INSTALLATION GUIDE 

 

Brand:  

Refusol 

Type:    

Solar On Grid String Inverter 

Models:  

REFUsol 08K , REFUsol 10K , REFUsol 13K , REFUsol 17K ,REFUsol 20K, REFUsol 23K-MV,                           

REFUsol 40K, REFUsol 46K-MV 

MANDATORY CHECKS 

 
Firmware Version - 

300-01-06-10-S or above 

CONNECTION DIAGRAM 

 

Figure R1 – Refusol Sring Inverter Connections

 

 

 

Figure R2- Connector Pins 

Table RT1 – Refusol RS485 chip connections with TrackSo IoT 

Gateway

 

Refusol Pin 

No. 

Refusol Assignment 

TrackSo Pin 

No. 

TrackSo Assignment 

(only used for 

termination)

 

Power+ 

(Via Adapter) 

RS485 +

 

D + 

RS485 -

 

D - 

Reference

 

 

 

 

1.

 

Please open RS485 terminal (communication port 1) as shown in 

Figure R1

.  

2.

 

Please make the connections from the Terminal Block of RS485 chipset to TrackSo IoT Gateway as 
mentioned in the Table – RT1 and using the connector supplied with inverer as shown in R2 

3.

 

Connector Details - Phoenix Contact type M12MS SACC-4SC SH plug 

4.

 

Terminate the bus as required. The bus termination is made by means of wire jumpers on RS485 OUT to the 
last bus inverter. To make the termination take a short cable, remove the cable insulation, and connect the 
pin 1 to pin 2 as well as pin 3 to pin 4. 

 

 

 