5.0 DIP Switch Settings

(DIP SW 1) Momentary or Alternate triggering

5

0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1

6

0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1

7

0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1

8

0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1

Delay

(Sec.)

O

FF

30

60

90

120

150

180

210

240

270

300

330

360

390

420

450

AUTO ALERT TO EVAC SWITCHOVER TIMER SETTINGS. 0 = OFF. 1 = ON.

SW

ON

OFF

1

Triggers momentary 

Triggers alternate 

2

Alert/Evac ON

Not Used

SW

TRIGGER OPERATION & ALERT/EVAC SETTINGS

3

Front switches active

Front switches  de-activated

4

Alert/Evac OFF

Fig 3

Fig 4

Alternate: 

When the A 1741 is in Alternate mode (DIP switch1 

OFF) the closing contact must be held for the duration of the 
MP3 play time, if it is released before the MP3 ends the MP3 will 
stop playing immediately. If the contact is held closed continual-
ly the MP3 will continue to loop over and over until the contact 
is released. 

Momentary:

 In Momentary mode (DIP switch1 ON) a

momentary closing contact or pulse on the trigger pins will 
activate the MP3. The A 1741 will continue to play the MP3

till it finishes and will stop playing and wait for another trigger activation. 
To stop an MP3 playing when in Momentary mode the Cancel trigger or Cancel switch is used. A momentary closing 
contact on the Cancel trigger or closure of the Cancel switch will stop the MP3 playing (it is recommended that the 
Cancel contact or switch be held up to 2 seconds to ensure the MP3 stops playing).

(DIP SW 2) Alert/Evacuation Tones ON or OFF

When switch 2 is set to “OFF” the Alert and Evac tones cannot be triggered either by the front switches or the rear 
terminal contacts. If switch 2 is set to “ON” the Alert and Evac tones can always be triggered via the rear terminal con-
tacts. However the front switch triggering is dictated by DIP Switch 3.

(DIP SW 3) Front Switch Activation 

When switch 3 is set to “OFF” the front switches become de-activated from use. When these switches are de-activated 
the “Switches Disabled” LED on the front of the unit will illuminate. This function disables all the switches including the 
cancel, alert and evac. 

(DIP SW 4)

Not currently used

(DIP SW 5-8) Alert/Evacuation Tones change over option

The Alert and evacuation tones conform to Australian Standards AS1670.4 and are used to notify building occupants of 
an emergency situation. 
The Alert tone comes with a change over option which forces the A 1741 to switch from the Alert to the Evacuation 
tone after a prescribed time. DIP switches 5-8 set these change over times from 30 seconds to 450 seconds in 30 second 
intervals. If all DIP switches are set to “OFF” the changeover is disabled.

Summary of Contents for A 1741

Page 1: ...they activate This reduces the chance of accidental triggering Switched output The switched output terminal is triggered when any zone is activated The voltage is the same as the power supplied to the...

Page 2: ...es and Indicators These switches are used to trigger the Alert and Evacuation tones which conform to AS1670 4 The LED s inside the switches indicate when the associated message is playing The tones ca...

Page 3: ...ave a common ground 6 Message 1 8 Triggers The message triggers are activated by closing contacts on the rear of the unit whether by a normally open switch or a timer or controller The triggers can be...

Page 4: ...r Cancel switch is used A momentary closing contact on the Cancel trigger or closure of the Cancel switch will stop the MP3 playing it is recommended that the Cancel contact or switch be held up to 2...

Page 5: ...ll need a PC equipped with a SD card reader to do this not supplied Step by step guide to put a MP3 into Trigger1 with a Windows installed PC Step 1 Make sure the PC is on and card reader connected an...

Page 6: ...s MP3 file needs to be deleted and replaced by the MP3 file you want to play when you activate trigger1 The MP3 file name is not important only that there is one MP3 file in the trig1 folder Make sure...

Page 7: ...h settings The Alert tone comes with a change over option which forces the A 1741 to switch from Alert to the Evacuation tone after a prescribed time Use DIP switches 5 8 to adjust this time or switch...

Page 8: ...ard MP3 rates 128kbps recommended Sample rate All standard MP3 rates 44kHz recommended Channels Stereo or mono Specifications subject to change without notice 7 0 Troubleshooting NO Power Power LED do...

Reviews: