Regada ST 0 Installation, Service And Maintenance Instructions Download Page 20

18 

 

ST 0, STR 0 

Fig.8 

  Having the transmitter adjusted put the jumper again on the terminals 81 and 82 in case that the 

output signal wont be used  (the circuit through the terminals 81 and 82 should be closed). 

 

Connect the control signal to the terminals 86/87 and 88.

 

 

3.4.1  EPV – 3-wire version (Fig. 8, 8a) 

 

The  resistive  transmitter  with  the  converter  is  in  the  plant  adjusted  to  have  the  output  current 

signal metered on the terminals 81-82 as follows:  

  in the position ”open“ .............  20 mA, resp. 5 mA, resp. 10V 

  in the position ”closed“ ...........  0  mA,  resp. 

4mA, resp.0 mA 

according  to  the  specified  version  of  the 
converter. 

 

If  the  transmitter  requires  a  new  adjustment 
follow these steps: 

  Put the actuator to the position „closed“ and 

switch the power supply off. 

  Adjust the resistive transmitter according to 

the  previous  chapter.  The  resistance  is  to 
be metered on the terminals X-Y, resp. 0%-
100%  (Fig.  8,  8a).  The  used  transmitter 
resistance is

 2000 

 resp. 100 

.

 

  Switch the converter

s power supply on. 

  Turn the adjusting trimmer ZERO resp A to adjust the output current signal rate measured on the 

terminals 81-82 to 0 mA, resp. 4mA, resp. 0V. 

  Set the actuator to the position ”open“. 

  Turn the adjusting trimmer GAIN resp. B to adjust the output current signal rate measured on the 

terminals 81-82 to 20mA, resp. 5 mA, resp. 10V. 

  Check  the  output  signal  of  the  converter  in  the  both 

limit positions, and repeat the procedure if needed. 

Note: 
The  output  signal  of  (0-20mA,  4-20mA,  0-5mA,  resp.  0-10V  
according to the specification) can be adjusted at the range from 
85  up  to  100%  of  the  rated  stroke  stated  on  the  actuator

nameplate.  At  values  less  than  85%  the  value    of  the  output 
signal is reduced proportionally.

 

 
 

3.5  Adjustment of position controller (Fig. 9) 

 

The  built-in  position  controller  REGADA  of  new 

generation  is  a  user-friendly  control  system  to  control 
actuators  with  an  analogue  signal.  The  controller  takes 
advantages of high-power RISC processor MICROCHIP to 
perform  all  functions.  It  provides  also  continuous 
automotive  diagnostics  of  the  system,  error  messages  as 
well  as  number  of  relay  switching  and  number  of 
controller's  operation  hours.  Placing  an  analogue  signal 
onto the input terminals of the terminal board 86/87 (GND, 
-) and 88 (+) causes that the EA output is reset.  
 

Required parameters and functions can be programmed using function buttons SW1 - SW2 and 

LED diodes D3 - D4 placed directly on the controller, see Table 2. 
 

Fig. 8a 

Summary of Contents for ST 0

Page 1: ...74 0813 02 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS Electric linear actuators ST 0 STR 0...

Page 2: ...min Operating stroke mm Input operation signal Warranty period months Transmitter potentiometer Serial number of electric motor Serial number of transmitter Serial number of position controller Tests...

Page 3: ...5 3 1 Gear unit adjustment 16 3 2 Position unit adjustment Fig 6 16 3 3 Adjustment of resistant transmitter 16 3 4 Adjustment of the Electronic Position Transmitter EPV the Resistive Transmitter Poten...

Page 4: ...th producer It is forbidden to use EA as a lifting mechanism 1 2 Safety instructions 1 2 1 Characteristics of the Product Regarding Its Exposure Rate EA of ST and STR types are reserved technical devi...

Page 5: ...with EN ISO 7010 ISO 7000 and IEC 60417 within valid edition Dangerous voltage EN ISO 7010 W012 Stroke of the electric linear actuator Switching off thrust Manual control 0096 ISO 7000 Protection term...

Page 6: ...max 2 000 hours Lifetime at operating hours depends on loading and switching frequency Note High switching frequency does not ensure better regulation Setting of regulation parameters should be there...

Page 7: ...50 but at most 1000 mg sq m per day protection enclosure IP 6x AE6 with atmospheric occurrence of corrosive and pollution media AF2 with possibility of effects of medium sinusoid vibrations with frequ...

Page 8: ...fed and controlled through two thrust switches 2 The thrust switches are switched with a finger 5 The position switches are switched with motion of the cams 4 The actuators are controlled with connect...

Page 9: ...power Nom speed Men current Capacitor capacity mm min mm mm N N N kg V 10 W 1 min A F V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 3 200 4 000 4 500 2 560 3 200 3 800 1 280 1 600 1 900 5 640 800 950 3 200 4 00...

Page 10: ...rsion without built in power supply with built in power supply Output signal for 2 wire version 4 20 mA DC Output signal for 3 wire version 0 5 mA DC 0 20 mA DC 4 20 mA DC 0 10 V DC Power supply volta...

Page 11: ...ng in direction opening frequency of relay switching in direction closing Supply voltage terminal 61 L1 1 N 230 V AC 10 Frequency 50 60 Hz 2 Input control signals analogue 0 20 mA 4 20 mA 0 10 V Input...

Page 12: ...acking Surfaces without surface treatment are treated by conservation preparation MOGUL LV 2 3 before packaging Conservation is not necessary if the following storage conditions are complied with Stor...

Page 13: ...nto operation Assembled EA but not put into operation is necessary to protect by the equivalent method as during storage for example suitable protective cover After assembly to the armature in free an...

Page 14: ...nnection dimensions according to DIN Standards Fig 2 Connection procedure Set the actuator A and the valve B to the position closed Put the actuator A onto the valve B Screw the actuator shaft 8 into...

Page 15: ...g nut 4 pillar nut 6 pillar 7 coupling screw B valve 10 valve shaft 12 locking nut 13 valve flange Mechanical connection for versions with flange Fig 4 Connection procedure Set the actuator A and the...

Page 16: ...ing nut 5 actuator flange 6 pillar B valve 10 valve shaft 11 connecting nut 12 locking nut 13 valve flange 2 1 2 Electric connection and checking of function 1 Follow instructions in the part Requirem...

Page 17: ...ng The procedure is as follows Press the button SW1 for about 2 sec i e till the D3 diode is got on to set the controller to the autocalibration mode During this process the controller checks the feed...

Page 18: ...eps Put the actuator to the position where the switch S5 should indicate the position open Turn the cam switching the switch S5 clockwisely until the switch S3 14 switches Put the actuator to the posi...

Page 19: ...the procedure if needed Note The output signal of 4 20mA can be adjusted at the range from 75 up to 100 of the rated stroke stated on the actuator s nameplate At values less than 75 the value 20mA is...

Page 20: ...resp 0V Set the actuator to the position open Turn the adjusting trimmer GAIN resp B to adjust the output current signal rate measured on the terminals 81 82 to 20mA resp 5 mA resp 10V Check the outp...

Page 21: ...insensitiveness of controller of 1 10 3 set by the producer CONTINUE D3 yellow diode number of blinking Adjust menu D4 red diode number of blinking Adjusted parameter 1 blink narrow thrust 2 blinks na...

Page 22: ...e D4 diode reports about the type of the error Else after finishing the initialisation process the controller is put into the regulation mode Error messages of the controller with D4 diode at initiali...

Page 23: ...face occurred it is to be removed to prevent actuator against corrosion The EA ST STR requires just negligible service Proper putting into operation is a recondition of reliable operation The service...

Page 24: ...s operation the replacement of cover seals and oil filling seals must be done The grease in the supplied actuators is designed for the lifetime of the product It is not necessary to change the grease...

Page 25: ...mA 250V fuse e g Siba or MSF 250 Note If the EA requires dismantling follow the chapter Dismantling Taking the EA to pieces for repair purposes is allowed only by professionally qualified persons trai...

Page 26: ...24 ST 0 STR 0 6 Enclosures 6 1 Wiring diagrams Wiring diagrams for EA ST...

Page 27: ...ent converter 3 wire version with power supply Z269 wiring diagram of resistive transmitter with current converter or capacitive transmitter 2 wire version with power supply B1 remote transmitter resi...

Page 28: ...26 ST 0 STR 0 6 2 Dimensional drawings EA ST STR The dimensions are valid also for the following dimensional drawings where only mechanical connection types are shown...

Page 29: ...ST 0 STR 0 27 Flange DIN 3358...

Page 30: ...28 ST 0 STR 0 Pillars...

Page 31: ...ST 0 STR 0 29 Flange...

Page 32: ...30 ST 0 STR 0 Flange...

Page 33: ...ST 0 STR 0 31 Flange...

Page 34: ...32 ST 0 STR 0 Pillars...

Page 35: ...ST 0 STR 0 33 Flange...

Page 36: ...34 ST 0 STR 0 Pillars...

Page 37: ...ST 0 STR 0 35 Flange...

Page 38: ...36 ST 0 STR 0 Flange...

Page 39: ...ST 0 STR 0 37...

Page 40: ...38 ST 0 STR 0...

Page 41: ...heck report Service center Date of repair Guarantee repair no User of actuator Claim applied by Actuator type number Actuator production number Product claim fault Detected product fault Used spare pa...

Page 42: ...uarantee service check report Service center Date of repair User of actuator Actuator operating place Actuator type number Actuator production number Detected product fault Used spare parts Remarks Is...

Page 43: ...n cka 7 080 01 Pre ov Tel 421 0 51 7480 460 Fax 421 0 51 7732 096 E mail regada regada sk Czech Republic Exclusive representation Regada s r o Ltd for sale of electric actuators Regada esk s r o N m 5...

Reviews: