background image

57

Regency Bellavista™ B41XT Gas Fireplace

MAINTENANCE

3)

  Check for evidences of excessive 

condensation, such as water droplets forming 
in the inner liner, and subsequently dripping 
out the joints, Continuous condensation can 
cause corrosion of caps, pipe, and fi ttings. 
It may be caused by having excessive 
lateral runs, too many elbows, and exterior 
portions of the system being exposed to 
cold weather.

4)

  Inspect joints, to verify that no pipe 

sections or fi ttings have been disturbed, 
and consequently loosened. Also check 
mechanical supports such as Wall Straps, 
or plumbers' tape for rigidity.

LOG REPLACEMENT

The unit should never be used with broken logs. 
Turn off the gas valve and allow the unit to cool 
before opening door and carefully remove the 
logs. (The pilot light generates enough heat to 
burn someone.) If for any reason a log should 
need replacement, you must use the proper 
replacement log. The position of these logs 
must be as shown in the diagrams under Log 
Installation.

Note:  Improper positioning of logs may 

create carbon build-up and will 
severely alter the unit's performance 
which is not covered under 
warranty.

THERMOPILE / 

THERMOCOUPLE

1)  Open the Bottom Louvers or Grills. Remove 

the Top Louver or Grill.

2)  Remove the Trim Kit, Glass Door, Log 

Set, Grate and Burner Assembly (see the 
"Log Installation" & "Glass Door Removal" 
sections).

3)  Disconnect thermocouple by loosening 

nut from the valve with a 9mm wrench. 
Disconnect thermopile by loosening 2 
screws marked TP on the valve.

4)  Remove 2 screws from the pilot assembly 

and pull up far enough to be able to loosen 
the thermocouple or thermopile with a 7/16" 
wrench. NOTE: the pilot line is very fragile, 
use caution when pulling it up.

5)  Drop the thermocouple or thermopile down 

through the extrusion and pull it out of the 
unit.

6)  Reinstall the new ones in reverse order.

GLASS GASKET

 
If the glass gasket requires replacement use a 
tadpole glass gasket (Part # 936-155). 
  

DOOR GLASS

Your Regency

®

  fi replace is supplied with high 

temperature 5mm-Ceramic glass. If your glass 
requires cleaning, we recommend using an 
approved glass cleaner available at all authorized 
dealers. Do not use abrasive materials.

CAUTION & WARNINGS:

*  Do not clean when the glass is hot.
*  The use of substitute glass will void all  
    product warranties.
*  Care must be taken to avoid breakage of  
    the glass.
*  Do not strike or abuse the glass.
*  Do not operate this fi replace without the  
   glass front or with a cracked or broken  
   glass front.
*  Wear gloves when removing damaged or  
   broken glass.
*  Replacement of the glass panels should be  
   done by a licensed or qualifi ed service per 
   son.

GLASS REPLACEMENT

In the event that you break your glass by impact, 
purchase your replacement from an authorized 
Regency dealer only. Replacement glass (Part 
#940-362/P) is shipped already installed into 
the door frame. Reinstall as per Glass Door 
Installation in the "Glass Door Removal" section.

MAINTENANCE 

INSTRUCTIONS

1)

  Always turn off the gas valve before cleaning. 

For relighting, refer to lighting instructions. 
Keep the burner and control compartment 
clean by brushing and vacuuming at least 
once a year. When cleaning the logs, use a 
soft clean paint brush as the logs are fragile 
and easily damaged.

2)

  Clean appliance and door with a damp 

cloth (never when unit is hot).  Never use 
an abrasive cleaner. The glass should be 
cleaned with a gas fi replace glass cleaner. 

The glass should be cleaned when it starts 
looking cloudy.

3)

  The heater is fi nished in a heat resistant 

paint and should only be refi nished with heat 
resistant paint. Regency

®

 uses StoveBright 

Paint - Metallic Black #6309.

