CB40E Gas Fireplace

Caution Requirements

The top, back and sides of the fireplace are defined by 

standoffs. The metal ends of the standoff may 

NOT

 be 

recessed into combustible construction.

WARNING

Fire hazard is an extreme risk 

if these clearances (air space) to combustible materials are not 

adhered to. It is of greatest importance that this fireplace and vent 

system be installed only in accordance with these instructions.

CLEARANCES CB40E (3 SIDED)

Clearance: 3 sided

Dimension

Measured From:

A: From Floor

25-9/16" (649mm)

Top of Fireplace Opening

A���� : Mantel Height (min.)

**

Top of Fireplace Opening

B: Sidewall (on one side)

8-1/2" (216mm)

Side of Fireplace Opening

C: Enclosure Width (min.)

48-7/16" (1230mm)

Minimum inside dimensions

D: Mantel Depth (max.)

**

E: Alcove Width

84" (2134mm)

Side wall to side wall (min.)

F: Alcove Depth

36" (914mm)

Front of Unit

G: To Enclosure Ceiling (min/max)

0-3" (76mm)

From top of enclosure

H: Convection Air outlet 

120 sq. inches (min)

* Top/front or side of enclosure

I: Enclosure Depth (min.)

19" (483mm)

Minimum inside dimensions

J: Opening Height

15-1/16" (383mm)

Bottom/Top of Fireplace Opening

K: To Ceiling (min) All 3 sides

1-1/2"

To Top of Ceiling

L: Chase Enclosure (min.)

63" (1600mm)

From base of unit/floor

Hearth

0"

No hearth required

** 

See mantel clearances chart in this manual

Flue Clearances to Combustibles

Horizontal - Top

3"

Horiztonal - Side 

2"

Horiztonal - Bottom

2"

Vertical

2"

Passing through wall/

floor/ceiling  -  when 

firestop is used.

1-1/2"

*  A minimum of 120 square inches of open area, not lower than 3" from top of enclosure, required for all 

installations — this can be achieved by having an open area in front, each side, and/or above as shown 

in the four diagrams on the next page.

The 

HeatWave

  Duct  Kit  has 

different  clearance  and  framing 

requirements, check the 

HeatWave

 

manual for details.

E

F

Alcove

Summary of Contents for City Series CB40E Series

Page 1: ... 4500 ft 42 DMS 53 DMS Minimum Input Altitude 0 4500 ft 0 1372m 15 500 BTU h 4 54 kW 15 500 BTU h 4 54 kW Maximum Input Altitude 0 4500 ft 0 1372m 28 500 BTU h 8 33 kW 28 500 BTU h 8 33 kW Vent Sizing 4 Inner 6 5 8 Outer 4 Inner 6 5 8 Outer 48 7 16 1231mm 25 9 16 648mm 37 3 8 949mm 43 1091mm 33 7 16 849mm 7 1 4 183mm Ø 4 102mm Ø 6 3 4 171mm 11 7 16 291mm 24 1 4 616mm 49 5 8 1261mm 18 11 16 475mm 1...

Page 2: ...lcove Depth 36 914mm Front of Unit G To Enclosure Ceiling min max 0 3 76mm From top of enclosure H Convection Air outlet 120 sq inches min Top front or side of enclosure I Enclosure Depth min 19 483mm Minimum inside dimensions J Opening Height 15 1 16 383mm Bottom Top of Fireplace Opening K To Ceiling min All 3 sides 1 1 2 To Top of Ceiling L Chase Enclosure min 63 1600mm From base of unit floor H...

Page 3: ...o ceiling with top opening Low framing with vents in front sides or top Full framing with low vents in front or sides Full framing with vents in front or sides K C I A1 A D L J H B L I C D A1 A J G G H H H B I C G A A1 G D J L H H B I B A D C J G G L H H ...

Page 4: ...escription CB40E A Framing Height 37 3 8 949mm B Framing Width 48 1 2 1232mm C Framing Depth 19 483mm D Minimum Height to Combustibles 63 1600mm G Vent Centerline Height 56 1 4 1429mm I Gas Connection Opening Height 2 51mm J Gas Connection Height 4 106mm K Gas Connection Inset 13 330mm L Gas Connection Opening Width 3 1 2 89mm Note A combined minimum of 120 square inches of open area is required f...

Page 5: ...agram on the right Note Ensure the paint that is used on the mantel and the facing is high quality or the paint may discolour MANTEL LEG CLEARANCES Combustible mantel leg clearances as per diagram Combustible Material 2 12 6 4 8 10 Standoff Wood Stud On Edge 0 14 9 15 1 16 10 20 26 Top of Fireplace Opening 12 305mm Drywall wood wood panel etc 2 To Bottom of Fireplace Lip 12 MANTEL LEG 8 1 2 CB40E ...

Page 6: ... two 45o elbows equal one 90o elbow Note Must use optional rigid pipe adapter Part 510 994 when using Rigid Pipe Venting Systems Maintain clearances to combustibles as listed in Clearances section Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A vent guard should be used whenever the termination is lower than the specif...

Page 7: ...eet otherwise rigid venting must be used HORIZONTAL VENTING WITH TWO 2 90O ELBOWS One 90o elbow Two 45o elbows Option V H H1 With these options maximum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet total horizontal Please note minimum 1 foot between 90o elbows is required A 1 Min 2 Max B 2 Min 4 Max C 3 Min 5 Max D 4 Min 6 Max E 5 Min 7 Max F 6 Min 8 Max Res...

Page 8: ... every 3 feet Firestopsarerequiredateachfloorlevelandwhenever passing through a wall Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems Refer to the Vent Restrictor Position section for details on how to change the vent restrictor from the factory setting of Set 0 through to Set 3 if required NOTE A minimum of 1 305mm vertical off the top of the unit is required b...

Page 9: ...re required at each floor level and whenever passing through a wall Must use optional rigid pipe adaptor Part 510 994 when using rigid pipe vent systems Vertical Venting with Three 3 90o Elbows One 90o elbow Two 45o elbows V H1 H V1 Option V H H1 V V1 With these options max totalpipelength is 30 feet with min of 10 feet total vertical and max 8 feet total horizontal Please note min 1 foot between ...

Page 10: ... the bottom edge of the ventilated fireplace chase opening The TV may be recessed into a wall as shown below This can only recess into the chase opening a maximum of 3 1 2 inches and must be a minimum of 12 inches from the fireplace lip to the first stud To achieve a maximum of 3 1 2 recess the wall must be of a maximum of 2 as shown TV RECESSED INTO WALL The TV cannot be any lower than this finis...

Reviews: