9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

7.REGISTER OF OPERATION DATA  AND ALARMS.

By simultaneously holding down buttons MENU +

 for 3 seconds the user can report on the REGISTER OF OPERATION DATA AND ALARMS, by pressing 

ENTER we can advance through the sequence, once finished the sequence we come back to the main display . This is all the sequence:

•  REGISTER HOURS (HF). Counter of total time that the pump has been operating.

•  REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop.

•  REGISTER SWITCH (Cr). Number of connections to the electric supply.

•  ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

•  ALARM COUNT I MAX (A2). Number of overcurrent alarms.

•  ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

•  ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

•  ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

•  ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

•  ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

1.Press push-button MENU for 3 seconds to start the configuration sequence.

2. Input the nominal intensity value in Amps using 

▲▼

 enabling the thermal protection. 

For VSC1-7.5 must be within 0 and 7.5 A, the default value is 7.5 A.

For VSC1-12 must be within 0 and 12 A, the default value is 12 A.

This value is located over the characteristics plate of the motor. Press ENTER for validation.

3.Using the START/STOP pushbutton verify the rotation sense. By mean of keys 

▲▼

 (0/1) we can change it. 

Press ENTER for validation. (3 Phase Models ONLY)

4. Using 

▲ 

this value can be changed to lower/increase the speed of rotation (speed of the pump start up). 

This can help if there are potential leaks in the line, or long/short runs of pipework. The value must be within 

30 and 35 Hz. Default value is 30 Hz. Press push-button ENTER, for validation and quit this menu.

5. If the installation does not have level probe press ENTER to validate 0. If the installation has a level probe, 

use keys 

▲▼

 to change 0 by 1.

6. The device is configured as 0-SINGLE as default value. In case of group assembly (M-S), the Master device 

has to be configured as 1-MASTER and the Slave as 2-SLAVE. ENTER to validate.

7. In case 1-MASTER is selected it can be adjusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this 

parameter is disabled.

8. System is ready. By pressing AUTO ON/OFF to quit the manual operating mode.

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

All the records are saved even if the device has been disconnected from the electric supply. 

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to indicate 10234 overcurrent alarms:

ON

OFF

9. CONFIGURATION.

In the configuration menu we can adjust either maximum current (

A

) and minimum pump speed (

FL

).  Next steps shoud be followed:

 

 

1. Press push-button 

MENU

 during 3 seconds to start the configuration sequence.

 

2. Input the nominal intensity value in Amps using 



 enabling the thermal protection.

 

For Easy 09MM must be within 0 and 9 A, the default value is 9 A.

 

For Easy 12MM must be within 0 and 12 A, the default value is 12 A.

 

For Easy 06MT must be within 0 and 6 A, the default value is 6 A.

 

For Easy 10MT must be within 0 and 10 A, the default value is 10 A.

 

This value is located over the characteristics plate of the motor. Press 

ENTER

 for validation.

 

 

3. Using the 

START/STOP

 pushbutton verify the rotation sense. By mean of keys 



(0/1) we can change it. Press

                  

ENTER

 for validation. 

MT types only.

 

 

4. Using 

 can be increased the lower limit of the speed of rotation.

 

The value must be within 30 and 35 Hz. Default value is 30 Hz. 

 

Press push-button 

ENTER

, for validation and quit this menu.

    

5. If the installation does not have level probe press 

ENTER

 to validate 0.

 

If the installation has a level probe, use keys

 



to change 0 by 1.

 

6. The device is configured as 

0-SINGLE 

as default value. In case of group assembly (M-S), the Master device has 

to be configured as 

1-MASTER 

and the Slave as 

2-SLAVE. 

ENTER to validate.

7. In case 

1-MASTER 

is selected it can be ajusted a maximum time of continued functioning. After the 

configurated time (t.A) of a continued functioning an alternance will be forced. Value 00 means this parameter 

is disabled.

 

8. System is ready. By mean of 

AUTO ON/OFF

 quit the manual operating mode.

10. R

EGISTER OF OPERATION DATA  AND ALARMS.

By using  simultaneously  

MENU

 + 

 during 3” is acceded to 

REGISTER OF OPERATION DATA AND ALARMS

, by mean 

of 

ENTER 

we can advance through the sequence, once finished the sequence we come back to the main display . This is all 

the sequence:

REGISTER HOURS (HF). Counter of total time that the pump has been operating. 

REGISTER STARTS (CF). Number of cycles of operation, a cycle is a start and a stop. 

REGISTER SWITCH (Cr). Number of connections to the electric supply.

ALARM COUNT DRY RUN (A1). Number of dry-running alarms.

ALARM COUNT I MAX (A2). Number of overcurrent alarms.

ALARM COUNT. DISCONNECTED PUMP (A3). Number of disconnected pump alarms.

ALARM COUNT. TEMP (A6). Number of alarms by excessive temperature.

ALARM COUNT. SHORTCIRCUIT (A7). Number of short circuit alarms.

ALARM COUNT. OVERVOLTAGE (A8). Number of overvoltage alarms.

ALARM COUNT. UNDERVOLTAGE (A9). Number of undervoltage alarms.

All the records are saved even if the device has been disconnected from the electric supply.

Note: For quantities with more than 2 figures they will appear in consecutive screens after each ENTER. For example, to 

indicate 10234 overcurrent alarms:

       .....                                                                                                                              ....

-10-

12. ALARMS

In case of simultaneous alarms, quit the automatic mode and go to manual mode, pressing  the pushbutton 

AUTOMATIC ON/OFF

 (led light PUMP will turn off). 

Using key 

▲▼

 will be displayed the succesive alarms. Once visualized, for leaving the menu,  press ENTER returning to MANUAL mode.