4)

  Make a  periodic check of burner for proper 

position and condition. Visually check the 
fl ame of the burner periodically, making sure 
the fl ames are steady; not lifting or fl oating. 
If there is a problem, call a qualifi ed service 
person. 

5)

  The appliance and venting system must be 

inspected before use, and at least annually, 
by a qualifi ed fi eld service person, to ensure 
that the fl ow of combustion and ventilation 
air is not obstructed.

Note:  Never operate the appliance without 

the glass properly secured in place.

6)

  Do not use this appliance if any part has been 

under water. Immediately call a qualifi ed 
service technician to inspect the appliance 
and to replace any part of the control system 
and any gas control which has been under 
water.

7)

  In the event this appliance has been serviced 

check that the vent-air system has been 
properly resealed & reinstalled in accordance 
with the manufacturer's instructions.

8)

  Verify operation after servicing.

General Vent Maintenance

Conduct an inspection of the venting system 
semi-annually. Recommended areas to inspect 
as follows:

1)

  Check the Venting System for corrosion in 

areas that are exposed to the elements. These 
will appear as rust spots or streaks, and in 
extreme cases, holes. These components 
should be replaced immediately.

2)

  Remove the Cap, and shine a fl ashlight down 

the Vent. Remove any bird nests, or other 
foreign material.

DC SPARKER BATTERY 

REPLACEMENT

1)

  Remove the battery cover from the DC 

Sparker - remove  the AA battery.

2)

  Replace with a new 'AA' battery and reinstall 

battery cover.

Summary of Contents for Bellavista B41XT

Page 1: ...any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department FPI FIREPLACE PRODUCTS INTERNATIONAL LTD 6988 Venture St Delta BC Canada V4G 1H4 918 810a 12 14 11 Owners Installation Manual Tested by Installer Pleas...

Page 2: ...ood fireplace at the flick of a switch The Bellavista B41XT has been approved by Warnock Hersey Intertek for both safety and efficiency As it also bears our own mark it promises to provide you with economy comfort and security for many trouble free years to follow Please take a moment now to acquaint yourself with these instructions and the many features of your Regency Fireplace Bellavista Benefi...

Page 3: ...n instructions and local codes if any In the absence of local codes follow the current National Fuel Gas Code ANSI Z223 1 and the current National Electrical Code ANSI NFPA 70 in the U S A and the current CAN CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22 1 in Canada This appliance comes equipped with a dedicated 8 Ground Lug for attachment of the ground wire to th...

Page 4: ...30 Unit Installation with Horizontal Termination 31 5 x 8 venting 31 Unit Installation with Horizontal Termination 32 5 x 8 venting 32 Unit installation with Vertical Termination 33 5 x 8 venting 33 Gas Line Installation 33 Pilot Adjustment 34 High Elevation 34 Gas Pipe Pressure Testing 34 S I T Valve Description 34 Brick panel installation 35 Optional panel installation 36 Log set installation 38...

Page 5: ...tubulure d chappement lev e Pression à la tubulure d chappement basse Grandeur de l injecteur D bit minimum selon D bit maximum selon l altitude Calorifique Calorifique é é é é é é 11 2 74kPa 10 2 49kPa 6 4 1 60kPa 49 DMS 0 4500 ft pi 0 1372 m WC C E WC C E WC C E 29 500 Btu h 8 65 kW 37 500 Btu h 10 99 kW Minimum supply pressure Manifold pressure high Manifold pressure low Orifice size Minimum in...

Page 6: ...ctly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspect...

Page 7: ...NS UNIT DIMENSIONS 46 11 16 1186mm 38 3 16 970mm 41 11 16 1059mm 43 1092mm 35 889mm 49 3 16 1249mm 41 5 8 1057mm 36 11 16 932mm 38 7 8 987mm 24 610mm 36 3 8 924mm 22 5 16 567mm 19 7 16 494mm 1 25mm 23 1 4 591mm 13 3 16 335mm 28 1 2 724mm 38 1 2 978mm ...

Page 8: ...APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING BEDDING MATERIAL ETC IT IS IMPERATIVE THAT CONTROL COMPARTMENTS BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN DUE TO HIGH TEMPERATURES THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITU...

Page 9: ... Finishing section e VentingRequirements Referto Venting section 2 Assemble Top Standoffs and Top Facing Support and Side Nailing Strips Refer to Unit AssemblyPriortoInstallation Section Note Mustbedonebeforeinstallingunitinto place 3 Install vent Refer to Venting sections 4 Install 1 AA battery into the DC Sparker Note Pilot cannot be lit without battery in place 5 Makegasconnections Testthepilot...

Page 10: ...ir space to combustible materials It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions E B C D F A B41XT Clearance Requirements Minimum Vent Clearances to Combustibles Clearance Dimension Measured From A Mantel Height min 24 610mm Top of Fireplace Opening B Sidewall 12 1 2 318mm one side only Side of Fireplace Opening C Ceilin...

Page 11: ...rances from top of front facing are shown in the diagram on the right Note A non combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non combustible board Mantel Clearances B41XT A B C D From Top of Fireplace Opening 35 1 4 895mm 32 1 4 819mm 28 1 2 724mm 24 610mm Combustible 0 Top of Fireplace Opening 12 1 7 A B C Non combustible Header steel...

Page 12: ... 1 2 89mm 48 3 4 1238mm Non combustible 41 3 4 1060mm Non combustible Material Non combustible Header steel stud on edge 47 1 4 1200mm Framing 36 3 4 933mm Min 3 1 2 89mm Non combustible Non combustible INSTALLATION 12 1 2 Side Wall Measured from side of Fireplace Opening 7 4 Mantel leg Mantel leg Allowable mantel leg projection 3 1 1 2 Top View ...

Page 13: ...ear Vent 23 1 4 591mm O Top Vent Framing Depth Top Vent 22 5 8 575mm P Corner Facing Wall Width 60 1 4 1530mm Q Corner Facing Wall Width 85 3 16 2163mm R Rear Vent Framed Chase Ceiling Rear 49 1 2 1257mm R Top Vent Framed Chase Ceiling Top 54 1 2 1384mm S Rear Vent Vent Centerline Height Rear 28 1 2 724mm S Top Vent Vent Centerline Height Top 47 1 2 1207mm Rigid Flex T Gas Connection Height 1 1 2 ...

Page 14: ...ges the sides and top of the firebox opening Full Screen Doors Only If finishing with any material thicker than 1 1 4 a 3 4 gap must be maintained between the full screen doors and the finishing material This gap is necessary to facilitate the installation and removal of the full screen doors Note All non combustible facing material should butt up cleanly to the flanges around the firebox opening ...

Page 15: ...finished surface to be flush with the front of the unit Total facing thickness can vary from 1 2 13mm to 1 1 4 32mm thick The Top Facing Support can be mounted in 3 different positions depending on the thickness of the facing material 1 Mount Top Facing Support using the 3 supplied screws into the three pre punched screw holesonthetopfrontoftheunit UseholepositionsA B orCdependingonyourfacingdepth...

Page 16: ...te Cover 1 Insulation Filling 1 Remove the door by releasing the spring hooks at the bottom and lifting the door up off the door frame 2 From inside the firebox remove the baffle plate by removing 4 screws remove top front screw first Baffle Plate 3 From the inside of the firebox remove the exhaust assembly by removing the 10 screws 5 From the outside top of the firebox remove top insulation cover...

Page 17: ...all screws are tight but do not over tighten All 4 screws must be used 13 Set vent restrictor accordingly see next page 14 From inside the firebox re install the baffle plate from step 2 11 From the outside top of the firebox install the intake collar as sembly Secure with 4 1 4 x 1 2 screws Ensure all screws are tight but do not over tighten All 4 screws must be used Intake Collar Assembly Exhaus...

Page 18: ... 2 screws Ensure all screws are tight but do not over tighten See diagram 2 SET 3 THIS HOLE SETS THE VENT RESTRICTOR AT 1 1 2 SET 2 THIS HOLE SETS THE VENT RESTRICTOR AT 2 1 2 SET 1 THIS HOLE SETS THE VENT RESTRICTOR AT 3 1 2 NO VENT RESTRICTOR Factory setting Baffle Plate Diagram 3 Diagram 1 VENTING INTRODUCTION The B41XT uses the balanced flue technology Co Axial system The inner liner vents pro...

Page 19: ... line extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 30cm 9 23cm L Clearance to a mechanical air supply inlet 3 91cm above if within 10 3m horizontally 72 1 8m 36 90cm b M Clearance above paved sidewalk or a paved driveway located ...

Page 20: ... 58DVA CS 5DT CSS 5DRS TE 5DE45B Wall Support Band 58DVA WS 5DT WS B 5DWS N A Offset Support 58DVA ES N A from FPI 5DT OS N A N A Wall Thimble Black 58DVA WT 5DT WT 5DWT TE 5DE90 Wall Thimble Support Ceiling Support 58DVA DC N A from FPI N A N A TE 5DE90B Firestop Spacer 58DVA FS 5DT FS 5DFS N A Trim Plate Black 58DAV WFS 5DT TP 5DCP N A Description Simpson Direct Vent Pro Selkirk Direct Temp Meta...

Page 21: ...impson Direct Vent Vent Guard Optional 946 623 P AstroCap XL Horizontal Cap 770 994 Rigid Pipe Adaptor Must use with all rigid piping 946 506 P Vent Guard Optional 946 606 Starter collar reducer 5 x 8 to 4 x 6 5 8 946 625 Vinyl Siding Standoff AstroCap XL Note When using Metal Fab Sure Seal Rigid Piping please note that the Adaptor 4DDA must be used in conjunction with FPI Rigid Pipe Adaptor 510 9...

Page 22: ...0 6 4 8 Vertical Height Feet Rigid or Flex 47 1 2 1 2m Horizontal Feet Max 36 0 9m 2 0 6 4 8 2 0 6 4 8 Vertical Height Feet 28 1 2 0 7m Horizontal Feet Max 36 0 9m Vent Restrictor Set 1 Factory Setting No Restrictor Required VENTING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS FLEX VENT OR RIGID PIPE 5 X 8 REAR VENTING DEFLECTOR INSTALLATION FOR REAR VENTED HORIZONTAL TERMINATIONS Rear Venting Deflect...

Page 23: ...p or rear vent Notes 1 Liner sections should be continuous without any joints or seams 2 Only Flex pipe purchased from Regency may be used for Flex installations 3 Regency Direct Vent System Flex is only approved for horizontal terminations NOTE If longer runs are required the FPI Direct Vent system Flex 946 616 includes all parts needed to install the B41XT with a maximum 10 run FPI Kit Length Co...

Page 24: ...p Wall Thimble Vinyl Siding Standoff Optional Horizontal Termination A Top Vent No Vertical Rise When venting with a 90 elbow directly off the unit Flex vent or approved Rigid Vent System Max 3 ft horizontal run B Rear Vent w Horizontal Termination Max 3ft horizontal run B A HORIZONTAL TERMINATIONS RIGID PIPE 5 X 8 IMPORTANT Must use Rear Venting Deflector packaged with unit in rear vent horizonta...

Page 25: ...2 Includes 1 AstroCap XL 946 623 P 1 Rigid Pipe Adaptor 770 994 1 Vinyl Siding Standoff Optional 946 625 1 Wall Thimble 58DVA WT 1 6 Galvanized Rigid Pipe 58DVA 06 1 8 1 2 Galvanized Pipe Extension 58DVA 08A 1 45º Galvanized Elbow 58DVA E45 1 90ml MillPac 948 128 28 1 2 724mm Placement of the Unit into the Corner Back Top Corner of Unit to Wall 3 Inside Corner out along the Wall 60 1 4 Across the ...

Page 26: ...ARRANGEMENTS FOR HORIZONTAL TERMINATIONS The diagram shows all allowable combinations of vertical runs with horizontal terminations using one 90o two 45o elbows equal one 90o elbow Maintain clearances to combustibles as listed in Clearances section Horizontal vent must be supported every 3 feet Firestops are required at each floor level and whenever passing through a wall A wall thimble is mandato...

Page 27: ...ace of wall without siding and add 2 inches When using Rigid Vent other than Simpson Dura Vent 3 screws must be used to secure rigid pipe to adaptor The FPI AstroCap XLTM is certified for installations using FPI venting systems as well as Simpson Dura Vent Direct Vent Pro ICC Excel and Selkirk Direct Temp AstroCap XLTM is a proprietary trademark of FPI Fireplace Products International Ltd Dura Ven...

Page 28: ...igid pipe adaptor 770 994 No Vent Restrictor Installed 8 Max HORIZONTAL TERMINATIONS THREE 3 90O ELBOWS RIGID PIPE 5 X 8 77 7 77777M V1 H1 H V With these options max total pipe length is 30 feet with min of 12 feet total vertical and max 9 feet total horizontal Please note min 1 foot between 90o elbows is required Lengths do not include elbow indicated Must use rigid pipe adaptor 770 994 Option V ...

Page 29: ...ver passing through a wall Maintain clearances to combustibles as listed in the Clearances section Refer to the Vent Restrictor Position section for details on how to change the vent restrictor from the factory setting to 3 1 2 opening 2 1 2 opening and to 1 1 2 opening Note Must use optional flue adapter when using Rigid Pipe Part 770 994 Minimum 8 2 4m Min 47 1 2 1 2m 0 2 4 6 40 8 10 12 14 16 18...

Page 30: ...6 Min E 4 Min 5 Max 7 Min F 5 Min 6 Max 8 Min G 6 Min 7 Max 9 Min H 7 Min 8 Max 10 Min With these options max total pipe length is 30 feet with min of 10 feet total vertical and max 8 feet total horizontal Please note min 1 foot between 90o elbows is required One 90o elbow Two 45o elbows Lengths do not include elbow indicated Must use rigid pipe adaptor 770 994 No Vent Restrictor Installed INSTALL...

Page 31: ...r screws through the top and side nailing strips Diagram 1 Note For best results and optimum performance with each approved venting system it is highly recommended to apply Mill Pac sealant supplied to every inner pipe connection Failuretodosomayresult in drafting or performance issues not covered under warranty Silicone red RTV is optional Diagram 2 Horizontal runs of vent must be supported every...

Page 32: ...he tabs are on top and bottom Fasten the other thimble half to the inside wall The thimble halves slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls 5 Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up there are markings on the cap that show which wayis up This will position the termination cap with proper down slope for ...

Page 33: ...ame the hole as shown in Diagram 2 and install the firestop NOTE Forbestresultsandoptimumperform ance with each approved venting system it is highly recommended to apply Mill Pac sealant supplied toeveryinnerpipeconnec tion Failure to do so may result in drafting or performance issues not covered under warranty Silicone red RTV is optional 4 Assemble the desired lengths of pipe and elbows Ensure t...

Page 34: ... over tighten Incorrect flame pattern will have small probably yellow flames not coming into proper contact with the rear burner or thermopile or thermocouple HIGH ELEVATION This unit is approved in Canada for altitude to 4500ft CAN CGA 2 17 M91 ForNaturalGas installations above 4500 ft follow current CAN CGA B149 1 PILOT ADJUSTMENT Periodically check the pilot flames Correct flame pattern has thr...

