Regency

®

 P33-4 Zero Clearance Direct Vent Gas Fireplace

25

Riser Vent

Termination

Min. 6-1/4"*

(159mm)

INSTALLATION

Diagram 3

UNIT INSTALLATION WITH HORIZONTAL TERMINATION

Diagram 1

 b)

  Horizontal runs of vent must be 

supported every three feet. Wall straps 
are available for this  purpose.

5)

  Mark the wall for a 10" x 10"  square hole. 

The center of the square hole should line 
up with the centerline of the horizontal pipe. 
Cut and frame the 10 inch square hole in 
the exterior wall where the vent will be 
terminated. If the wall being penetrated is 
constructed of non-combustible material, i.e. 
masonry block or concrete, a 7"(178mm) 
diameter (7-1/2"(191mm) dia. for fl ex) hole 
is acceptable. 

Note:

 a)

  The horizontal run of vent must be level, 

or have a 1/4 inch rise for every 1 foot 
of run towards the termination. Never 
allow the vent to run downward. This 
could cause high temperatures and may 
present the possibility of a fi re.

 

b)

  The location of the horizontal vent 

termination on an exterior wall must meet 
all local and national building codes, 
and must not be blocked or obstructed.  
See "Exterior Vent Terminal Locations" 
Section.

 

c)

 

Snorkel Terminations:

 

 

For installations requiring a vertical rise 
on the exterior of the building, 14-inch 
and 36-inch tall Snorkel Terminations 
and the Riser Vent  as shown in 
Dia. 2 & 2a are available. Follow the 
same installation procedures as used 
for standard Horizontal Termination. 
NEVER install the snorkel upside 
down.

*As specifi ed in CGA B149 Installation Code. 
Local codes or regulations may require different 
clearances.

Diagram 2

 

 

Below Grade Snorkel Installation

 

 

If the Snorkel Termination must be 
installed below grade, i.e. basement 
application, proper drainage must be 
provided to prevent water from entering 
the Snorkel Termination. Refer to 
Dura-Vent Installation instructions for 
details. Do not attempt to enclose the 
Snorkel within the wall, or any other 
type of enclosure.

6)

 

The arrow on the vent cap should 
be pointing up.

 Insure that the 1-1/2" 

clearances to combustible materials are 
maintained (Dia. 3). Install the termination 
cap.

 

AstroCap

TM

 or Dura-Vent Horizontal 

Termination Cap may be used.

Diagram 2a

Install the vent system according to the 
manufacturer's instructions included with the 
components.

1)

  Set the unit in its desired location. Check 

to determine if wall studs or roof rafters 
are in the way when the venting system is 
attached. If this is the case, you may want 
to adjust the location of the unit. Rough in 
the gas preferably on the right side of the 
unit and the electrical (junction block is on 
the left side) on the left.

2)

  Direct Vent pipe and fi ttings are designed 

with special twist-lock connections to 
connect the venting system to the appliance 
fl ue outlet. A twist-lock appliance adaptor 
is an available option that must be used in 
conjunction with the Simpson Dura-Vent 
Direct Vent GS system. 

3)

  Put a bead of silicone inside the outer section 

of the adapter and a bead of Fireplace Mate 
on the inner collar. Slip the adapter over the 
existing inner and outer fl ue collar and fasten 
to the outer collar only with the 3 supplied 
screws (drilling pilot holes will make this 
easier). Level the fi replace and fasten it to 
the framing using nails or screws through 
the nailing strips.

4)

  Assemble the desired combination of pipe 

and elbows to the appliance adaptor and 
twist-lock for a solid connection.

Note:

 

a)

    Twist-lock procedure: Four indentations, 

located on  the female ends of pipes and 
fi ttings, are designed to  slide straight 
onto the male ends of adjacent pipes 
and fi ttings, by orienting the four pipe 
indentations so they match and slide 
in to the four entry slots on the male 
ends, Dia. 1. Push the pipe sections 
completely  together, then twist-lock 
one section clockwise approximately 
one-quarter turn, until the two sections 
are fully locked. The female locking lugs 
will not be visible from the outside, on 
the Black Pipe or fi ttings. They may be 
located by examining the inside of the 
female ends.   

NOTE:

   

For best results and optimum 

performance with each approved venting 
system, it is highly recommended to apply 
“Mill-Pac” sealant (supplied) to every in-
ner pipe connection. Failure to do so may 
result in drafting or performance issues not 
covered under warranty. Silicone (red RTV) 
is optional.

 

The four wood screws provided should 
be replaced with appropriate fasteners for 
stucco, brick, concrete, or other types of 
sidings.

Note:  If installing termination on a siding 

covered wall, a vinyl siding standoff 
or furring strips must be used to 
ensure that the termination is not 
recessed into the siding.

 

7)

  Before connecting the horizontal run of vent 

pipe to the vent termination, slide the Wall 
Thimble (Part # 620-926) over the vent 
pipe.

Min. 12"*
(305mm)

Dura-Vent

Snorkel

Summary of Contents for P33-LP4

Page 1: ...in the vicinity of this or any other appliance Installation and service must be performed by a quali ed installer service agency or the gas supplier FOR YOUR SAFETY What to do if you smell gas Do not...

Page 2: ...0 or the current Standard of Fire Safety Criteria for Manufactured Home Installations Sites and Communities ANSI NFPA 501A and with CAN CSA Z240 MH Mobile Home Standard in Canada This appliance instal...

Page 3: ...re You Start 6 General Safety Information 6 Manufactured Mobile Home Additional Requirements 6 Installation Checklist 7 Locating Your Fireplace 7 Unit Dimensions 7 Duct System Option 7 Combustible Man...

Page 4: ...if there is a difference the label on the unit is the correct one SAFETY LABEL For the State of Massachusetts installation and repair must be done by a plumber or gas tter licensed in the Commonwealth...

Page 5: ...de directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VE...

Page 6: ...electrical wiring locations in walls and ceilings when cutting holes for termination 11 Under no circumstances should this appliancebemodi ed Partsthathavetobe removed for servicing should be replace...

Page 7: ...and operation fully explained to customer This includes 1 Clockingtheappliancetoensurethecorrect ring rate rate noted on label after burning appliance for 15 minutes 2 Ifrequired adjustingtheprimaryai...

Page 8: ...lated res is failure to maintain required clearances air space to combustible materials It is of the greatest importance that this replace and vent system be installed only in accordance with these in...

Page 9: ...nt to combustible material cannot be maintained 2 Frame in the enclosure for the unit with framing material FRAMING AND FINISHING 16 1 2 419mm Minimum 4 102mm 3 76mm 1 1 2 38mm 30 762mm 10 254mm dia H...

Page 10: ...ount Side Nailing Strip using the 3 supplied screws into the three pre punched screw holes at the front sides of the unit Adjust support to desired facing material thickness UNIT ASSEMBLY PRIOR TO INS...

Page 11: ...m horizontally from the centerline of the regulator J Clearance to service regulator vent outlet min 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to a...

Page 12: ...erminal Locations Section Regency Direct Vent Flex Termination Kit Part 946 513 includes all the parts needed to install the P33 4 with a maximum run of 2 feet If installing the P33 with a continuous...

Page 13: ...trips 3 Assemble the vent assembly by applying Mill Pac to the 4 100mm inner collar of the terminationand slippingthe4 100mm liner over it at least 1 3 8 35mm Fasten with the3screws drillingpilotholes...

Page 14: ...nches Flat Wall Installation Max Wall Vent Length Thickness inches Required inches 7 1 4 6 10 1 4 9 13 1 4 12 12 1 4 15 7 8 11 14 5 8 Adj Pipe 18 1 4 25 1 4 11 14 5 8 Adj Pipe Alternate Horizontal Ter...

Page 15: ...46DV 08AB 911B 4DT AJB N A N A N A Adjustable Length 17 24 Galvanized Disc See 46DV 16A 917 N A from FPI N A N A N A N A Adjustable Length 17 24 Black Disc See 46DV 16AB 917B N A N A N A SV4LBA24 Adj...

Page 16: ...A N A N A N A Mansonry Chimney Conversion Kit includes Cap Adapter 18 x18 Flashing 46DVA KCT 935 N A N A N A N A Wall Firestop 46DVA WFS 947 N A N A N A N A Colinear Flex Connectors 46DVA ADF 923F N...

Page 17: ...s to combustibles Note Must use optional rigid pipe adapter when using rigid vent systems Part 510 994 RIGID PIPE VENTING ARRANGEMENTS Vertical Terminations Propane Natural Gas The shaded area in the...

Page 18: ...as The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations with rigid pipe vent systems for Propane and Natural Gas Maximum two 45o elb...

Page 19: ...zontal vent must be supported every 3 feet Firestops are required at each oor level and whenever passing through a wall A vent guard should be used whenever the terminationislowerthanthespeci edminimu...

Page 20: ...8 Max One 90o elbow Two 45o elbows Option H V H H1 H2 With these options maximum total pipe length is 30 feet with minimum of 11 feet total vertical and maximum 9 feet total horizontal P l e a s e n...

Page 21: ...B 3 Min 2 Max 4 Min 5 Max C 4 Min 3 Max 6 Min 6 Max D 5 Min 4 Max 8 Min 7 Max E 6 Min 5 Max 10 Min 8 Max F 7 Min 6 Max 12 Min 9 Max One 90o elbow Two 45o elbows Option V H V V1 With these options max...

Page 22: ...5o elbows One 90o elbow Two 45o elbows With these options max total pipe length is 30 feet with min of 11 feet total vertical and max 7 feet total horizontal Please note min 1 foot between 90o elbows...

Page 23: ...Parts Part Description 946 529 Co linear DV Vertical Termination Cap 948 305 3 Flex 35 ft 946 563 Co Axial to Co Linear Adapter Kit which contains the following Co linear Flex Adapter Outer Pipe Inne...

Page 24: ...AL TERMINATIONS with Co linear Flex System for both Residential Manufactured Homes into Masonry Fireplaces The shaded area in the diagrams show the allowable vertical terminations INSTALLATION 8 2 4m...

Page 25: ...e unit in its desired location Check to determine if wall studs or roof rafters are in the way when the venting system is attached If this is the case you may want to adjust the location of the unit R...

Page 26: ...venting system it is highly recommended to apply Mill Pac sealant supplied to every in ner pipe connection Failure to do so may result in drafting or performance issues not covered under warranty Sili...

Page 27: ...STALLATION Incorrect ame pattern will have small probably yellow ames not coming into proper contact with the rear burner or thermopile or thermocouple HIGH ELEVATION This unit is approved in Canada f...

Page 28: ...ce Installation of the LPG Conversion Kit 1 Shut off the gas supply 2 P33 4 Only a Remove the louvers and bay door if it is installed b Open the ush door and remove the door c Remove the logs embers...

Page 29: ...en wrench as shown in Fig 4 rotate the screw clockwise until snug do not overtighten 13 Verify that if the conversion is from NG to LPG the screw must be re assembled with the red o ring visible Fig 5...

Page 30: ...is not too hot and is easy to reach for changing the battery Note It should be kept away from the chain 14 Tie up the loose wire with the wire clip Ground wire from kit Chain 1 Locate the Piezo Ignito...

Page 31: ...instructionsbelowcarefully and refer to the diagrams If logs are broken do not use the unit until they are replaced Broken logs can interfere with the pilot operation Log Kit 431 930 contains the foll...

Page 32: ...m on the front of the burner tray in the places shown in the photo below Do not compress the rock wool leave it loose Separate platinum embers and place them on the front of the burner on and around t...

Page 33: ...Diagram 2 Note Top and bottom louvers are different 3 Open the bottom louver Pull the Burner ON OFF control box from inside the bottom of the replace and position the slots in the bracket over the 2...

Page 34: ...stall top louver by sliding the two bracket clips into the brackets located on top of the bay door See below The tted louver leaves a small gap between faceplate bottom and louver top Bay Louver Top H...

Page 35: ...n the inside top of the outer frame of the appliance Also remove the center screw b Slide the cut outs in the Top and Bottom Flange of the Full Screen Door Frame under the screw heads which were loose...

Page 36: ...pping Phillips screws provided Bottom Grill Hinge Location 7 Mount the Burner ON OFF Control Box to the left side of the Bottom Grill using 2 x 8 1 4 Philips Head Screws Burner ON OFF Control Box Left...

Page 37: ...roved may be used CAUTION Do not wire millivolt wall thermostat wires to 120V wire Thermostat Wire Table Optional REMOTE CONTROL UsetheRegency RemoteControlKit approved for this unit Use of other syst...

Page 38: ...tat will continue to operate However a 120V A C power supply is needed for the fan blower operation Do not cut the ground terminal off under any circumstances NOTE Even if the fan is not purchased wit...

Page 39: ...and are away from sharp edges CAUTION Labelallwires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation INSTALLATION For PROPANE Units and Units Equ...

Page 40: ...and 1 screw on the right side Secure left side with 2 screws Secure right side with one screw Secure the 2 boxes together with one screw Hold control box assembly in place and mark the position of the...

Page 41: ...Regency P33 4 Zero Clearance Direct Vent Gas Fireplace 41 OPERATING INSTRUCTIONS COPY OF THE LIGHTING PLATE INSTRUCTIONS Gas Inlet OFF Gas Inlet...

Page 42: ...all wiring is correct and enclosed to prevent possible shock 3 Check to ensure there are no gas leaks 4 Make sure the glass in the door frame is properly positioned Never operate the appliance with th...

Page 43: ...Also check mechanical supports such as Wall Straps or plumbers tape for rigidity GOLD PLATED or BRASS LOUVERS TRIM The 24 carat gold plated or brass nish on the louvers and trim requires little mainte...

Page 44: ...Do not use abrasive materials Do not clean the glass when hot In the event that you break your glass by impact purchase your replacement from an authorized Regency dealer only and follow our step by...

Page 45: ...16 wrench 7 Scrape off the old gasket from the oor of the rebox and from the valve tray assembly 8 Install a new gasket and reinstall the valve tray assembly Note Failure to install a new gasket may s...

Page 46: ...Right Side 36 Brick Panel Top 37 430 056 Brick Clip Top 38 430 057 Brick Clip Bottom 432 917 Fan Assembly 120 Volts Optional 42 910 331 P Fan Motor 120 Volts 432 966 Fan Switch Assy 120 Volts 43 910...

Page 47: ...Regency P33 4 Zero Clearance Direct Vent Gas Fireplace 47 PARTS LIST...

Page 48: ...57 910 478 S I T Valve NG LP 58 Valve Bracket 59 Firebox Base 60 Valve Tray 66 910 038 Pilot Assy 3 way ame S I T NG 910 039 Pilot Assy 3 way ame S I T LP 904 568 Ori ce 44 Natural Gas 904 163 Ori ce...

Page 49: ...ver Assy Bottom 433 538 Flush Door Assembly Complete 135 940 088 P Glass Flush 137 904 691 U Clip 139 936 155 Glass Gasket Tadpole 140 948 042 Spring Hinge Black 430 940 Finishing Trim Set Black Optio...

Page 50: ...P Center Glass 110 Bay Door Frame 112 Bay Brick Panel Spacer 117 904 196 Magnet 1 round 118 Louver Hold Down 120 400 189 Glass Retainer 432 956 Bay Door Trim set Gold 123 Bay Door Trim each Black 430...

Page 51: ...agent Transportation Prepaid if requested Porcelain Enamel Absolute perfection is either guaranteed nor commercially possible Any chips must be reported and inspected by an authorized dealer within t...

Page 52: ...al No __________________________________________________________ Printed in Canada Regency replace products are designed with reliability and simplicity in mind In addition ourinternalQualityAssurance...

Reviews: