11

Alarm Reset Sequence

Alarm Standby Delay Sequence

ON

OFF

ALARM VALUE

OFF

ON

OFF

OFF

TIME

AUTOMATIC

RESET

MANUAL

RESET

MANUAL RESET

PERFORMED BY OPERATOR

INPUT

ALARM MODE

(ABSOLUTE LOW ACTING SHOWN)

ON

OFF

ON

OFF

ON

OFF

ON

ON

OFF

ON

OFF

ON

UNIT

POWER-ON

STANDBY

ENABLED

STANDBY
DISABLED

TIME

INPUT

ALARM VALUE

ALARM MODE

(ABSOLUTE LOW ACTING

W/AUTO-RESET SHOWN)

CALIBRATION CHECKS 

The instrument has been fully calibrated at the factory for all input types. If 

the unit appears to be indicating or controlling incorrectly, see the Troubleshooting 

section before attempting this procedure.

If the TLA is suspected of reading incorrectly, the instrument may be checked 

for indication accuracy without disturbing the factory calibration. The following 

procedures may be used for this purpose.

Note: Allow ½ hour warm-up before checking these parameters.

mV Reading Check

1. Connect a DC mV source with an accuracy of 0.03% or better to terminal #8 

(-) & #9 (+).

2. Configure Input Parameters Module 1 for linear mV (Lin) input, under tYPE.

3. Compare the TLA read-out to the standard at various points over the range 

(-5.00 mV to 56.00 mV). The tolerance is ±(0.15% of r 1 LSD).

4. Calibrate the TLA if the readings are out of tolerance.

Thermocouple Cold Junction Temperature Check

1. Connect a thermocouple probe of known accuracy (Types T, E, J, K, N only) 

to TLA. Select the probe used in Configure Module 1.

2. Connect a reference temperature probe to measuring end of thermocouple to 

monitor temperature. Allow sufficient time for temperatures to equalize.

3. Compare TLA display with reference temperature probe. The TLA display 

should equal the calibrated probe temperature.  (Tolerance is ±1ºC.)

4. Calibrate the cold junction temperature if out of tolerance.

RTD Ohms Reading Check

1. Connect RTD simulator (with an accuracy of 0.1 ohm or better) capable of 

operating with less than 150 µA to terminals #8, #9, & #10.

2. Configure Input Parameters Module 1 for linear ohms (rLin) input, under tYPE.

3. Compare the TLA read-out with the RTD simulator at various points over the 

range 2.0 to 300.0 ohms. The tolerance is ±(0.3% of span + 1 LSD).

4. Calibrate the TLA RTD ohms if out of tolerance.

Error Flag E-CL

If error flag “E-CL” appears at power-up, a loss of calibration parameters due 

to noise spikes has occurred. Entering code 77 twice in Factory Service 

Operations Module (9-FS) erases the TLA calibration values and defaults the 

values to nominal settings. Reading errors of ±10% may result. It is recommended 

that the TLA be fully recalibrated. If using thermocouple only, the RTD 

calibration need not be performed.

Note: the “E-CL” flag may be cleared by “stepping” through cold junction 

calibration procedure without the need to change any calibration values. A 

±10% reading error will still exist.

INPUT

DEVIATION LOW-ACTING WITH POSITIVE ALARM VALUE (d-LO)

SP + AL

OUTPUT OFF

LED ON

OUTPUT ON

LED OFF

SP

HYS

OUTPUT ON

LED OFF

OUTPUT OFF

LED ON

SP + (-AL)

DEVIATION LOW-ACTING WITH NEGATIVE ALARM VALUE (d-LO)

INPUT

LED ON

OUTPUT ON

LED OFF

OUTPUT OFF

LED ON

OUTPUT ON

LED OFF

OUTPUT OFF

SP

HYS

OUTPUT ON

LED OFF

OUTPUT OFF

LED ON

OUTPUT ON

LED OFF

INPUT

BAND INSIDE ACTING (b-IN)

SP + AL

OUTPUT OFF

LED ON

OUTPUT ON

LED OFF

OUTPUT OFF

LED ON

SP - AL

SP

HYS

HYS

SP - AL 

LED ON

OUTPUT ON

LED OFF

OUTPUT OFF

LED ON

OUTPUT ON

SP + AL

BAND OUTSIDE ACTING (b-Ot)

INPUT

LED OFF

OUTPUT OFF

LED ON

OUTPUT ON

LED OFF

OUTPUT OFF

HYS

HYS

SP

Summary of Contents for TLA

Page 1: ...to activate according to a variety of actions Absolute HI or LO Deviation HI or LO and Band IN or OUT with adjustable hysteresis A standby feature suppresses the alarm during power up until the process stabilizes outside the alarm region The unit is constructed of a lightweight high impact plastic case with a tinted front panel The front panel meets NEMA 4X IP65 specifications when properly instal...

Page 2: ...nel latch Panel latch can be installed for vertical or horizontal instrument stacking One piece tinted plastic bezel Bezel assembly with circuit boards can be removed from the case to change the output board without removing the case from the panel or disconnecting wiring Unit meets NEMA 4X IP65 requirements for indoor use when properly installed Flame resistant Installation Category II Pollution ...

Page 3: ...ded This is especially useful in applications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter Also Signal or Control cables within an enclosure should be routed as far away as possible from contactors control relays transformers and other noisy components 4 Long cable runs are more susceptible to EMI pi...

Page 4: ... ventilation to ensure that the maximum operating temperature range is not exceeded Caution Disconnect power to the unit and to the output control circuits to eliminate the potential shock hazard when removing the bezel assembly Unit Removal Procedure To remove a unit from the panel first loosen the panel latch screws Insert flat blade screwdrivers between the latch and the case on either side of ...

Page 5: ...ging applications two or more thermocouple probes may be connected to the TLA always use the same type Paralleling a single thermocouple to more than one TLA is not recommended Generally the red wire from the thermocouple is negative and connected to the TLA s common RTD When connecting the RTD be certain that the connections are clean and tight RTD sensors have a higher degree of accuracy and sta...

Page 6: ...ode In this mode the process temperature is displayed in the main top display and the limit setpoint is displayed in the secondary bottom display When changes to the parameter configurations are needed the P button is pressed and the TLA will enter into the Parameter Mode PARAMETER CONFIGURATION BASIC STARTUP For basic start up it is important to verify or change Input Parameter Module 1 IN parame...

Page 7: ...egree resolution If changed be sure to check all parameters FLtr Digital Input Filtering and Display Update Select the relative degree of input signal filtering and display update rate The filter is an adaptive digital filter that discriminates between measurement noise and actual process changes Therefore the influence on step response time is minimal If the signal is varying too greatly due to m...

Page 8: ...n low acting with positive alarm value d LO deviation high acting with negative value d HI or band inside acting b IN is selected for the alarm action the indicator is OFF when the alarm output is ON See the Alarms section for complete details of each action If changed check alarm values The alarm values are either absolute values or relative to the limit setpoint value deviation and band alarms A...

Page 9: ...r this flag perform calibration procedure as noted in the Calibration section Alternatively stepping through one of the calibration procedures clears the error flag but does NOT validate the calibration accuracy in any manner USER PARAMETER VALUE CHART TLA Number _____________ MNEMONIC PARAMETER USER SETTING Limit Setpoint Alarm 2 Value Password Alarm 1 Value Input Parameters MNEMONIC PARAMETER US...

Page 10: ... ON OFF Energized High Trip Action Low Trip Action 5 0 Alarms Optional The alarm action figures describe the status of the alarm output and the front panel indicator for various over under temperature conditions The alarm output wave form is shown with the output in the automatic reset mode Select the alarm action with care in some configurations the front panel indicator LED might be OFF while th...

Page 11: ...e The TLA display should equal the calibrated probe temperature Tolerance is 1ºC 4 Calibrate the cold junction temperature if out of tolerance RTD Ohms Reading Check 1 Connect RTD simulator with an accuracy of 0 1 ohm or better capable of operating with less than 150 µA to terminals 8 9 10 2 Configure Input Parameters Module 1 for linear ohms rLin input under tYPE 3 Compare the TLA read out with t...

Page 12: ...rm up period before starting this procedure Do not use thermocouple wire for the millivolt or RTD ohms calibration This procedure may be aborted by disconnecting power to the TLA before exiting the configuration mode The existing calibration settings remain in affect Note After completing any of the calibration sequences the TLA defaults the input sensor type to thermocouple type J tc J Be sure to...

Page 13: ...ISPLAY 1 Input is below range of TLA 2 Temperature below range of input probe 3 Defective or incorrect transmitter or probe 4 Excessive low temperature for probe 5 Loss of setup parameters OLOL OR ULUL IN LOWER DISPLAY 1 Signal input exceeds allowable range by 5 1 Check remote signal source 1 Check input parameters 2 Change to input sensor with a lower temperature range 3 Replace transmitter or pr...

Page 14: ...t Board RBDLA210 AL1 LIMIT E B 0 7 8 4 MD1797 A2 A1 OUT EX P OUTPUT BOARD POWER CPU BOARD SUPPLY BOARD OUTPUT BOARD CONNECTOR BEZEL DISPLAY BOARD ASSEMBLY BEZEL BOARD LATCH DISPLAY BOARD CONNECTOR 9 0 Terminal Configurations 50 60 HZ 8VA 14 12 85 250 VAC AC 1 A2 N O 13 COMM COMM A1 N O LIMIT RELAY ALARM RELAYS 4 N O 5 AC 11 2 3 6 REMOTE RESET 9 TC 10 RTD 8 7 COMM 50 60 HZ 9VA AC 24V 10 DC 18 36V 7...

Page 15: ...15 This page intentionally left blank ...

Page 16: ...h Buyer its employees or sub contractors are or may be to any extent liable including without limitation penalties imposed by the Consumer Product Safety Act P L 92 573 and liability imposed upon any person pursuant to the Magnuson Moss Warranty Act P L 93 637 as now in effect or as amended hereafter No warranties expressed or implied are created with respect to The Company s products except those...