background image

7

The following list outlines conditions that are unique to factory recalibration:

1. Unlike the field scaling procedures, there are no software under and over

range indications while performing a factory recalibration. Therefore,
care must be taken to insure the selected range extents are not exceeded.
The minimum scale and full scale calibration values must be set to the
extents of the range being calibrated.
For example: If the Input Range DIP switches are set for the 4-20 mA

range, minimum scale must be set at 4 mA, and full scale must be set
at 20 mA.

2. At least one input calibration must be completed before calibrating any

output range. When calibrating the input voltage range, it is
recommended that a range above 1 V be used to provide better accuracy.

3. If multiple input or output ranges are to be calibrated, DO NOT

REMOVE POWER TO CHANGE THE RANGE. Place the appropriate
Field/Fact. DIP switch; S1-1 for outputs, and S1-2 for inputs to the down
position, and set the remaining DIP switches for the range to be
calibrated. 

Note: Be sure to change the terminal wiring to match the

Input or Output range DIP switch settings before performing the
calibration procedure. Set calibration source to 0 V or 0 mA before
changing wiring.

INPUT RECALIBRATION

1. To enter the factory calibration mode, set switches S1-1 and S1-2 down, S1-

3 through S1-5 up, and S1-6 through S1-10 down.

2. Connect a signal source to the correct input terminals based on the

maximum signal input to be calibrated. If an output range will be calibrated
after the input range is calibrated, connect a voltage or current meter to the
appropriate output terminals at this time.

3. Apply power to the IAMA. After the version number indication, the green

LED will flash rapidly for 2 seconds indicating the factory calibration mode
has been entered. Allow the IAMA to warm up for 5 minutes minimum and
follow the manufacturer’s warm up procedure for the calibration source.

4. Set the Input Range DIP switches to the desired input range according to

Table 3.

5. Complete Steps 2.6 through 2.10 of Input Scaling Using Field

Configuration. 

Note: There will be no over or under range indication of the

LED’s during this procedure, so use care not to exceed the range extents.

6. If an output is to be calibrated, continue from #2 of Output Recalibration

below. If no further input or output calibration is to be completed, return S1-
1 and S1-2 to the down position and remove power from the IAMA. Apply
power and check for accurate operation of the newly calibrated range or
ranges.

OUTPUT RECALIBRATION

1. Complete 1 through 5 of the input recalibration procedure for at least one

range.

2. For current output, set 20 mA/1 mA switch (S2) to desired full scale output.

(20 mA - on; 1 mA - off)

3. Set Output Field/Fact. switch (S1 switch 1) to the off position.
4. Set the Output Range DIP switches to the desired output range according to

Table 2.

5. Complete Steps 4.10 through 4.14 of Output Scaling Using Field

Configuration. 

Note: There will be no over or under range indication of the

LED’s during this procedure, so use care not to exceed the range extents.

6. If no further calibration is to be completed, return S1-1 and S1-2 to the down

position and remove power from the IAMA. Apply power and check for
accurate operation of the newly calibrated range or ranges.

RECALIBRATING FACTORY STORED VALUES

WARNING: Read the complete procedure at least

once before attempting to recalibrate the factory
values. This procedure should only be
performed due to factory checksum error or
unacceptable error. This procedure should be
performed by qualified technicians using
accurate calibration equipment.

TROUBLESHOOTING

For further technical assistance, contact technical support at the appropriate company numbers listed.

INSTALLATION

The unit is equipped with a universal mounting foot for attachment to standard DIN style mounting rails, including G profile rail

according to EN50035 - G32 , and top hat (T) profile rail according to EN50022 - 35 x 7.5 and 35 x 15. The unit should be installed in a
location that does not exceed the maximum operating temperature and provides good air circulation. Placing the unit near devices that
generate excessive heat should be avoided.

G Rail Installation

To install the IAMA on a “G”

style DIN rail, angle the module
so that the upper groove of the
“foot” catches under the lip of the
top rail. Push the module toward
the rail until it snaps into place.
To remove a module from the
rail, push up on the bottom of the
module while pulling out and
away from the rail.

T Rail Installation

To install the IAMA on a “T”

style rail, angle the module so
that the top groove of the “foot”
is located over the lip of the top
rail. Push the module toward the
rail until it snaps into place. To
remove a module from the rail,
insert a screwdriver into the slot
on the bottom of the “foot”, and
pry upwards on the module until
it releases from the rail.

Summary of Contents for IAMA Series

Page 1: ...the field if desired The modules environmental operating temperature range is 20 C to 65 C DIN rail mounting saves time and panel space The units are equipped with universal mounting feet for attachment to standard DIN style rails including top hat profile rail according to EN50022 35x7 5 and 35 x 15 and G profile rail according to EN50035 G32 SAFETY SUMMARY All safety related regulations local co...

Page 2: ...which restores the respective setting The Factory and Field E2PROM locations contain the same calibration values when the IAMA is received from the factory Therefore until the IAMA is field scaled factory and field modes perform identically See SCALING PROCEDURE for detailed instructions on field programming the IAMA The units can be scaled to any minimum scale and full scale values within the ext...

Page 3: ...ive earth b Connect the shield to earth ground at both ends of the cable usually when the noise source frequency is above 1 MHz c Connect the shield to common of the unit and leave the other end of the shield unconnected and insulated from earth ground 2 Never run Signal or Control cables in the same conduit or raceway with AC power lines conductors feeding motors solenoids SCR controls and heater...

Page 4: ...t 100 VDC Terminal 10 max signal input 100 mA Terminal 12 signal common 1 3 Set Input Range switches S1 switches 6 through 10 to the desired Input Range See Table 3 0 to 10 VDC range shown 1 4 Set Input Field Fact switch S1 switch 2 to the off position 1 5 Apply power to the IAMA Solid illumination of Green LED if signal is within the minimum and maximum limits of the selected input range Slow bli...

Page 5: ...the Red LED blinks slowly and the Green LED turns off Removing power aborts scaling begin at Step 2 1 2 9 Apply maximum scale input The Red and Green LEDs will alternately blink 2 10 Set Input Field Fact switch S1 switch 2 to the on position Red LED extinguishes and Green LED becomes solid Your scaled values are now saved and recalled if the Input Field Fact switch S1 switch 2 is in the on positio...

Page 6: ...max signal input 10 VDC Terminal 9 max signal input 100 VDC Terminal 10 max signal input 100 mA Terminal 12 signal common 4 9 Apply power to the IAMA and allow a warm up period of five minutes 4 10 Set Output Field Fact switch S1 switch 1 to the on position The Red and Green LEDs will alternately blink If Red LED blinks slowly increase signal until Red and Green LEDs alternately blink 4 11 Adjust ...

Page 7: ... calibration is to be completed return S1 1 and S1 2 to the down position and remove power from the IAMA Apply power and check for accurate operation of the newly calibrated range or ranges OUTPUT RECALIBRATION 1 Complete 1 through 5 of the input recalibration procedure for at least one range 2 For current output set 20 mA 1 mA switch S2 to desired full scale output 20 mA on 1 mA off 3 Set Output ...

Page 8: ...elies on no other warranties or affirmations APPLICATION Cost efficiency measurements of a printing company included the reduction of bulk stock of the various inks used in their printing processes The company currently had various ink flow and level devices with different current and voltage outputs and wanted to record these measurements into a control room PC Several IAMA Universal Signal Condi...

Reviews: