background image

8

 Regency E21 Gas Fireplace Insert

HIGH ELEVATION

This  unit  is  approved  in  Canada  for  altitude 

0  to  4500  ft.  (CAN/CGA  2.17-M91)  with  the 

orifi ce supplied.

System Data

For altitude:  Natural Gas  0-2000 ft.   

 

 

Propane: 

0-4500 ft.

Burner Inlet Orifi ce Sizes:

                 

          Natural Gas   Propane

   Burner 

#43           #54                     

Max. Input Rating 

  - Natural Gas 

23,500 Btu/h

- Propane 

22,500 Btu/h

Min. Input Rating 

- Natural Gas

--

+/-5%  11,750 Btu/h

  -Propane      +/-5%  11,250 Btu/h 

Supply Pressure

  Natural Gas 

min.  5.0" w.c.

  Propane 

min.  12.0" w.c. 

Manifold Pressure  (High)

  Natural Gas 

3.8"   +/- 0.2" w.c.

  Propane 

11"   +/- 0.2" w.c.

Circulation Fan: 

120 VAC, 60 Hz

Variable Speed: 

 127 CFM, thermally  

activated

NATURAL GAS  E21-NG1

For altitude:        2000 ft - 4500 ft.

Burner Inlet Orifi ce Size: 

44 DMS

Max. Input Rating 

22,000 Btu/h

Min. Input Rating 

+/-5% 11,000 Btu/h

INSTALLATION

GAS CONNECTION

Only persons licensed to work with gas piping 

may make the necessary gas connections to 

this appliance.  

The gas connection is a 3/8" NPT accessible on 

the left side of the unit.  The gas line connection 

may be made of rigid pipe, copper pipe or an 

approved fl ex connector. (If you are using rigid 

pipe,  ensure  that  the  valve  can  be  removed 

for servicing.) Since some municipalities have 

additional local codes it is always best to consult 

with your local authorities and the CAN/CGA 

B149 installation code.

For USA installations follow local codes and/or 

the  current  National  Fuel  Gas  Code,  ANSI 

Z223.1.

When using copper or fl ex connectors use only 

approved fi ttings. Always provide a union so that 

gas lines can be easily disconnected for burner 

or fan servicing. Flare nuts for copper lines and 

fl ex connectors are usually considered to meet 

this requirement.

Important:  Always check for gas leaks 

with a soap and water solution or gas 

leak detector. Do not use open fl ame 

for leak testing.

For minimum and maximum supply pressure 

see the System Data table.

1)

  If  the  appliance  is  to  be  installed  into  an 

existing chimney system, thoroughly clean 

the masonry fi replace that has been chosen 

for the Regency Gas Fireplace.

2)

  The appliance is provided with an opening on 

the left hand side of the control compartment 

for the gas line.

Note: During any pressure testing of the gas 

supply piping system that exceeds test pressures 

of  1/2  psig,  this  appliance  and  its  individual 

shut-off valve must be disconnected from the 

piping system.  If test pressures equal to or less 

than 1/2 psig are used then this appliance must 

be isolated from the piping system by closing 

its individual manual shut-off valve during the 

testing.

CAUTION:    If  the  glass  is  removed  for 

servicing,  it  must  be  replaced  prior  to 

operating  the  appliance.    The  glass  must 

be  fixed  in  the  closed  position  when 

operating.

Summary of Contents for E21-LP1

Page 1: ... try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department FPI FIREPLACE PRODUCTS INTERNATIONAL LTD 6988 Venture St Delta BC Canada V4G 1H4 918 354a MODELS E21 NG1 Natural Gas E21 LP1 Propane E21 G...

Page 2: ...ou with all the warmth and charm of a fireplace at the flick of a switch The models E21 NG1 and E21 LP1 of this series have been approved by Warnock Hersey for safety As it also bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the many features of your Regenc...

Page 3: ...bel 4 INSTALLATION INSTRUCTIONS Before You Start 5 General Safety Information 5 Policy for Factory Built Fireplaces 6 Installation Checklist 6 Minimum Fireplace Clearances 6 Clearances to Combustibles 7 Gas Connection 8 System Data 8 High Elevation 8 Wiring Diagram 9 Flue Connector Installation 9 Offset Flue Adaptor 10 Venting 10 Combustion Ventilation Air Combustion Ventilation Air Combustion Ven...

Page 4: ...Au dessus B 14 355mm MADE IN CANADA FABRIQUE AU CANADA FPI Fireplace Products International Ltd Delta B C Canada FIREPLACE INSERT E21 NG1 E21 LP1 APPAREIL FONCTIONNANT CONCU POUR Natural Gas Naturel Gaz Propane ETRE INSERE DANS UN FOYER Minimum supply pressure 5 0 WC C E 1 25 kPa 12 0 WC C E 2 99 kPa Pression d alimentation minimum Manifold pressure high 3 8 WC C E 0 95 kPa 11 0 WC C E 2 74 kPa Pr...

Page 5: ...building Make sure that the vent is installed as per Venting instructions 5 This appliance may only be installed in a vented solid fuel burning masonry listed factory built fireplace or zero clearance kit part 530 936 6 This appliance is Listed for bedroom installationswhenusedwithaListedMillivolt Thermostat Some areas may have further requirements check local codes before installation 7 This appli...

Page 6: ...am shows the minimum fireplace opening required to be able to install the Regency gas fireplace insert INSTALLATION CHECKLIST 1 Locate appliance check Clearances to Combustibles page 7 2 Make gas and electrical connections page 8 Test the pilot Must be as per diagram page 11 3 Install Flue Connector page 9 4 Install vent page 10 5 Test Gas pressure page 10 and check aeration page 11 6 Test for flue s...

Page 7: ...hes 229mm The minimum clearance from the top of the louver to a combustible mantel is 14 inches 356mm 14 inches 356mm The minimum height from the top of the louver to the ceiling is 36 inches 914mm 36 inches 914mm See diagram Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board ...

Page 8: ...consult with your local authorities and the CAN CGA B149 installation code For USA installations follow local codes and or the current National Fuel Gas Code ANSI Z223 1 When using copper or flex connectors use only approvedfittings Alwaysprovideaunionsothat gas lines can be easily disconnected for burner or fan servicing Flare nuts for copper lines and flex connectors are usually considered to meet ...

Page 9: ...current CSA C22 1 in Canada or with the National Electrical Code ANSI NFPA 70 1987 in USA NOTE This unit is equipped with a heat sensor thermodisc which will prevent the blower from operating until the unit reaches the correct temperature Green Ground Neutral Live Black Black Red Black Fan Thermodisc ON OFF Rotary Speed Control 120V AC 60 Hz Ground Fan Grounding Lug Detail Lockwasher Fan ground Po...

Page 10: ...typeB Ventorapprovedaluminium flex liner may also be used with a 4 to 3 reduc ing adapter Consult venting charts and local code requirements TheRegencyInsertincorporatesitsowninternal draft hood so no additional external draft hood is required Check periodically that the vent is unrestricted and an adequate draft is present when the unit is in operation Beforeinstallingtheventsystemensurethatthe da...

Page 11: ...dRegency Installer at the time of installation or service a scrap piece of sheet metal or other noncombustiblematerial intheupperlouver thiswillpreventthenaturalconvectionofthe unit from interfering with the test Note The smoke should be drawn into the louver If the smoke is still not drawn in turn the unit off and check for the causeofthelackofdraft Ifnecessary seek expert advice OPTIONAL BRICK P...

Page 12: ...ide of the log snugly against the right edge of the burner tray Vermiculite Embers Vermiculite Embers Vermiculite Embers Vermiculite LOG SET INSTALLATION Read the instructions below carefully and refer to the diagrams If logs are broken do not use the unit until they are replaced Broken logs can interfere with the pilot operation The gas log kit set 532 930 contains the following a 02 66 Rear Log ...

Page 13: ...rs provided join the left side trim with the ON OFF switch to the top trim See diagram 2 Connect the right side trim to the top trim 4 Place the trim on the assembled faceplate panels aligning the wire connections from the switches with the notch on the left side panel 5 Connect the fan switch wires by taking the black and red wires with the male ends in the grey harness and connect them with the ...

Page 14: ...nets on the back of each trim piece close to the ends Place the top and bottom trim pieces on the bay front 3 Install top and bottom louvers Note Topandbottomlouversandbrackets are different See diagram below 2 Install bottom louver by sliding the two bracket clips into the brackets located underneath the bay door and secure with 2 screws into the bracket on the bottom of the Bay Front as per diag...

Page 15: ...he Grate by removing the screws on each side of the grate 7 Remove the Burner Tray by removing 1 screw on each side of the tray then slide the tray to the left and lift out 8 Pull off the pilot cap to expose the pilot orifice 9 Unscrew the pilot orifice with the allen key provided and replace with the LP pilot orifice in the kit 10 Remove burner orifice with 1 2 wrench Use another wrench to hold onto ...

Page 16: ...the switch box in place then pull the thermosdisc out of the bracket 11 Remove and discard the 3 pressure regulator mounting screws A pressure regulator tower B and diaphragm C 12 Insure that the rubber gasket D is properly positioned and install the new HI LO pressure regulator assembly to the valve using the new screws E supplied with the kit Tighten screws securely 13 Replace Burner Tray and re...

Page 17: ...th the wire connectors from the fan speed control Place clips over wires and tuck into side trim 2 Lift the unit up slightly and push down on the corners of the Bottom Trim Bracket and slide under unit Bottom Trim Bracket Push in Corners 3 Completely secure full screen door to the unit by securing 4 screws to the Left and Right Side Trim 4 Secure the Top Frame by sliding it on the screws at the to...

Page 18: ...h Bottom Frame Hinge Location 5 Install Spring Hinges to the Left and Right Side of the bottom of the firebox using 2 screws per hinge 7 Install the Left and Right Side Screen Doors by placing over top of the hinges on the faceplate Hold the door at a 45 degree angle to avoid scratching the faceplate Hinge Screen Door 8 Close screen doors ...

Page 19: ...ace to that location Use Thermostat Wire Table 2 Connect the two wires to the gas valve See diagram below CAUTION Do not wire millivolt remote control wires to 120V wire 3 Install 3AAAalkaline batteries in transmitter and 4 AA alkaline batteries in the receiver Install the receiver and its cover in the wall Switch the remote receiver to remote mode The remote control is now ready for operation Opt...

Page 20: ...PERATING INSTRUCTIONS Beforeoperatingthisappliance proceedthrough the following check list 1 Read and understand these Instructions before operating this appliance 2 Check to see that all wiring is correct and enclosed to prevent possible shock LIGHTING PROCEDURE IMPORTANT Gas cock knob cannot be turned from PILOT to OFF unless it is partially depressed 1 Open the bottom louver assembly 2 If the c...

Page 21: ...ghtly and turn clockwise to OFF Knob cannot be turned from PILOT to OFF unless knob is pushed in slightly Do not force 2 Wait five 5 minutes to clear out any gas If you then smell gas STOP follow B in the safety information above on this label If you don t smell gas go to the next step 3 Turn knob on gas control counterclockwise to PILOT 4 Push in control knob all the way and hold in Continually p...

Page 22: ...OLD PLATED ACCESSORIES The24caratgoldplatedfinishontheaccessories requires little maintenance and need only be cleanedwithadampcloth DONOTuseabrasive materials or chemical cleaners as they may harm the finish and void the warranty Clean any fingerprints off before turning the unit on If the top louvers start to discolour check the door gasket seal and replace if necessary AUTOMATIC CONVECTION FAN OPE...

Page 23: ...f the bracket under the left side of the firebox bottom 13 Remove valve assembly from stove body by removing 3 phillips screws 14 Remove the valve from the bracket and replace Reverse steps to install valve DOOR GLASS REPLACEMENT Your Regency stove is supplied with high temperature 5mmNeoceramceramicglassthat will withstand the highest heat that your unit will produce In the event that you break yo...

Page 24: ...ush Louver set Gold Black 532 914 Flush Louver set Steel Black 21 Top Flush Louver 23 Bottom Flush Louver 530 952 Bay Louver set Black 530 954 Bay Louver set Gold Black 530 955 Bay Louver set Steel Black 25 Top Bay Louver 26 Bottom Bay Louver 530 945 Brick Panel Set Standard 532 901 Brick Panel Set Standard Brown 532 902 Brick Panel Set Standard Red 532 903 Brick Panel Set Herringbone Brown 532 90...

Page 25: ...T Nat Gas 910 099 Valve SIT Propane 53 910 190 Piezo Ignitor Nut 56 910 076 Pilot Assembly SIT 3 flame NG 910 077 Pilot Assembly SIT 3 flame Propane 904 162 43 Orifice NG 904 163 54 Orifice LP 59 402 526 Grate Diffuse Assembly 62 532 530 Burner Assembly NG LP 69 532 930 Complete Log Set 533 969 Conversion to Propane Kit Not available as a replacement part PARTS LIST ...

Page 26: ... 906 Bay BricK Panel Standard Red 111 400 153 Bay Glass Trim Top Black 112 904 196 1 Round Ceramic Magnet 113 400 152 Bay Glass Trim Bottom Black 402 956 Gold Trim Bay Front 402 958 Steel Trim Bay Front 114 Glass Retainer Side Top Bottom 115 Glass Retainer Center Top Bottom Flush Door 530 547 P Flush Door Assembly Complete 107 936 243 Gasket Adhesive Backed 7 8 153 Glass Side Trim 154 Flush Glass ...

Page 27: ...ate Standard Contour Trim Right 125 Faceplate Standard Contour Trim Top 126 Faceplate Standard Contour Trim Left 532 950 Trim Set Standard Contour Brass 532 919 Faceplate Trim Set Oversize Contour Black 141 Faceplate Contour Oversize Side Right 142 Faceplate Contour Oversize Top 143 Faceplate Contour Oversize Side Left 144 Trim Contour Oversize Side Right 145 Trim Contour Oversize Top 146 Trim Ass...

Page 28: ...___________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ________________________...

Page 29: ...___________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ________________________...

Page 30: ...___________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ________________________...

Page 31: ...sible Any chips must be reported and inspected by an authorized dealer within three days of installation Reported damage after this time will be subject to rejection It is the general practice of FPI to charge for larger higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated for manufacturer defect The authorized selling dealer is respon...

Page 32: ...ty in mind In addition our internal Quality Assurance Team carefully inspects each unit Team carefully inspects each unit thoroughly before it leaves our door thoroughly before it leaves our door thoroughly before it leaves our door Fireplace Products International Fireplace Products International Fireplace Products International Fireplace Products International Fireplace Products International Lt...

Reviews: