MO 3, MO 3.3, MO 3.4, MO 3.5
7
1.7 Conservation, packing, transport, storing and unpacking
Surfaces without surface treatment are treated by conservation preparation MOGUL LV 2-3 before
packaging .
Conservation is not necessary if the following storage conditions are complied with:
• Storage temperature: -10 to +50 °C
• Relative air humidity max.80 %
• Electric actuators and their accessories must be stored in dry, well ventilated covered spaces, protected
against impurities, dust, soil humidity (by placement to racks, or on palettes), chemicals and foreign
interventions
• There shall be no corrosive gases present in the storage areas.
The EA MO are delivered in solid packages guaranteeing resistance in accordance with EN/IEC 60 654 -1 and
EN/IEC 60 654-3.
Package is a box. Products in boxes is possible to load on the pallets (pallet is returnable). On the outer
side of the package is stated:
•
manufacturer label,
•
name and type of product,
•
number of pieces,
•
other data – notices and stickers.
The forwarder is obliged to secure packed products, loaded on transportation means, against self-motion;
if open transportation means are used, to secure their protection against atmospheric precipitations and
splashing water. Displacement and securing of products in transportation means must provide their stable
position, exclude the possibility of their inter-collision and their collision with the vehicle walls.
Transportation can be executed by heatless and non hermetic spaces of transportation vehicles with influences
within the range:
- temperature: -25° C up to +70° C (a strange version – 45 ° C up to + 45 ° C)
- humidity : 5 up to 100 %, with max. water content 0.029 kg/kg of dry air
- barometric pressure 86 up to 108 kPa.
Upon receiving of EA examine, if during transportation, resp. storing did not come to its damage. At the
same time verify, if the data on the labels corresponds to accompanying documentation and purchase-
sale contract / order. Eventual discrepancies, faults and damages should be reported without any delay
to supplier.
Electric actuators and their accessories must be stored in dry, well ventilated covered spaces,
protected against impurities, dust, soil humidity (by placement to racks, or on palettes), chemicals and
foreign interventions, at ambient temperature from -10°C up to +50
°
C and at relative air humidity max.
80 %.
Warning:
1. It is not acceptable to store EA outdoors, or in areas not protected against direct climate influence!
2. It is not recommended to set up the electric actuator manually without mechanic connection with armature.
The electric actuator does not have mechanic restriction of working stroke in terminal positions and therefore
can after exceeding of the stroke come to mistuning of parameters set up by production plant.
3. Eventual damages to surface finish remove without delay – thus preventing damage by corrosion.
4. If storing takes longer than 1 year, it is necessary to inspect lubrication fillings before putting EA into
operation.
5. Assembled EA, but not put into operation is necessary to protect by the equivalent method as during storage
(for example suitable protective cover).
6. After assembly to the armature in free and wet areas, or in areas with temperature changes, connect without
delay heating resistor – thus preventing damages caused by corrosion from liquefied water in the control
area.
7. Excessive preserving grease remove just before putting EA into operation.
1.8 Assessment of the product and packaging and removal of contamination
The product and its package are made of recycling materials. Do not throw the single parts of the package
and of the product after their life but sort them according to instructions in corresponding executives or
regulations of environment protection, and allow their recycling.
The product, however, contains a mineral oil fill dangerous for the environment. Please avoid oil leak into
the environment at its disposal.
!
Summary of Contents for MO 3
Page 35: ...MO 3 MO 3 3 MO 3 4 MO 3 5 33 7 Enclosures 7 1 Wiring diagrams Wiring diagrams MO...
Page 36: ...34 MO 3 MO 3 3 MO 3 4 MO 3 5...
Page 37: ...MO 3 MO 3 3 MO 3 4 MO 3 5 35 Wiring diagrams MO with controller...
Page 41: ...MO 3 MO 3 3 MO 3 4 MO 3 5 39 4 x tooth F10 shape D F10 shape C DIN 3338 F10 shape E ISO 5210...
Page 42: ...40 MO 3 MO 3 3 MO 3 4 MO 3 5 Mechanic connections for EA MO 3...
Page 43: ...MO 3 MO 3 3 MO 3 4 MO 3 5 41...
Page 45: ...MO 3 MO 3 3 MO 3 4 MO 3 5 43 Dimension drawings for EA MO 3 5...
Page 46: ...44 MO 3 MO 3 3 MO 3 4 MO 3 5 Dimension drawings for EA MO 3 4...
Page 47: ...MO 3 MO 3 3 MO 3 4 MO 3 5 45 Dimension drawings for EA MO 3 3...
Page 50: ...48 MO 3 MO 3 3 MO 3 4 MO 3 5 Mechanic connections for EA MO 3 4 with connect adapter...
Page 51: ...MO 3 MO 3 3 MO 3 4 MO 3 5 49...