MOUNTING INSTRUCTIONS

This operator interface is designed for through-panel mounting. A panel cut-

out diagram and a template are provided. Care should be taken to remove any 

loose material from the mounting cut-out to prevent that material from falling 

into the operator interface during installation. A gasket is provided to enable 

sealing to NEMA 4X/IP66 specification. Install the 14 kep nuts provided and 

tighten evenly for uniform gasket compression. 

Note: Tightening the kep nuts beyond a maximum of 17 inch-pounds (1.92 

N-m) may cause damage to the front panel.

CONNECTING TO EARTH GROUND

Each G310 has a chassis ground terminal on the back of the unit. Your unit 

should be connected to earth ground (protective earth).

The chassis ground is not connected to signal common of the unit. 

Maintaining isolation between earth ground and signal common is not required 

to operate your unit. But, other equipment connected to this unit may require 

isolation between signal common and earth ground. 

To maintain isolation 

between signal common and earth ground care must be taken when connections 

are made to the unit.

 For example, a power supply with isolation between its 

signal common and earth ground must be used. Also, plugging in a USB cable 

may connect signal common and earth ground.

1

1. USB’s shield may be connected to earth ground at the host. USB’s shield 

in turn may also be connected to signal common.

POWER SUPPLY REQUIREMENTS

The units require a 24 VDC power supply rated at 30 W. Your unit may draw 

considerably less than the rated power depending upon the options being used. 

As additional features are used your unit will draw increasing amounts of power. 

Items that could cause increases in current are additional communications, 

optional communications card, CompactFlash card, and other features 

programmed through Crimson.

In any case, it is very important that the power supply is mounted correctly if 

the unit is to operate reliably. Please take care to observe the following points:

–  The power supply must be mounted close to the unit, with usually not 

more than 6 feet (1.8 m) of cable between the supply and the operator 

interface. Ideally, the shortest length possible should be used.

–  The wire used to connect the operator interface’s power supply should 

be at least 22-gage wire. If a longer cable run is used, a heavier gage 

wire should be used. The routing of the cable should be kept away from 

large contactors, inverters, and other devices which may generate 

significant electrical noise.

–  A power supply with an NEC Class 2 or Limited Power Source (LPS) 

and SELV rating is to be used. This type of power supply provides 

isolation to accessible circuits from hazardous voltage levels generated 

by a mains power supply due to single faults. SELV is an acronym for 

“safety extra-low voltage.” Safety extra-low voltage circuits shall 

exhibit voltages safe to touch both under normal operating conditions 

and after a single fault, such as a breakdown of a layer of basic 

insulation or after the failure of a single component has occurred.

8.925

(226.7)

2.975

(75.6)

12.25 (311.2)

6.125 (155.6)

11.725 (297.8)

8.40

(213.4)

14X 

.188 (

4.8)

All tolerances ±0.010" (±0.25 mm).

ALL NONINCENDIVE CIRCUITS MUST BE WIRED USING 

DIVISION 2 WIRING METHODS AS SPECIFIED IN THE NATIONAL 

ELECTRICAL CODE, NFPA 70 FOR INSTALLATION WITHIN THE 

UNITED STATES, OR AS SPECIFIED IN THE CANADIAN 

ELECTRICAL CODE FOR INSTALLATION IN CANADA.

The protective conductor terminal is bonded to conductive 

parts of the equipment for safety purposes and must be 

connected to an external protective earthing system.

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT 

EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA 

IS KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS.

i

nStalling

 a

n

 o

ption

 c

ard

Each option card comes with a cable for communications and three 

screws for attaching the option card to the G3’s main board.

To install the option card, remove all power and I/O communications 

cables from the unit and remove the rear cover.  Connect the cable from the 

option card to the connector on the main board. Be sure both ends of the 

cable are firmly seated into their appropriate connector housings. Use the 

three screws provided to mount the option card to the main board as shown 

in Figure 1.

Carefully replace the rear cover by reversing the instructions for 

removing the rear cover.

TYPICAL EXPANSION CARD INSTALLATION

Figure 1

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT

EQUIPMENT UNLESS POWER HAS BEEN DISCONNECTED

AND THE AREA IS KNOWN TO BE NON-HAZARDOUS.

Summary of Contents for G310C2

Page 1: ...sh Card 6 G3CFxxxx G3RS RS 232 485 Optional Communication Card G3RS0000 G3CN CANopen Optional Communication Card G3CN0000 G3DN DeviceNet Optional Communication Card G3DN0000 G3GSM GSM GPRS Modem Optio...

Page 2: ...rage Humidity 80 maximum relative humidity non condensing from 0 to 50 C Vibration according to IEC 68 2 6 Operational 5 to 150 Hz in X Y Z direction for 1 5 hours 2 g Shock according to IEC 68 2 27 O...

Page 3: ...face Ideally the shortest length possible should be used The wire used to connect the operator interface s power supply should be at least 22 gage wire If a longer cable run is used a heavier gage wir...

Page 4: ...in the folder C Program Files Red Lion Controls Crimson 2 0 Device after Crimson is installed This may have already been accomplished if your G310 was configured using the USB port Once the driver is...

Page 5: ...1 3 2 4 6 7 ON ON CBLPROG0 ICM5 CONNECTING A G310 OPERATOR INTERFACE TO AN ICM5 Application Dependent ICM5 DIP Switch Settings Examples of RS485 2 Wire Connections G3 to Red Lion RJ11 CBLRLC00 DLC IA...

Page 6: ...his operator interface utilizes a resistive analog touchscreen for user input The unit will only produce an audible tone beep when a touch on an active touchscreen cell in sensed The touchscreen is fu...

Page 7: ...r in a manner whereby it may be damaged and its contents come into contact with human skin The battery used by the G310 is a lithium type CR2025 BATTERY INVERTER TOP BOTTOM G310C2 WARNING EXPLOSION HA...

Page 8: ...format CompactFlash Insert Face Up C o m p a c tF l a s h T o p S i d e INDOOR VERSUS OUTDOOR The G310C2x0 and the G310R2x0 use an overlay with a textured finish and keys that are embossed This overla...

Reviews: