background image

Instruction Manual TAP, TAP-CLAMP / Temperature And Pressure Gauge  English 

  

19 

 

Note on R000: 
Additional function to select from table of refrigerant: If use entry 
„R000“ it means „Pressure only“. No readouts from chart. It gives the 
possibility to measure only pressure and temperature without any 
refrigerant chart temperatures shown. 
 

 
 

Set favorites 

- Press [MENU] button 

 1 sec. to activate selection mode. 

 
- Press [DOWN] button 

 1 sec. to scroll down to the refrigerant 

menu. 
 
- Press [SET] button 

 1 sec. to enter refrigerant menu. 

 
- Press [UP] or [DOWN] button 

 1 sec. to scroll to the desired 

refrigerant. 
 
- Press [ON/OFF] button < 1 sec. to add refrigerant to favorites. 

 

 

Note: 
New favorite is placed at first of column. 
Last of the 6 entries drops out. 

 

 
 

Set pressure 
unit 

- Press [MENU] button 

 1 sec. to activate selection mode. 

 
- Press [DOWN] button 

 1 sec. to scroll down to the pressure unit 

menu. 
 
- Press [SET] button 

 1 sec. unit field will flash. 

 
- Press [UP] or [DOWN] button 

 1 sec. to select pressure unit. 

 
- Press [SET] button 

 1 sec. to confirm. 

 
- Press [MENU] button 

 1 sec. to return to main display. 

 

 
 

Summary of Contents for 4687785

Page 1: ...RE GAUGE Installation and operating guide Temperature And Pressure Gauge Installations und Bedienungsanleitung Temperatur und Druckpr fger t Guide d installation et d utilisation Istruzioni per l inst...

Page 2: ...essure Gauge English 1 Contents Introduction 2 General information 4 Important safety notice 5 Technical Data 6 Parts description 8 Transport packaging and storage 15 Setup operation 16 Maintenance 22...

Page 3: ...ital display is applicable for pipe diameters 6 mm to 41 mm 1 4 to 1 5 8 Measurements and calculation of superheat or subcooling can be shown on pressure gauge display and or on your mobile device Up...

Page 4: ...t installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installat...

Page 5: ...nvironmental impact into consideration when procuring materials and manufacturing its products REFCO Manufacturing Ltd feels responsible for all of its products throughout their entire lifespan and ha...

Page 6: ...inadequately qualified personnel or unauthorised modification of the TAP The General Terms and Conditions as set out in the sales documentation shall apply Symbols and writing standards Illustration...

Page 7: ...models and variations of our products can be found in the REFCO catalogue or at www refco ch The REFCO App is available on App Store and Play Store Technical Data Temperature clamp Property Value The...

Page 8: ...Connection fitting SAE Size 125 mm x 57 mm x 34 mm Weight 200 gr 7 0 oz The TAP can be used with the following refrigerants R11 R113 R114 R12 R123 R124 R13 R134a R13B1 R22 R227 R23 R290 R32 R401A Liq...

Page 9: ...h Instruction Manual TAP Temperature And Pressure Gauge 8 Parts description Temperature Clamp Indicator LED light Display UNIT button Marking band blue or red ON OFF button Battery case cover 3 x 1 5...

Page 10: ...e And Pressure Gauge English 9 Pressure Gauge Marking band blue or red Mounting ring Connection Micro USB Slider switch Online Offline LED Indicator light Display Connection fitting SAE UP MENU DOWN S...

Page 11: ...ime 20 min configurable UNIT UNIT by short pressing 1 sec UNIT by pressing 1 sec C appears F appears Once set setting remains No function To escape from last set menu ON OFF UNIT By pressing ON OFF UN...

Page 12: ...ess transmission to pressure gauge off Display T1 T6 Number of TAP CLAMP T1 to T6 C F Temperature units Transmiting symbol Flashing during connection setup Constant after connection Auto Off 10 min 20...

Page 13: ...Backlight shuts off after 1 min Display shows OFF Backlight off Display off Backlight ON OFF Only in system On modus by short pressing ON 1 sec Backlight shuts off after 1 min Auto Off Factory default...

Page 14: ...g continuous to smart device LED light on Wireless connection to smart device is active To use TAP with smart device No measurements transmitting to smart device LED light off No wirless connection to...

Page 15: ...c Condensing temperature T1 T6 C F Temperature units T Temperature from temp clamp T K F Temperature difference T Temperature difference Settings Transmiting symbol Flashing during connection setup Co...

Page 16: ...ial transportation damage Any obvious damage should be reported to the vendor immediately TAP is a high grade instrument and should be transported and stored in a box for long term protection Packagin...

Page 17: ...battery compartment If you will not be using the TAP CLAMP for a long period of time remove the batteries from the battery compartment Switch on Press ON OFF button to switch on device After start im...

Page 18: ...ol and the auto off time disappear from display Set unit Press UNIT button 1sec Switch between C and F by using UNIT button 1 sec TAP Pressure Gauge Set up TAP Insert 4 x 1 5 V AAA batteries in the ba...

Page 19: ...Note Number for P1 to P6 is always concurrent with the TAP number Set refrigerant To change current refrigerant setting Press MENU button 1 sec to activate selection mode Press DOWN button 1 sec to s...

Page 20: ...c to scroll down to the refrigerant menu Press SET button 1 sec to enter refrigerant menu Press UP or DOWN button 1 sec to scroll to the desired refrigerant Press ON OFF button 1 sec to add refrigeran...

Page 21: ...5 meters Ensure TAP CLAMP S which shall be paired with TAP pressure gauge are switched on Ensure TAP pressures gauge is on Press MENU button 1 sec on TAP pressure gauge to activate selection mode Pre...

Page 22: ...utton 1 sec to activate selection mode Press UP button 1 sec to scroll up to the setting field Press SET button 1 sec to enter settings menu Press UP or DOWN button 1 sec to scroll to the desired fiel...

Page 23: ...wear Therefore the TAP should be regularly tested by the user for leaks Resetting pressure sensore on TAP pressure gauge The TAP pressure sensor can be reset in order to avoid incorrect measurement v...

Page 24: ...ed on 2 Press MENU button 1 sec to activate selection mode 3 Press UP button 1 sec to scroll up to the setting field 4 Press SET button 1 sec to enter settings menu 5 Press UP or DOWN button 1 sec to...

Page 25: ...t circuits are possible Don t dunk the temperature clamp below max water level See figure below Ice water calibration 0 C 32 F Risk of short circuit If the electronic components come into contact with...

Page 26: ...The display shows the ambient temperature 11 Press UNIT button 1 sec to quit the temperature calibration Room temperature calibration 1 Turn off the clamp 2 Place the clamp at constant temperature at...

Page 27: ...bration The accuracy will be affected due to the remaining refrigerant 7 While entering calibration the display shows 400 0 psi The default pressure of calibration standard is 400 psi 8 Press UP MENU...

Page 28: ...or wear are excluded from the guarantee Return and disposal Dispose of faulty rechargeable batteries spent batteries in accordance with the valid legal specifications At the end of its useful life sen...

Page 29: ......

Page 30: ...Deutsch Bedienungsanleitung DIGIMON DIGIMON4 1 REFCO Manufacturing Ltd Industriestrasse 11 6285 Hitzkirch Switzerland Telefon 41 41 919 72 82 Telefax 41 41 919 72 83 info refco ch www refco ch 4687790...

Reviews: