Installation
10
—
English
Vacuum spray degassing
—
18.12.2019
–
Rev. A
6.5.1
T erminal diagram
1
Main fuse
9
Digital inputs:
Water meter; Insufficient water
2
Fuse for motorized ball valve
10
Ball control valve (supply)
3
CD degassing control valve
11
Pressure analogue input
4
Group message
12
External make-up demand (Levelcontrol only)
5
Optional for conductivity
13
WV make-up valve
6
Ball control valve
(correcting variable (25) / Return value (46))
14
Pump
7
RS-485 interface
15
Mains supply
8
---
T erminal
number
S ignal
F unction
Wiring
1
PE
230 V power supply via mains
cable and plug.
Pre-wired
2
N
3
L
4
PE
"PU" pump
Pre-wired
5N
N
6 M1
M 1
7
Y2
CD degassing control valve
Pre-wired
8
N
9
PE
10
Y 1
WV make-up valve
Pre-wired
11
N
12
PE
13
COM
Group message (floating).
User,
optional
14
NC
15
NO
16
Not assigned
External make-up demand from
a pressurisation station;
controller must be set to
"Levelcontrol"!
User,
optional
17
Make-up (230
V)
18
Make-up (230
V)
19
PE shield
Level analogue input, not used
by the device.
---
20
- Level (signal)
21
+ Level (+ 18 V)
22
PE (shield)
Pressure analogue input
Pre-wired
23
- Pressure
(signal)
24
+ Pressure (+
18 V)
25
0
–
10 V
(correcting
variable)
Ball control valve
Pre-wired
26
0
–
10 V
(feedback)
27
GND
28
+ 24 V (supply)
29
A +
RS-485 interface.
User,
T erminal
number
S ignal
F unction
Wiring
30
B -
optional
31
GND
32
+ 24 V
Insufficient water switch - dry-
running protection
Pre-wired
33
E1
Contact water meter, for
evaluation of the make-up,
terminal 32/33 closed = meter
pulse.
User,
optional
34
E2
Insufficient water switch, contact
32/34. Lead the cable of the
insufficient water switch through
the cable gland and connect at
the terminals
Pre-wired
6.5.2
RS -485 interface
6.5.2.1
Connecting the RS-485 interface
Connect the interface as follows:
1.
For connecting the interface use only a cable with these properties:
–
LJYCY (TP), 4 × 2 × 0.8, maximum overall bus length 1000 m.
2.
Use a shielded cable to connect the interface to terminals 29, 30, 31 of the
main board in the control cabinet.
–
For connecting the interface, see chapter 6.5 "Electrical connection"
on page 9 .
3.
When using the device with a control centre not supporting an RS-485
interface (RS-232, for example), you must use a corresponding adapter.