5.1 Connect cables to the AC grid side and off-grid side
5 Cable Connection
Requirements
1.
Ensure
an AC circuit breaker
is installed
between the inverter and the
grid before connecting
RX-2505PU has terminals for on/off-grid. As shown in Figure 5-1,RX-2505PU has two AC output
ports and one
grid
power input port. An independent AC circuit breaker must be configured for
each system to safely disconnect the
connected
system
s
.
Engineers should refer to local standards to select cables. Cable length is generally 2 to 10 meters,
long cable will lead to voltage deviation from the rated value, consequently increasing the cross-
sectional area.
The rated current of single output terminal shall not exceed 5A, The total current shall not
exceed 10A
The maximum load current shall not exceed 10A
②
①
1
2
2.Grid voltage and grid frequency should be within the allowable range of inverter operation
the system to the grid.
Figure 5
-
1
-
Battery 240V terminals
Rev 20220610
RX2505PU
Page 18 of 32