Page 35: ...place and secure with the brick panel clip and screw removed from the firebox as shown below 6 Slide the top brick panel under the left or right side panel which ever is installed first right side panel shown here and back brick panel use care not to damage panel Left Panel Right Panel Back Panel Top Panel Back Panel Installed 7 Install the remaining side panel left or right following the same ins...

Page 36: ...ring normal operation This is normal and should not be considered a defect All hand and finger marks MUST be cleaned off with a soft cloth and a stainless steel cleaner Most stainless steel cleaners leave a film residue on the surface of the panels Use an ammonia based cleaner ie glass cleaner to remove this film before applying heat to the unit Failure to do this will result in burn stains on pan...

Page 37: ... hex head screw A B 6 Install left side panel repeat step 4 5 Slide top panel under the top of the back and right side panels as shown below Top panel bracket shown installed with Stainless Steel Panels 7 Carefully position and fit the top bracket in place by ensuring the tabs of the bracket fit into the baffle openings as shown below Push downwards to secure the bracket to the top panel INSTALLAT...

Page 38: ...ces A Rear Bottom Right Log B Rear Top Left Log C Right Top Cross Log D Front Log Piece E Left Top Cross Log F Center Right Log G Front Bottom Left Log H Front Bottom Right Log I Center Left Log 902 156 Lava Rocks 902 179 Vermiculite 946 669 Platinum Embers supplied w packaged manual 1 Carefully remove the logs from the packaging and unwrap them The logs are fragile handle with care do not force i...

Page 39: ... shown below 8 Slide the left side of Log G back until it touches the tab on the burner shown below 10 Slide the right side of Log H back until it touches the tab on the burner shown below I G H 9 Place Log H on the right front side of the burner in front of log F Position Log G so it fits into the pin on the burner as shown below There is a notch on the bottom of log H position the log so the not...

Page 40: ...shown below 13 Position Log B on top of Log A Log B fits into the pin in Log A Ensure Log B sits upright 90 degrees with the left side of the log resting on the notch in Log E See next 2 diagrams 14 Position Log C on top of Log H Log C fits into the pin in Log H as shown below E G E A A B C 15 With Log C in position on Log H assure that Log C contacts the back corner of Log A as shown below C A E ...

Page 41: ... Separate platinum embers and place on the front burner on and around the lava rocks Avoid stacking platinum embers Platinum embers may be placed over burner ports IMPORTANT Do not cover burner ports with lava rocks as this will change the flame pattern Extra Lava Rocks 16 Place the lava rocks on the burner in front of the logs as shown below Be careful not to overlap the lava rock and ensure the ...

Page 42: ...ControlKit approved for this unit Use of other systems may void your warranty The remote control kit comes with a hand held transmitter a receiver and a wall mounting plate 1 Choose a convenient location on the wall to install the receiver and the receptacle box protection from extreme heat is very important Run wires from the fireplace to that location Use Thermostat Wire Table 2 Connect the two ...

Page 43: ...sing 4 Connect the Black wire to the left side terminal of the fan motor Slide the black wire and the green ground wire into grommet and push grommet into the fan assembly housing 5 Connect the Red wire onto the right side terminal of the fan motor Connect the red wire into the grommet and push grommet into the fan assembly housing BLACK RED 6 Position the fan base with the motor end towards the r...

Page 44: ...s and power cord by attaching one of the adhesive backed wire holder clips Part 910 199 onto the unit base TO REMOVE THE FAN 1 Turn the power off 2 Reverse the above instructions Maintenance The sealed bearings are lubricated there is no need to lubricate them further Extra lubricant will cause more lint and dust buildup causing the bearings to prematurely fail Regular cleaning and vacuuming of th...

Page 45: ...se of a power failure the burner switch and the optional remote control thermostat will continue to operate However a 120V A C power supply is needed for the fan blower operation Proflame GTMF and light options Do not cut the ground terminal off under any circumstances NOTE Even if the fan GTMF system or light options are not purchased with the unit it is still a good idea to bring power to the re...

Page 46: ...ransmitter Optional ON OFF Regency Remote Receiver or Thermostat Millivolt Optional Brown T Stat Black White S I T Valve Burner ON OFF To THTP To TH To TH White Gas In DC Spark Box Ground Ground Green Neutral Live Black Red Red Minimum Convection Air Temp Switch Ground ON OFF Rotary Speed Control 120V AC 60 Hz Fan Optional Fan WIRING DIAGRAM FOR GTMF REMOTE WIRING DIAGRAM FOR NG AND LP UNITS 2 ft ...

Page 47: ...uded Feature Note 1 Proflame Flame Modulator for GTM GTMF Remote Controls are sold seperately Choice of NG or LP flame modulator to match unit fuel type See Regency Retail Price pages for complete details 1 1 1 Note Regency Proflame systems include a white and black wall cover switch INSTALLATION ...

Page 48: ...wider slot of the polarized receptacle should be at the top A wall mounted switch should be installed to turn the accent lighting on off See wiring diagram in the instruction manual Diagram 1 Remove the left and right screws Diagram 2 Slide burner assembly to the right and then remove 8 Remove the 2 screws securing the rear log tray and lift out Diagram 3 Diagram 3 7 Slide the burner assembly to t...

Page 49: ...to the base tray 16 Secure diffusers onto base tray from the backside of the tray with 2 screws 17 Reinstall base tray with light diffusers use caution when installing do not damage the bulb 18 Install amber glass on to light diffusers Note Glass is longer than diffuser for ease of removal 19 Reverse steps 9 1 NOTE The ground wire will need to be pulled back out of the protective casing to be able...

Page 50: ...he 2 screws to secure in place Finishing Trim Edge of Unit B41XT B36XT W 43 3 8 40 1 2 H 37 5 8 35 3 4 OPTIONAL FINISHING TRIM INSTALLATION Diagram 3 Use the hook to pull the spring out until you can put the hook into the slot on the bottom door bracket Repeat for 2nd spring See Diagram 3 Diagram 2 The standard flush door comes with a black frame To install the frame simply hook the top door flang...

Page 51: ...ket with 2 screws as shown below 3 Flip the hinges down to 90 line up the louver flush panel as shown below 4 Fasten the hinges to the louver flush panel with 3 screws each as shown below 5 Flip up the louver flush panel to close 6 To install the top louver flush panel line up the 2 tabs on the louver flush panel with the corresponding bracket clip on the inside top of the unit see below Location ...

Page 52: ...3 4 3 4 Factory Setting 6 Mountthedoorframeonto4loosenedscrewsfromstep2andretighten Note The door frame is adjustable up by 3 4 to accommodate for finished flooring The door frame can also be adjusted out 3 4 from the unit to accommodate finishing materials See Diagram 4 3 Remove2screwsfrominsidethefireboxinthelocationshownbelow 4 Slide bracket into slot on the back of the full screen door frame S...

Page 53: ... To install the lower screen mesh panel line up the 2 hinges with the brackets in the unit as shown below 7 Secure the bracket installed in Step 4 to the inside of the firebox in the same location and with the same screws from Step 3 10 Attach each hinge to the corresponding bracket with 2 screws as shown below 11 Flip the hinges down to 90 line up the lower mesh screen door as shown below INSTALL...

Page 54: ...ang the screen doors 15 The full screen doors are stabilized by 2 magnets which are attached to a bracket Install the bracket to the flange at the base of the unit using 2 screws There are 2 hole locations on the bracket to accom modate flush wall thicker finishing materials Location of bracket clips in unit Final Screen Door Install Thicker Finishing Screw Location Flush Wall Screw Location INSTA...

