14
Regency GF950L Gas Fireplace
CLEARANCES FOR NON-COMBUSTIBLE FLUSHED FINISHING WITH MANTEL
Due to the extreme heat this fireplace emits, the mantel
clearances are critical.
Combustible mantel clearances from top of front facing are shown
in the diagram on the right.
Note:
For a flushed finish using non-combustible finishing, seven
13mm stand-off tabs around the fireplace opening must be broken
off. The top nailing flange cannot be used and a non-combustible
steel stud must be installed to support the non-combustible facing.
Note: Ensure the paint that is used on the mantel and the
facing is "high quality" or the paint may discolour.
NON COMBUSTIBLE MANTEL LEG CLEARANCES
Mantel leg & Non-combustible finishing clearances as per diagram: (Flushed Finish)
Allowablemantel
leg projection
181mm
254mm
330mm
38mm
MANTELLEG
102mm
178mm
Allowablemantel
leg projection
181mm
254mm
330mm
38mm
MANTELLEG
102mm
178mm
Allowablemantel
leg projection
181mm
254mm
330mm
38mm
MANTELLEG
102mm
178mm
83mm
Non-combustible
83mm
Non-combustible
Combustible Material
(152mm)
(305mm)
0
To Uni
t
Base
(605mm)
(254mm)
Top of
Fireplace
Opening
(508mm)
(305mm)
(420mm)
(191mm)
Non-Combustible facing (min.12mm)
Non-Combustible steel stud
(152mm)
756mm to underside
of steel stud
(100mm)
(247mm)
(200mm)
(322mm)
installation