background image

-2-

Bulletin No. G12-H

Revised  2019-08-30

Drawing No. LP0910

 

MOUNTING INSTRUCTIONS

PANEL CUT-OUT

For  hazardous  location  installation  the  following  shall  be  taken  into

consideration:

-   When  used  in  a  Zone  22  environment,  the  device  shall  be  panel

mounted  in  at  least  Zone  22  IECEx/ATEX-Certified  tool  accessible
enclosure with a minimum ingress protection rating of at least IP64
as defined in IEC/EN 60529.

-   When  used  in  a  Zone  2  environment,  the  device  shall  be  panel

mounted  in  at  least  Zone  2  IECEx/ATEX-Certified  tool  accessible
enclosure with a minimum ingress protection rating of at least IP54
as defined in IEC/EN 60529.

-  

This  device  is  open-type  and  must  be  mounted  in  a  su

tight end-enclosure in accordance with articles 500 and 502 of the

NEC and positioned so only the face of the display is exposed.

-  Must be wired using Division 2 wiring methods as specified in article

501-4(b),  502-4(b),  and  503-3(b)  of  the  National  Electric  Code,
NFPA 70 for installation within the United States, or as specified in
section  19-152  of  Canadian  Electrical  Code  for  installation  in
Canada.

CONNECTING TO EARTH GROUND

Each operator panel has a chassis ground terminal on the back of the

unit.  Your  unit  should  be  connected  to  earth  ground.  Steps  should  be
taken  beyond  connecting  to  earth  ground  to  eliminate  the  buildup  of
electrostatic charges.

The  chassis  ground  is  not  connected  to  signal  common  of  the  unit.

Maintaining  isolation  between  earth  ground  and  signal  common  is  not
required to operate your unit. But, other equipment connected to this unit
may  require  isolation  between  signal  common  and  earth  ground. 

To

maintain isolation between signal common and earth ground care must
be taken when connections are made to the unit.

 For example, a power

supply with isolation between its signal common and earth ground must
be used. Also, plugging in a USB cable may connect signal common and
earth ground.

1

1

 USB’s shield may be connected to earth ground at the host. USB’s

shield in turn may also be connected to signal common.

2.95 (75)

1.48 (37.5)

1.08

(27.4)

2.95

(75)

VESA MOUNT (MIS-D 75) DIMENSIONS

11.458 (291.0)

7.561

(192.0)

4X R.10 (2.5)

MAX.

All tolerances ±.059" (±1.5 mm)

OPERATOR INTERFACE INSTALLATION

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range: -20 to 60 °C, or lowest range among

equipment used in your Graphite system. Consult the user manual
or 

www.redlion.net/OpTemp

 for further details.

Storage Temperature Range: -20 to 70 °C
Vibration to IEC 68-2-6: Operational 5-500 Hz, 4 g
Shock to IEC 68-2-27: Operational 40 g (10 g, modules w/relays)
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
Installation Category II, Pollution Degree 2 as defined in IEC/EN 60664-1.

CERTIFICATIONS AND COMPLIANCES

:

CE Approved

EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant

ATEX Approved

   II 3 G Ex ic nA IIC T4 Gc
   II 3 D Ex tc IIIC T135°C Dc
DEMKO 14 ATEX 1387X

EN 60079-0, -11, -15, -31

IECEx Approved

Ex ic nA IIC T4 Gc
Ex tc IIIC T135°C Dc
IECEx UL 15.0035X

IEC 60079-0, -11, -15, -31

UL Listed: File #E302106
UL Hazardous: File #E317425
Type 4X Indoor / IP66 Enclosure rating (Face only) for G12Cxxxx models
Type 4X Outdoor Enclosure rating (Face only) for G12Sxxxx
IP20 Enclosure rating (Rear of unit)

ABS Type Approval for Shipboard Applications

CONNECTIONS

: High compression cage-clamp terminal block

Wire Strip Length: 0.3" (7.5 mm)
Wire Gauge Capacity: One 14 AWG (1.63 mm) solid, 

two 18 AWG (1.02 mm) or four 20 AWG (0.81 mm)

CONSTRUCTION

: Cast aluminum enclosure with NEMA 4X/IP66 rating

when correctly fitted with the gasket provided. These devices have
only been evaluated for low risk of mechanical impact.

WEIGHT

: 5.06 lb. (2.29 Kg)

FOOT MAY BE REMOVED
FOR THICKER PANEL
INSTALLATIONS

This  operator  interface  is  primarily  designed  for

through-panel  mounting.  Four  VESA  mount  tapped
screw-holes (M4 x 0.7, 5 mm deep) are present on the
rear  of  the  panels  to  allow  for  stand  or  wall  mounting.
Care should be taken to remove any loose material from
the mounting cut-out to prevent that material from falling
into the operator interface during installation. A gasket is
provided  to  enable  sealing  to  NEMA  4X/IP66
specification. To maintain the IP66 rating of the panel, an
equivalently  IP  rated  enclosure  should  be  used.  Install
the  fifteen  mounting  clips  provided  and  tighten  to  6.0
pound-force inch [96 ounce-force inch] (0.68 N m) evenly
for uniform gasket compression. 

Provisions  should  be  made  to  prohibit  the  product

from  being  exposed  to  UV  radiation  while  in  use.  Care
should  be  taken  not  to  rub  or  buff  the  touchscreen
surface  in  a  way  that  might  cause  the  accumulation  of

static charges.