Page 55: ...hould be cleaned after the unit has cooled down or the film will bake on and become very difficult to remove Use a non abrasive cleanerandDONOTATTEMPTTOCLEAN THE GLASS WHILE IT IS HOT TheFIRSTFIREinyourheaterispartofthepaint curing process To ensure the paint is properly cured it is recommendedyou burnyourfireplace for at least four 4 hours the first time When first operated the unit will release ...

Page 56: ... the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Forced or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas contr...

Page 57: ...s front Wear gloves when removing damaged or broken glass Replacement of the glass panels should be done by a licensed or qualified service per son GLASS REPLACEMENT In the event that you break your glass by impact purchase your replacement from an authorized Regency dealer only Replacement glass Part 940 362 P is shipped already installed into the door frame Reinstall as per Glass Door Installati...

Page 58: ...am 1 Remove the left and right screws Diagram 2 Slide burner assembly to the right and then remove 8 Remove the 2 screws securing the rear log tray and lift out Diagram 3 Diagram 3 7 Slide the burner assembly to the right to release it from the orifice then lift it out 9 Remove the 2 screws securing the base tray lift base tray up and out Diagram 4a and 4b Diagram 4a Diagram 4b 10 Replace the bulb...

Page 59: ...he wall switch wires from the valve see Diagram 6 Diagram 5 Diagram 4a Diagram 4b Diagram 3 Diagram 6 Diagram 7 Diagram 8 INSTALLING VALVE 1 Placenewvalvetrayandgasketintoposition 2 Reinstall the 14 hold down screws 3 Hook up the 2 TP and 2 TH wires to the ap propriate connections on the valve 4 Reinstall the rear log tray 5 Install burner grate assembly 6 Hook up the gas line and check for gas le...

Page 60: ... Assembly Part Description 18 506 917 Fan Assembly 19 910 215 P Fan Motor 120 Volts 432 966 Fan Switch Assy 120 Volts 20 910 813 Power Cord 120 Volts 21 910 330 Fan Speed Control 22 904 586 Knob Speed Control 23 910 142 Thermodisc Fan Auto ON OFF 24 946 000 Round Duct Adaptor 25 910 367 Box Plastic Switch Receptacle 26 910 412 Fan Speed Controller 27 910 417 Knob White 28 910 366 Switch Cover Plat...

Page 61: ... High Low 820 7 506 072 Valve Shield 8 506 071 Valve Mounting 9 506 055 Valve Tray Plate 10 506 075 Air Deflector 11 380 013 Pilot Holder Extruded 12 910 038 Pilot Assembly NG 910 039 Pilot Assembly LP 910 386 Thermocouple 910 341 Thermopile Part Description 904 660 Orifice 30 NG 904 431 Orifice 49 LP 506 574 P Valve Assembly NG 506 576 P Valve Assembly LP 506 003 Valve Assembly Gasket 15 506 062 ...

Page 62: ... Black 506 926 Louvers Set Steel Black 3 506 916 Black Flush Panels Set 4 506 901 Brick Panels Standard Brown 506 902 Brick Panels Standard Red 506 905 Brick Panels Standard Cinder Gray 5 506 907 Inner Panels Brushed Stainless Steel 506 908 Inner Panels Black Enamel 6 506 980 Full Screen Doors Black 506 982 Full Screen Doors Midnight Grey 506 984 Full Screen Doors Midnight Brown ...

Page 63: ...ent Transportation Prepaid if requested Porcelain Enamel Absolute perfection is either guaranteed nor commercially possible Any chips must be reported and inspected by an authorized dealer within three days of installation Reported damage after this time will be subject to rejection It is the general practice of FPI to charge for larger higher priced replacement parts and issue credit once the rep...

Page 64: ...__________________________________________________________ Phone ___________________________________________________________ Date Installed ______________________________________________________ Serial No __________________________________________________________ Register your Regency warranty online www regency fire com Reasons to register your product online today View and modify a list of all y...

Reviews: