background image

5

2.1  Remove power.

2.2  Connect signal source to the correct input terminals based on the maximum signal

input.

Terminal 7: max. signal input 1 VDC
Terminal 8: max. signal input 10 VDC
Terminal 9: max. signal input 100 VDC
Terminal 10: max. signal input 100 mA
Terminal 12: signal common

2.3  Set Input Range switches (S1 switches 6 through 10) to the desired input range

(See Table 3). Select the lowest possible range that will support the desired
maximum signal. Example: if the desired span is 20 mV to 85 mV, the best range
selection is 0 to 100 mV. The 0 to 200 mV will also suffice, but the accuracy will be
reduced. (0 to 10 VDC range shown).

2.4  Set Input Field/Fact. switch (S1 switch 2) to the off position.

2.5  Apply power to the IAMA and allow a warm up period of five minutes. Follow

the manufacturer’s warm up procedure for the calibration source.

2.6  Set Input Field/Fact. switch (S1 switch 2) to the on position.

The Red and Green LEDs will alternately blink.

2.7  Apply desired minimum scale signal.

2.8  Set Input Field/Fact. switch (S1 switch 2) to the off position.

The Red and Green LEDs will alternately blink.
If the signal is equal or below the minimum limit of the selected range, the Red LED

blinks slowly and the Green LED turns off. Removing power aborts scaling, begin
at Step 2.1.

2.9  Apply maximum scale input.

The Red and Green LEDs will alternately blink.

2.10  Set Input Field/Fact. switch (S1 switch 2) to the on position.

Red LED extinguishes and Green LED becomes solid. Your scaled values are now

saved and recalled if the Input Field/Fact. switch (S1 switch 2) is in the on position
when power is applied.

Red LED will blink slowly if signal is equal to or below minimum limit and blinks

rapidly if signal increases above maximum limit.

2.11  Input scaling complete. Go to Step 3.0 or Step 4.0.

3.1  Remove power.

3.2  For voltage output values, go to Step 3.4
For current output values, continue at Step 3.3

3.3  Set 20mA/1mA switch (S2) to desired full scale output.
(20mA - on; 1mA - off)

3.4  Set Output Field/Fact. switch (S1 switch 1) to the off position.

3.5  Set Output Range switches (S1 switches 3, 4, and 5) to the desired Output Range

(See Table 2). (4 to 20 mA range shown)

3.6  Connect external device to appropriate IAMA output terminals.

Terminal 6: + Voltage
Terminal 5: - Voltage
Terminal 4: + Current
Terminal 1: - Current

3.7  Apply power to the IAMA and allow a warm up period of five minutes. Output

set-up complete.

2.0  INPUT SCALING USING 

FIELD

CONFIGURATION

3.0 OUTPUT SET-UP USING 

FACTORY

CONFIGURATION

Step 2.3

Step 2.4

Step 2.6

Step 2.8

Step 3.5

Step 2.10

Step 3.3 & 3.4

Summary of Contents for IAMA Series

Page 1: ...the field if desired The modules environmental operating temperature range is 20 C to 65 C DIN rail mounting saves time and panel space The units are equipped with universal mounting feet for attachment to standard DIN style rails including top hat profile rail according to EN50022 35x7 5 and 35 x 15 and G profile rail according to EN50035 G32 SAFETY SUMMARY All safety related regulations local co...

Page 2: ...which restores the respective setting The Factory and Field E2PROM locations contain the same calibration values when the IAMA is received from the factory Therefore until the IAMA is field scaled factory and field modes perform identically See SCALING PROCEDURE for detailed instructions on field programming the IAMA The units can be scaled to any minimum scale and full scale values within the ext...

Page 3: ...ive earth b Connect the shield to earth ground at both ends of the cable usually when the noise source frequency is above 1 MHz c Connect the shield to common of the unit and leave the other end of the shield unconnected and insulated from earth ground 2 Never run Signal or Control cables in the same conduit or raceway with AC power lines conductors feeding motors solenoids SCR controls and heater...

Page 4: ...t 100 VDC Terminal 10 max signal input 100 mA Terminal 12 signal common 1 3 Set Input Range switches S1 switches 6 through 10 to the desired Input Range See Table 3 0 to 10 VDC range shown 1 4 Set Input Field Fact switch S1 switch 2 to the off position 1 5 Apply power to the IAMA Solid illumination of Green LED if signal is within the minimum and maximum limits of the selected input range Slow bli...

Page 5: ...the Red LED blinks slowly and the Green LED turns off Removing power aborts scaling begin at Step 2 1 2 9 Apply maximum scale input The Red and Green LEDs will alternately blink 2 10 Set Input Field Fact switch S1 switch 2 to the on position Red LED extinguishes and Green LED becomes solid Your scaled values are now saved and recalled if the Input Field Fact switch S1 switch 2 is in the on positio...

Page 6: ...max signal input 10 VDC Terminal 9 max signal input 100 VDC Terminal 10 max signal input 100 mA Terminal 12 signal common 4 9 Apply power to the IAMA and allow a warm up period of five minutes 4 10 Set Output Field Fact switch S1 switch 1 to the on position The Red and Green LEDs will alternately blink If Red LED blinks slowly increase signal until Red and Green LEDs alternately blink 4 11 Adjust ...

Page 7: ... calibration is to be completed return S1 1 and S1 2 to the down position and remove power from the IAMA Apply power and check for accurate operation of the newly calibrated range or ranges OUTPUT RECALIBRATION 1 Complete 1 through 5 of the input recalibration procedure for at least one range 2 For current output set 20 mA 1 mA switch S2 to desired full scale output 20 mA on 1 mA off 3 Set Output ...

Page 8: ...elies on no other warranties or affirmations APPLICATION Cost efficiency measurements of a printing company included the reduction of bulk stock of the various inks used in their printing processes The company currently had various ink flow and level devices with different current and voltage outputs and wanted to record these measurements into a control room PC Several IAMA Universal Signal Condi...

Reviews: