red lion TLA User Manual Download Page 3

3

OUTPUT SPECIFICATIONS

1. 

LIMIT AND ALARM OUTPUT RELAYS

:

Contact Rating

: 5 A @ 250 VAC or 30 VDC (resistive load).

Life Expectancy

: 100,000 cycles at max. load rating. (Decreasing load 

increases life expectancy.)

2. 

LIMIT OUTPUT

: TLA21000: Form-C relay; TLA11100: Form-A relay. 

Selectable for high or low trip activation. If the process temperature goes 

above the limit setpoint for a high trip, or below the limit setpoint for a low 

trip, the limit relay will de-energize to initiate a process shutdown. The limit 

output cannot be reset until the process temperature returns to the proper 

operating range; manual reset is required (local or remote).

Annunciators

:

“EX” - Lit when the process temperature exceeds the limit setpoint.

“OUT” - Lit when the limit output is de-energized.

3. 

ALARM OUTPUTS (Optional)

: One or two Form-A relays.

Modes

:

Absolute High Acting 

Absolute Low Acting

Deviation High Acting 

Deviation Low Acting

Inside Band Acting 

Outside Band Acting

Reset Action

: Programmable; automatic or latched. Latched alarms can be 

reset regardless of limit exceed condition.

Standby Mode

: Programmable; enable or disable.

Hysteresis

: Programmable.

Annunciator

: “A1” and “A2” programmable for normal or reverse acting.

Although Red Lion Controls Products are designed with a high degree of 

immunity to Electromagnetic Interference (EMI), proper installation and wiring 

methods must be followed to ensure compatibility in each application. The type 

of the electrical noise, source or coupling method into a unit may be different 

for various installations. Cable length, routing, and shield termination are very 

important and can mean the difference between a successful or troublesome 

installation. Listed are some EMI guidelines for a successful installation in an 

industrial environment.
1. A unit should be mounted in a metal enclosure, which is properly connected 

to protective earth.

2. Use shielded cables for all Signal and Control inputs. The shield connection 

should be made as short as possible. The connection point for the shield 

depends somewhat upon the application. Listed below are the recommended 

methods of connecting the shield, in order of their effectiveness.

a. Connect the shield to earth ground (protective earth) at one end where the 

unit is mounted.

b. Connect the shield to earth ground at both ends of the cable, usually when 

the noise source frequency is over 1 MHz.

3. Never run Signal or Control cables in the same conduit or raceway with AC 

power lines, conductors, feeding motors, solenoids, SCR controls, and 

heaters, etc. The cables should be run through metal conduit that is properly 

grounded. This is especially useful in applications where cable runs are long 

and portable two-way radios are used in close proximity or if the installation 

is near a commercial radio transmitter. Also, Signal or Control cables within 

an enclosure should be routed as far away as possible from contactors, 

control relays, transformers, and other noisy components. 

4. Long cable runs are more susceptible to EMI pickup than short cable runs.
5. In extremely high EMI environments, the use of external EMI suppression 

devices such as Ferrite Suppression Cores for signal and control cables is 

effective. The following EMI suppression devices (or equivalent) are 

recommended:

Fair-Rite part number 0443167251 (RLC part number FCOR0000)

Line Filters for input power cables:

Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000)

6. To protect relay contacts that control inductive loads and to minimize radiated 

and conducted noise (EMI), some type of contact protection network is 

normally installed across the load, the contacts or both. The most effective 

location is across the load.

a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide 

varistor (MOV) across an AC inductive load is very effective at reducing 

EMI and increasing relay contact life.

b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor 

switch, care must be taken not to exceed the breakdown voltage of the 

transistor when the load is switched. One of the most effective ways is to 

place a diode across the inductive load. Most RLC products with solid 

state outputs have internal zener diode protection. However external diode 

protection at the load is always a good design practice to limit EMI. 

Although the use of a snubber or varistor could be used.

RLC part numbers: Snubber: SNUB0000

   

Varistor: ILS11500 or ILS23000

7. Care should be taken when connecting input and output devices to the 

instrument. When a separate input and output common is provided, they 

should not be mixed. Therefore a sensor common should NOT be connected 

to an output common. This would cause EMI on the sensitive input common, 

which could affect the instrument’s operation.
Visit RLC’s web site at http://www.redlion.net/Support/InstallationConsiderations.

html for more information on EMI guidelines, Safety and CE issues as they 

relate to Red Lion Controls products.

EMC INSTALLATION GUIDELINES

RBD48111

RBDLA210

REPLACEMENT 

OUTPUT BOARD

TLA11100

Form-A Relay

Form-A Relay

Form-A Relay

TLA21000

Form-A Relay

Form-C Relay

PART NUMBERS

ALARM 2 OUTPUT

ALARM 1 OUTPUT

LIMIT OUTPUT

18 to 36 VDC / 24 VAC

85 to 250 VAC

RBD48111

RBDLA210

REPLACEMENT 

OUTPUT BOARD

TLA11110

Form-A Relay

Form-A Relay

Form-A Relay

TLA21010

Form-A Relay

Form-C Relay

PART NUMBERS

ALARM 2 OUTPUT

ALARM 1 OUTPUT

LIMIT OUTPUT

ORDERING INFORMATION

Summary of Contents for TLA

Page 1: ...to activate according to a variety of actions Absolute HI or LO Deviation HI or LO and Band IN or OUT with adjustable hysteresis A standby feature suppresses the alarm during power up until the process stabilizes outside the alarm region The unit is constructed of a lightweight high impact plastic case with a tinted front panel The front panel meets NEMA 4X IP65 specifications when properly instal...

Page 2: ...nel latch Panel latch can be installed for vertical or horizontal instrument stacking One piece tinted plastic bezel Bezel assembly with circuit boards can be removed from the case to change the output board without removing the case from the panel or disconnecting wiring Unit meets NEMA 4X IP65 requirements for indoor use when properly installed Flame resistant Installation Category II Pollution ...

Page 3: ...ded This is especially useful in applications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter Also Signal or Control cables within an enclosure should be routed as far away as possible from contactors control relays transformers and other noisy components 4 Long cable runs are more susceptible to EMI pi...

Page 4: ... ventilation to ensure that the maximum operating temperature range is not exceeded Caution Disconnect power to the unit and to the output control circuits to eliminate the potential shock hazard when removing the bezel assembly Unit Removal Procedure To remove a unit from the panel first loosen the panel latch screws Insert flat blade screwdrivers between the latch and the case on either side of ...

Page 5: ...ging applications two or more thermocouple probes may be connected to the TLA always use the same type Paralleling a single thermocouple to more than one TLA is not recommended Generally the red wire from the thermocouple is negative and connected to the TLA s common RTD When connecting the RTD be certain that the connections are clean and tight RTD sensors have a higher degree of accuracy and sta...

Page 6: ...ode In this mode the process temperature is displayed in the main top display and the limit setpoint is displayed in the secondary bottom display When changes to the parameter configurations are needed the P button is pressed and the TLA will enter into the Parameter Mode PARAMETER CONFIGURATION BASIC STARTUP For basic start up it is important to verify or change Input Parameter Module 1 IN parame...

Page 7: ...egree resolution If changed be sure to check all parameters FLtr Digital Input Filtering and Display Update Select the relative degree of input signal filtering and display update rate The filter is an adaptive digital filter that discriminates between measurement noise and actual process changes Therefore the influence on step response time is minimal If the signal is varying too greatly due to m...

Page 8: ...n low acting with positive alarm value d LO deviation high acting with negative value d HI or band inside acting b IN is selected for the alarm action the indicator is OFF when the alarm output is ON See the Alarms section for complete details of each action If changed check alarm values The alarm values are either absolute values or relative to the limit setpoint value deviation and band alarms A...

Page 9: ...r this flag perform calibration procedure as noted in the Calibration section Alternatively stepping through one of the calibration procedures clears the error flag but does NOT validate the calibration accuracy in any manner USER PARAMETER VALUE CHART TLA Number _____________ MNEMONIC PARAMETER USER SETTING Limit Setpoint Alarm 2 Value Password Alarm 1 Value Input Parameters MNEMONIC PARAMETER US...

Page 10: ... ON OFF Energized High Trip Action Low Trip Action 5 0 Alarms Optional The alarm action figures describe the status of the alarm output and the front panel indicator for various over under temperature conditions The alarm output wave form is shown with the output in the automatic reset mode Select the alarm action with care in some configurations the front panel indicator LED might be OFF while th...

Page 11: ...e The TLA display should equal the calibrated probe temperature Tolerance is 1ºC 4 Calibrate the cold junction temperature if out of tolerance RTD Ohms Reading Check 1 Connect RTD simulator with an accuracy of 0 1 ohm or better capable of operating with less than 150 µA to terminals 8 9 10 2 Configure Input Parameters Module 1 for linear ohms rLin input under tYPE 3 Compare the TLA read out with t...

Page 12: ...rm up period before starting this procedure Do not use thermocouple wire for the millivolt or RTD ohms calibration This procedure may be aborted by disconnecting power to the TLA before exiting the configuration mode The existing calibration settings remain in affect Note After completing any of the calibration sequences the TLA defaults the input sensor type to thermocouple type J tc J Be sure to...

Page 13: ...ISPLAY 1 Input is below range of TLA 2 Temperature below range of input probe 3 Defective or incorrect transmitter or probe 4 Excessive low temperature for probe 5 Loss of setup parameters OLOL OR ULUL IN LOWER DISPLAY 1 Signal input exceeds allowable range by 5 1 Check remote signal source 1 Check input parameters 2 Change to input sensor with a lower temperature range 3 Replace transmitter or pr...

Page 14: ...t Board RBDLA210 AL1 LIMIT E B 0 7 8 4 MD1797 A2 A1 OUT EX P OUTPUT BOARD POWER CPU BOARD SUPPLY BOARD OUTPUT BOARD CONNECTOR BEZEL DISPLAY BOARD ASSEMBLY BEZEL BOARD LATCH DISPLAY BOARD CONNECTOR 9 0 Terminal Configurations 50 60 HZ 8VA 14 12 85 250 VAC AC 1 A2 N O 13 COMM COMM A1 N O LIMIT RELAY ALARM RELAYS 4 N O 5 AC 11 2 3 6 REMOTE RESET 9 TC 10 RTD 8 7 COMM 50 60 HZ 9VA AC 24V 10 DC 18 36V 7...

Page 15: ...15 This page intentionally left blank ...

Page 16: ...h Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pursuant to the Magnuson Moss Warranty Act P L 93 637 as now in effect or as amended hereafter No warranties expressed or implied are created with respect to The Company s products except those...

Reviews: