57
F O R M
DVR
®
2400 and DVR
®
2500 Digital Voltage Regulator
Installation, Operation and Maintenance Manual
SB0056E
Revised
November 2018
Regal Beloit America, Inc.
100 East Randolph Street
Wausau, WI 54402-8003
www.regalbeloit.com/Brands/
Marathon-Generators
Is Aux Input Type
correct?
If Aux Input is
used, check Input
Type for correct
setting (e.g. 4-20
mA); Turn off Aux
Input if not needed
Are UP/DOWN
contact inputs
influencing set
point?
Monitor Contact
Offset; Adjust as
necessary
Monitor Droop
Offset; Set Droop
to 0% if not
needed
Is Droop function
influencing set
point?
Are PT (if used)
correct?
Check the regulator for PT
Ratio setting and
adjust as
necessary. Check
PT polarity.
GENERATOR VOLTAGE NOT
MATCHING SET POINT
Does the
regulator
“Frame Size”
setting match
generator?
Inspect the regulator
setting. Change to
agree with
generator if
necessary
Is Aux Input
influencing set
point?
Monitor Aux Input
Offset; Turn off
Aux Input if not
needed
yes
check
check
check
check
check
TROUBLESHOOTING FLOWCHART
GENERATOR VOLTAGE
NOT STABLE
Is Aux Input
influencing set
point?
Monitor Aux Input
signal source for
stability; Turn off
Aux Input if not
needed
check
DROOP CONTROL OR VAR/PF
REGULATION NOT WORKING
Are PT (if used)
correct?
Check the regulator for PT
Ratio setting and
adjust as necessary.
Check PT polarity.
check
Is CT ratio correct?
Check the regulator for CT
Ratio setting and
adjust as
necessary
check
Is CT polarity
correct?
Check physical
markings on CTs or
compare DVRPortal
TM
software
power meter with known kW.
Correct as necessary.
See Figs. 4-7, 4-8, 4-9
check
yes
yes
yes
yes
no
no
no
Use HMI or
DVRPortal
TM
software
Visual Check / Use
DVRPortal
TM
software
Visual Check / Use
DVRPortal
TM
software
Use DVRPortal
TM
software
Use DVRPortal
TM
software
Use DVRPortal
TM
software
Use DVRPortal
TM
software
Visual Check / Use
DVRPortal
TM
software
Visual Check / Use
DVRPortal
TM
software