Regency Bellavista® B41XTE -10 Gas Fireplace
|
29
|
29
installation
16
2
2
0
0
12
12
6
6
18
4
47-1/2"
(1207mm)
Minimum
Height
Requirement
4
14
8
8
10
10
14
16
18
20
Vertical
Height
(Feet)
Horizontal (Feet)
Restrictor 1-1/2 Open
Set 3
Restrictor 2-1/2 Open
Set 2
Restrictor 3-1/2 Open
Set 1
VENTING ARRANGEMENTS
FOR HORIZONTAL TERMINATIONS
The diagram shows all allowable combinations of vertical runs with horizontal terminations,
using one 90
o
(two 45
o
elbows equal one 90
o
elbow).
• Maintain clearances to combustibles as listed in "Clearances" section
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each floor level and whenever passing through a wall.
• A wall thimble is mandatory for all horizontal terminations due to high temperatures.