background image

4.

RATE DISPLAY

: 6-digits, may be enabled or disabled in any count mode

Display Range

: 0 to 999999

Over Range Display

: “



Maximum Frequency

: 25 KHz

Minimum Frequency

: 0.01 Hz

Accuracy

: ±0.01%

5.

COUNT/RATE SIGNAL INPUTS (INPUT A and INPUT B)

:

See Section 2.0 Setting the DIP Switches for complete Input specifications. 
DIP switch selectable inputs accept pulses from a variety of sources. Both 
inputs allow selectable active low or active high logic, and selectable input 
filtering for low frequency signals or switch contact debounce.

Input A

: Logic level or magnetic pickup signals.

Trigger levels: V

IL

 = 1.25 V max; V

IH

 = 2.75 V min; V

MAX

 = 28 VDC

Mag. pickup sensitivity: 200 mV peak, 100 mV hysteresis, 40 V peak max.

Input B

: Logic level signals only

Trigger levels: V

IL

 = 1.0 V max; V

IH

 = 2.4 V min; V

MAX

 = 28 VDC

6.

USER INPUT

: Programmable

Software selectable for active logic state: active low, pull-up (24.7 K

 to +5 

VDC) or active high, pull-down resistor (20 K

).

Trigger levels: V

IL

 = 1.0 V max; V

IH

 = 2.4 V min; V

MAX

 = 28 VDC

Response Time: 10 msec typ.; 50 msec debounce (activation and release)

7.

MEMORY

: Nonvolatile E

2

PROM retains all programming parameters and 

count values when power is removed.

8.

OUTPUTS

:

Type

: Dual Form C contacts

Isolation to Input & User/Exc Commons

: 1400 Vrms for 1 min. 

Working Voltage: 150 Vrms

Contact Rating

: 5 amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 

H.P. @ 120 VAC (inductive load)

Life Expectancy

: 100 K cycles min. at full load rating. External RC snubber 

extends relay life for operation with inductive loads.

Response Time

: Turn On or Off: 4 msec max.

 9. 

ENVIRONMENTAL CONDITIONS

:

Operating temperature

: 0 to 50 °C

Storage temperature

: -40 to 70 °C

Operating and storage humidity

: 0 to 85% max. RH (non-condensing)

Vibration According to IEC 68-2-6

: Operational 5 to 150 Hz, in X, Y, Z 

direction for 1.5 hours, 2g’s.

Shock According to IEC 68-2-27

: Operational 30 g (10g relay), 11 msec in 3 

directions.

Altitude

: Up to 2,000 meters

10.

CONNECTIONS

: High compression cage-clamp terminal block

Wire Strip Length

: 0.3" (7.5 mm)

Wire Gage

: 30-14 AWG copper wire

Torque

: 4.5 inch-lbs (0.51 N-m) max.

11. 

CONSTRUCTION

: This unit is rated for NEMA 4X/IP65 outdoor use. IP20 

Touch safe. Installation Category II, Pollution Degree 2. One piece bezel/
case. Flame resistant. Synthetic rubber keypad. Panel gasket and mounting 
clip included.

12.

CERTIFICATIONS AND COMPLIANCES

:

SAFETY

Type 4X Enclosure rating (Face only), UL50
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment 

for measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529
IP20 Enclosure rating (Rear of unit), IEC 529

For Model No. PAXLCRU0 Only

: UL Listed, File # E137808, UL508, 

CSA C22.2 No. 14-M95

LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: Electrical Equipment for Measurement, 

Control and Laboratory use.

Notes:

1. Criterion A: Normal operation within specified limits.
2. Criterion C: Temporary loss of function which requires operator 
intervention.

13.

WEIGHT

: 10.4 oz. (295 g)

1.0 I

NSTALLING THE

 M

ETER

Installation

The PAX Lite meets NEMA 4X/IP65 requirements when properly installed. 

The unit is intended to be mounted into an enclosed panel. Prepare the panel 
cutout to the dimensions shown. Remove the panel latch from the unit. Slide the 
panel gasket over the rear of the unit to the back of the bezel. The unit should 
be installed fully assembled. Insert the unit into the panel cutout. 

While holding the unit in place, push the panel latch over the rear of the unit 

so that the tabs of the panel latch engage in the slots on the case. The panel latch 

should be engaged in the farthest forward slot 

possible. To achieve a proper seal, tighten the 

latch screws evenly until the unit is snug 

in the panel (Torque to approximately 

7 in-lbs [79N-cm]). Do not over-

tighten the screws.

Installation Environment

The unit should be installed in a location that does not exceed the maximum 

operating temperature and provides good air circulation. Placing the unit near 
devices that generate excessive heat should be avoided.

The bezel should be cleaned only with a soft cloth and neutral soap product. 

Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the 
aging process of the bezel.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the 

keypad of the unit.

-.00

(92  )

-.0

+.8

3.62

+.03

(45  )

1.77

-.0

+.5

-.00

+.02

PANEL CUT-OUT

PANEL
GASKET

BEZEL

PANEL
MOUNTING
SCREWS

LATCHING
SLOTS

PANEL

LATCHING
TABS

PANEL
LATCH

Immunity to Industrial Locations:

Emissions:

Electrostatic discharge

EN 61000-4-2

Criterion A
4 kV contact discharge
8 kV air discharge

Electromagnetic RF fields

EN 61000-4-3

Criterion A
10 V/m

2 kV L&N-E power

Fast transients (burst)

EN 61000-4-4

Criterion A
2 kV power
1 kV signal

Surge 

EN 61000-4-5

Criterion C
1 kV L-L, 

0.5 cycle

RF conducted interference

EN 61000-4-6

Criterion A
3 V/rms 

Voltage dip/interruptions

EN 61000-4-11

Criterion A

Emissions

EN 55011

Class A

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Summary of Contents for PAX LITE PAXLCR00

Page 1: ...t If equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired Do not use this meter to directly command motors valves or other actuators not equipped with safeguards To do so can be potentially harmful to persons or equipment in the event of a fault to the meter SPECIFICATIONS 1 DISPLAY 6 digit 0 56 14 2 mm intensity adjustable Red LE...

Page 2: ...ents for electrical equipment for measurement control and laboratory use Part 1 IP65 Enclosure rating Face only IEC 529 IP20 Enclosure rating Rear of unit IEC 529 For Model No PAXLCRU0 Only UL Listed File E137808 UL508 CSA C22 2 No 14 M95 LISTED by Und Lab Inc to U S and Canadian safety standards ELECTROMAGNETIC COMPATIBILITY Emissions and Immunity to EN 61326 Electrical Equipment for Measurement ...

Page 3: ...xternal EMI suppression devices such as ferrite suppression cores is effective Install them on Signal and Control cables as close to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install line filters on the power input cable to the unit to suppress power line interference Install them near the power entry point of t...

Page 4: ... A COMMON 4 5 6 7 5 24V EXC 3 t 2 5 A MAX Resistor to Limit Current ON 1 2 3 4 AC 5 INPUT A INPUT B COMMON 7 6 5 24V EXC COMMON 3 4 1 2 ON 3 4 2 2 kΩ 5 INPUT A INPUT B COMMON 7 6 5 24V EXC COMMON 3 4 2 1 ON 3 4 O C NPN 5 INPUT A INPUT B COMMON 7 6 5 24V EXC COMMON 3 4 1 2 3 ON 4 O C PNP 5 INPUT A INPUT B COMMON 7 6 5 24V EXC COMMON 3 4 1 2 3 4 ON COMMON 5 V 5 INPUT A INPUT B COMMON 7 6 5 24V EXC C...

Page 5: ...the display alternates between the present parameter and the selections value for that parameter The SEL and RST buttons are used to move through the selections values for that parameter Pressing the PAR button stores and activates the displayed selection value This also advances the meter to the next parameter For numeric values the value is displayed with one digit flashing initially the right m...

Page 6: ...g applications it is recommended to use Count with Direction for the count mode Simply leave the direction input unconnected Shaded area selections only apply when Counter B is enabled Dual Count mode or batch counter Counter A Subtract Counter A Add Counter A Add Counter A Add Quad A Count A Quad A Count A Quad A Count A Counter B Add Counter A Add Counter A Add Rate only Counter A Direction Coun...

Page 7: ...osition Number of Pulses Given that 128 pulses are equal to 1 foot display total feet with a one hundredth resolution Scale Factor 1 00 x 100 128 Scale Factor 0 007812 x 100 Scale Factor 0 7812 EXAMPLE 2 A manufacturer wants to count the total number of bricks molded in a process yielding 12 bricks per mold The counter receives 1 pulse per mold and should increase by 12 for each pulse received Sin...

Page 8: ...otted to a Display value of 0 and Input value of 0 0 Hz A linear relationship is formed between these points to yield a rate display value that corresponds to the incoming input signal rate The meter is capable of showing a rate display value for any positive slope linear process SCALING CALCULATION FOR KEY IN STYLE If a display value versus input signal in pulses per second is known then those va...

Page 9: ...s this code to be entered at the prompt in order to access Full Programming mode Quick Programming mode if enabled is accessed before the prompt appears PROGRAMMING SECURITY CODE to to USER INPUT FUNCTION USER INPUT STATE SECURITY CODE MODE WHEN PAR KEY IS PRESSED FULL PROGRAMMING MODE ACCESS 0 Full Programming Immediate Access not ______ 1 99 Quick Programming After Quick Programming with correct...

Page 10: ...ns to Press the PAR button to exit the module VIEW MODEL AND VERSION DISPLAY Select the display to which the Setpoint is assigned SETPOINT ASSIGNMENT Entering Code 66 will overwrite all user settings with the factory default settings The meter will display and then return to Press the PAR button to exit the module RESTORE FACTORY DEFAULT SETTINGS Some Setpoint parameters will not appear depending ...

Page 11: ...ction is programmed for timed output SETPOINT 2 OUTPUT OFF AT SETPOINT 1 SP2 Only High Acting Boundary Type activates the output when the assigned display value equals or exceeds the Setpoint value Low Acting activates the output when the assigned display value is less than or equal to the Setpoint SETPOINT BOUNDARY TYPE This parameter only applies to Low Acting Boundary Type setpoints Select to d...

Page 12: ...oint Annunciator SP1 Only Setpoint Value Setpoint Output Time out Setpoint Output Logic Exit Programming Counter Auto Reset Setpoint Boundary Type Setpoint Output Power up State Setpoint Standby Operation SP2 Output Off at SP1 Output SP1 Output Off at SP2 Output SEL SEL SEL SEL SEL PAR PAR PAR PAR PAR Counter B Scale Factor Counter B Decimal Point User Input Function Dual Count or Batch Only Count...

Reviews: