Revised 2016-02-12
Hardware Installation
Battery
2-30
Sixnet
®
SeriesRAM
®
9000
Hardware Guide
Note:
The unit may ship with a battery pull-tab insulator in place that prevents the battery from dis-
charging prior to first use. Remove the insulator when you are ready to install and use the unit. The
insulator is removed by simply pulling it out.
Note:
The battery does not provide power to the unit either as a main power source or as a
backup. It only powers the SRAM memory and real-time clock, and only when there is no power
supplied to either P1 or P2.
Note:
For full temperature ATEX and/or IECeX compliance you must use a battery rated to 125C
such as the Panasonic BR1225A/BN.
Battery Removal and Installation:
Step 1:
Open Battery door on bottom of unit by removing the single screw.
Step 2:
Insert a small flat-head screwdriver into the slot as shown below: