background image

8

INSTALLATION

R E D Z O N E

T M

  D V S   S E R I E S   A I R   H A N D L E R   M A N U A L

C L O S E T   I N S T A L L A T I O N   
( R E T U R N   A I R   T H R U   O P E N I N G   
O R   G R I L L )

The DVS Air Handler can be installed in a closet on a  

supporting stand or be mounted from the closet wall  

using the closet as the return air plenum. Unit should be 

high enough from the floor to provide unimpeded return  

airflow into the bottom of the cabinet.

Closet return air opening can be on the front (in closet 

door), side (thru the wall) or a combination of both,  

providing there is clearance on the sides between unit’s 

cabinet and closet. Refer to ACCA Manual D or SMACNA  

for sizing and free area recommendations.

NOTE: 

Local codes may limit application of systems without a 

ducted return to single story dwellings. 

 

 

S U S P E N D E D   C A B I N E T   
I N S T A L L A T I O N

If the cabinet cannot be supported on a frame or supported 

from the wall, it may be suspended.

Use metal strapping or threaded rod with angle iron  

supports under cabinet for support. These supports  

MUST run parallel with the length of the cabinet  

(see Figures 6 and 7).

Ensure that there is adequate room to remove service  

and access panels after installing supporting brackets.

If an auxiliary drain pan is required, the support is  

to be placed under a drain pan. In such installations,  

the unit will need to be supported on vibration isolators 

(rubber or Styrofoam blocks).

IMPORTANT:

When a DVS unit is matched with an evaporative  

type (cased coil/condensing unit) split system for cooling  

application and the system is installed above a finished 

ceiling and/or an occupied space, building codes may call 

for a secondary insulated condensate pan (by others)  

to be installed under the entire unit. In other instances, 

some local codes may allow the running of a separate, 

secondary condensate line in lieu of the required drain pan. 

It is the responsibility of the installer to consult local codes 

for compliance.

DOOR
ASSEMBLY

8” MIN FOR
DOOR REMOVAL

(2) HEX NUTS, (2) WASHERS & (2)
LOCK WASHERS REQ. PER ROD

USE 1” SQUARE, 1-1/4 x 1-1/4 x 1/4
ANGLE IRON OR EQUIVALENT

SECURE ANGLE
IRON TO BOTTOM
OF AIR HANDLER
WITH 3 #8 x 3/4”
SCREWS TYPICAL
FOR 2 SUPPORTS

1/4” THREADED ROD
(4 REQUIRED)

F I G U R E   6     Horizontal Unit Suspension

WARNING

It is the installer’s responsibility to use an appropriate 

hanging method capable of supporting the unit’s weight. 

Refer to the specification section of this document for 

the respective unit’s installed weights.

NOTICE

For seismic hanging requirements, refer to local codes.

Summary of Contents for DVS1000

Page 1: ...t 4 Physical Data 5 Installation Locating and Mounting 6 10 Plumbing 11 14 Electrical Connections 15 17 Thermostat Installation 18 Start Up Procedure 19 Troubleshooting 20 Sequence of Operation 21 Mai...

Page 2: ...l brazing and un brazing operations Suitable fire extinguishing equipment shall be immediately available in the work area and shall be maintained in a state of readiness for instant use Read these ins...

Page 3: ...es in addition to instructions laid out in this manual The installation must comply with regulations of the local building heating plumbing and other codes Where local codes are not applicable the ins...

Page 4: ...al packages until installation The DVS Series Air Handler needs to be installed and commissioned by a knowledgeable qualified professional NOTES 1 This Air Handler is approved for upflow downflow and...

Page 5: ...0 254 DVS800 17 432 23 584 35 5 902 20 508 12 305 18 457 11 279 10 254 DVS1000 21 25 540 23 584 43 75 1111 20 508 16 406 18 457 15 381 14 356 DVS1200 21 25 540 23 584 43 75 1111 20 508 16 406 18 457 1...

Page 6: ...upplied filter rack installed For instructions on required modifications and assembly refer to Figures 3 and 4 SIDE FILTER RACK ASSEMBLY SCREW FILTER RACK TO SIDE OF CABINET USING MOUNTING HOLES CUT S...

Page 7: ...hored to the unit and to the floor or wall Mount the filter rack on the side or bottom of the cabinet that the return air knockout has been removed Horizontal Left and Right Installations The DVS Air...

Page 8: ...e and access panels after installing supporting brackets If an auxiliary drain pan is required the support is to be placed under a drain pan In such installations the unit will need to be supported on...

Page 9: ...y of the installer to inspect all previously installed air distribution system to determine its suitability for the new heating and or cooling system Existing ductwork may have to be modified and or i...

Page 10: ...s whenever possible as this takes less space The 3 duct should then be fastened to the joist with strapping material If the 3 duct is in an unconditioned space it must be insulated to local code then...

Page 11: ...piping systems that incorporate a domestic water supply NOTE Precautions must be taken during soldering to avoid debris or solder from lodging in piping system Mechanical Joining of Tubing Where used...

Page 12: ...g water will carry air bubbles along a vertical pipe Average flow velocities of 2 feet per second or higher can draw along air bubbles in a downward flow At the above stated velocities air bubbles sha...

Page 13: ...he line Stickers indicating direction of flow WATER IN and WATER OUT are labeled on the outside of the cabinet DO NOT reverse these lines as this will cause the unit to malfunction NOTICE ball valves...

Page 14: ...ball valve 2 BV2 STEP 4 OPEN cold water supply main valve ball valve 1 BV1 The system will begin the prime purge process using the street pressure Entrapped air bubbles being pushed out of the system...

Page 15: ...connections All electrical connections MUST comply with NEC and any other local codes or ordinances having jurisdiction USE COPPER WIRE ONLY Provide separate branch electric circuit with field suppli...

Page 16: ...ions between the unit and the thermostat use No 18 AWG colour coded insulated 63 F 35 C minimum wires Low Voltage Connections These units use a grounded 24 volt AC low voltage circuit and require at l...

Page 17: ...E Tap 2 LOW VELOCITY 0 4 NORMAL YELLOW TR Tap 3 LOW VELOCITY 0 4 BOOST BLUE TR Tap 4 MID VELOCITY 0 8 NORMAL PURPLE TR Tap 5 MID VELOCITY 0 8 BOOST BLACK TR MOTOR SPEED 24VAC PLUG MOTOR 120VAC PLUG WH...

Page 18: ...t waster escape Installation Thermostat should be mounted approximately 5 ft 1 5 m from floor close to or in a frequently used room preferably on an inside partitioning wall on a section of wall witho...

Page 19: ...is on and a call is present STEP 3 Turn thermostat on and switch system to the heating mode The thermostat shall be set higher than the actual room temperature this will cause the circulator to energi...

Page 20: ...Circuit board controls the blower motor in Heating mode Check that LOW FAN or HIGH FAN LED is illuminated Also check for 24VAC at these terminals on the circuit board If faulty refer to Faulty Circui...

Page 21: ...tisfied the blower switches to low fan speed for two minutes to remove remaining heat from the system Heat Blower OFF Delay When the heating thermostat demand W is removed the control de energizes the...

Page 22: ...A I R D U C T S Y S T E M S The supply and return air ducts should be inspected at least annually for blockages or damage M O T O R S The motor and pump are permanently lubricated and do not need per...

Page 23: ...1 3 Maximum Fuse or CKT BKR Size Amps 15 15 1 2 1 2 PIPING CONNECTIONS QTY INDOOR BLOWER MOTOR ELECTRICAL RATING AND PERFORMANCE UNIT OF MEASURE Inches Inches 1 2 3 4 Add on Cooling Tons 1 5 2 Supply...

Page 24: ...d domestic water heating an anti scald valve should be installed when the Tankless Water heater set thermostat is above 120 F 49 C refer to local codes and or all authority having jurisdiction For rec...

Page 25: ...pply Leaving CSA P 9 11 CFM Flow Air Water BTU Air Water Certified GPM Deg F Deg F Deg F Deg F Condition 120 14 800 105 90 130 18 700 114 92 400 1 70 140 22 000 121 95 Yes 150 25 100 129 99 160 28 300...

Page 26: ...8 Unit Technical Information Airflow Water Return Supply Output Supply Leaving CSA P 9 11 CFM Flow Air Water BTU Air Water Certified GPM Deg F Deg F Deg F Deg F Condition 120 22 300 105 90 130 27 000...

Page 27: ...Leaving CSA P 9 11 CFM Flow Air Water BTU Air Water Certified GPM Deg F Deg F Deg F Deg F Condition 120 28 800 104 91 130 34 700 111 95 800 2 0 70 140 40 600 117 99 Yes 150 46 500 124 103 160 52 400 1...

Page 28: ...on Airflow Water Return Supply Output Supply Leaving CSA P 9 11 CFM Flow Air Water BTU Air Water Certified GPM Deg F Deg F Deg F Deg F Condition 120 36 000 104 91 130 43 300 112 95 1000 2 5 70 140 50...

Page 29: ...g CSA P 9 11 CFM Flow Air Water BTU Air Water Certified GPM Deg F Deg F Deg F Deg F Condition 120 42 200 103 92 130 50 800 110 96 1200 3 0 70 140 59 400 116 100 150 68 100 123 104 160 76 800 130 108 H...

Page 30: ...itch CARLING TA20B CARLING TA20B CARLING TA20B CARLING TA20B CARLING TA20B Coil BC9061 BC9061 BC9061 BC7923FX BC7923FX Housing DC1020 600 5 DC1020 600 5 DC1020 600 5 DC1020 800 5 DC1020 800 5 Pump UPS...

Page 31: ...e installed by a qualified or licensed contractor Improper installation may void this Warranty This Warranty extends to the original purchaser but only while the product remains at the site of the ori...

Page 32: ...fficulties due to the following accident abuse or misuse alteration misapplication force majeure improper installation such as but not limited to inadequate water quality condensate damage or absence...

Reviews: