Controller
12 — English
Fillcontrol Auto Compact — 20.10.2020 - Rev. D
Indication on the
display
Meaning
Disable make-up?
JA
This value is only displayed if "YES" has been set in the
"With softening" menu option.
•
YES: The system stops the make-up process when
the set soft water capacity is exceeded.
•
NO: The system does not stop the make-up
process. The system displays the "Softening"
message.
Hardness reduction
10 °dH
This value is only displayed if "YES" has been set in the
"With softening" menu option.
•
Hardness reduction is calculated from the
difference of the overall water hardness GH
actual
and the target water hardness GH
target
.
Hardness reduction = GH
actual
-GH
target
l °dH
Enter the value in the controller. Consult the
manufacturer information for third-party products.
Cap. soft water
05000 l
This value is only displayed if "YES" has been set in the
"With softening" menu option.
The attainable soft water capacity is calculated from the
type of softening used and the specified hardness
reduction.
•
Fillsoft I, soft water capacity ≤ 6000/hardness red. l
•
Fillsoft II, soft water capacity ≤ 12000/hardness
red. l
Enter the value in the controller. Consult the
manufacturer information for the values of third-party
products.
Remaining cap. soft
w.
000020 l
This value is only displayed if "YES" has been set in the
"With softening" menu option.
•
Available soft water capacity.
Replacement
18 months
This value is only displayed if "YES" has been set in the
"With softening" menu option.
•
Manufacturer specification for the replacement
interval of the softening cartridges, regardless of
the calculated soft water capacity. The system
displays the "Softening" message.
Next maintenance
012 months
Recommended maintenance messages.
•
Off: Without maintenance recommendation.
•
001 – 060: Maintenance recommendation in
months.
Floating fault
contact
JA
For the output of messages to the floating contact, see
chapter 9.3 "Messages" on page 12 .
•
YES: Output of all messages.
•
NO: Output of all messages identified with
"xxx"
("01", for example).
Fault memory
˃
Switch to the "Fault memory" sub-menu.
•
Press "OK" to open the menu.
•
Use the "
▼▲
" buttons to open the sub-menu.
ER 01…xx
The last 20 alarms are stored with fault type, date, time,
and fault code.
See the chapter "Messages" for more information about
the ER... messages.
Parameter
memory
˃
Switch to the "Parameter memory" sub-menu.
•
Press "OK" to open the menu.
•
Use the "
▼▲
" buttons to open the sub-menu.
P0 = xx.x bar
Date | Time
The last 10 entries of the minimum working pressure are
stored with date and time.
V0.60
Information about the software version
9.2.1
Customer menu
The device controller is shipped with the following default settings. Use the
Customer menu to adjust these values to local conditions. In special cases, it is
possible to further adjust the values in the Service menu.
Parameter
Setting
Comment
Language
DE
Display language
Parameter
Setting
Comment
Fillcontrol XX
Magcontrol For systems with diaphragm-type
expansion vessel
Minimum operating
pressure P
0
1.5 bar
Only Magcontrol
see chapter 7.2 "Determining the P
minimum operating pressure for
the controller" on page 9
Safety valve, pressure
3.0 bar
Tripping pressure for the safety
valve at the heat generator in the
system
Next maintenance
12 months
Time left to the next due
maintenance
Volt-free contact
NO
Only the messages marked in the
"Messages" list
Make-up
Maximum make-up volume 1000 litres
Only if controller with "With water
meter yes"
Maximum make-up time
20 minutes Magcontrol
Maximum make-up cycles 3 cycles
within 2
hours
Magcontrol
Softening (Only if "With softening yes")
Shut off make-up
NO
In the event of soft water residual
capacity = 0
Hardness reduction
8°dH
= Setpoint – Actual
Maximum make-up volume 0 litres
Attainable make-up quantity
Soft water capacity
0 litres
Attainable water capacity
Cartridge replacement
18 months
Replace cartridge
9.2.2
Service menu
This menu is protected with a password. It can be accessed only by the Reflex
Customer Service. A partial summary of the settings stored in the Service menu is
proved in the Chapter Default settings.
Service menu
Parameter
Setting
Remarks
Makeup
Pressure differential,
"NSP" makeup
0.2 bar
Only Magcontrol
Pressure differential,
filling pressure PF – P
0
0.3 bar
Only Magcontrol
Water quantity for each
contact
10 l / K
Only if a water meter is
installed. (Fillset Impulse, for
example)
Maximum filling
contacts
OFF
Limits the filling volume.
Only if a water meter is
installed. (Fillset Impulse, for
example)
9.3
Messages
The display provides alarms in plain text and the ER codes shown in the list. Use
the arrow buttons to scroll through multiple alarms displayed at the same time.
The fault memory stores the last 20 alarms for review, see chapter 7.4
"Parametrising the controller in the Customer menu" on page 9 .
Alarm causes can be eliminated by the operator or a specialist workshop. If this is
not possible, contact the Reflex Customer Service.
Note!
Clearing of the cause must be confirmed by pressing the “Ack” button on
the operator panel. All other alarms are automatically reset as soon as
the cause has been eliminated.
Note!
Floating contacts, setting in the Customer menu, see chapter 7.4
"Parametrising the controller in the Customer menu" on page 9 .