Nailing Strip
Flush w/unit
Factory Set
Unit
Nailing Strip
12mm Forward
Unit
Nailing Strip
25mm Forward
MINIMUM THICKNESS OF THE FINISH MATERIAL: 12MM