POWER SUPPLY REQUIREMENTS

The DA50A Gateway requires a 12-24 VDC power supply. Your 

unit may draw considerably less than the maximum rated power 

depending upon the configuration and features being used. Your 

unit will draw increased power with a sled installed. Items that 

could cause increases in current are microSD card, communications 

sleds, and other features programmed through software.

To ensure you do not exceed the capacity of your DA50A 

Gateway host power supply, calculate the total power consumption 

required for all planned accessories.

It is very important that the power supply meets the following 

requirements and is mounted correctly if the unit is to operate 

reliably. Please take care to observe the following points:

 

– The power supply must be mounted close to the unit, with 

usually not more than 6 feet (1.8 m) of cable between the 

supply and the Gateway. Ideally, the shortest length possible 

should be used.

 

– The wire used to connect the Gateway power supply should 

be at least 22-gauge wire. If a longer cable run is used, a 

heavier gauge wire should be used. The routing of the cable 

should be kept away from large capacitors, inverters, and 

other devices which may generate significant electrical noise.

 

– Use a power supply with an NEC Class 2 or Limited Power 

Source (LPS) and SELV (safety extra-low voltage) rating. This 

type of power supply provides isolation to accessible circuits 

from hazardous voltage levels generated by a mains power 

supply due to single faults. Safety extra-low voltage circuits 

shall exhibit voltages safe to touch both under normal 

operating conditions and after a single fault, such as a 

breakdown of a layer of basic insulation or after the failure of 

a single component has occurred.

 

– Peak efficiency (DA50A) occurs at the low side of the voltage 

range (approx. 12 V), recommended for high temperature 

applications.

Visit www.redlion.net for a complete list of our NEC Class 2 

power supplies.

WIRING

All power, input and output (I/O) wiring must be in accordance 

with Class I, Division 2 wiring methods and in accordance with 

the authority having jurisdiction.

CONNECTING TO EARTH GROUND

Each DA50A has a chassis ground terminal on the top of the 

unit. Your unit should be connected to earth ground. Steps should 

be taken beyond connecting to earth ground to eliminate the 

buildup of electrostatic charges.

The chassis ground is not connected to signal common of the 

unit. Maintaining isolation between earth ground and signal 

common is not required to operate your unit. But, other equipment 

connected to this unit may require isolation between signal 

common and earth ground. To maintain isolation between signal 

common and earth ground care must be taken when connections 

are made to the unit. For example, a power supply with isolation 

between its signal common and earth ground must be used. Also, 

plugging in a USB cable may connect signal common and earth 

ground.

1

1

 USB’s shield may be connected to earth ground at the host. 

USB’s shield in turn may also be connected to signal common.

D

A50A PORT PINOUTS

FACTORY RESET BUTTON

The factory reset button located in the lower left area of the 

front of the unit can be used to clear the configuration. Hold in 

the reset button at power up until the status ring LED turns bright 

white. Click the button to cycle through colors on the status ring 

LED. If left at white, the unit will boot its existing configuration, 

and if left at red it will clear the units memory. Once the memory 

is cleared, the user will need to use the default password printed 

on the unit to access the configuration.

CONFIGURING A DA50A

The DA50A can be configured using Crimson

®

 3.2 software. 

Crimson is available as a no charge download from Red Lion’s 

website. Crimson updates for new features and drivers are posted 

on the website as they become available. By configuring the 

DA50A using the latest Crimson version, you are assured that 

your unit has the most up to date feature set. Crimson software 

can configure the DA50A through the Serial programming port, 

USB device port, Ethernet ports or microSD card.

The microSD card can be used to program a DA50A by placing 

an image file on the microSD card. The card is then inserted into 

the target DA50A and powered. Refer to the Crimson 3.2 User 

Manual for more information on the proper names and locations 

of this file.

CAUTION: Only UL listed wiring with temperature 

ratings greater than 90 °C permitted for Class I, Division 

2, Zone 2 and ATEX/IECex installations.
ATTENTION: Seul le câblage homologué UL avec des 

températures nominales supérieures à 90°C est autorisé 

pour les installations de classe I, Division 2 , zone 2 et 

ATEX/IECex.

CONNECTOR

POR

T 1

ETHERNET PORTS

MICRO SD CARD

USB DEVICE

POR

T 1

SERIAL PORTS

RESET BUTTON

POR

T 2

POR
T 2

COMM

COMM

CTS  (PIN 1)

RTS  (PIN 6)

Tx

Rx

COMM

TxA  (PIN 8)

TxB  (PIN 1)

RxA

RxB

TxB

TxEN

TxA

MICRO

SD CARD

LED

3

5 4

1

2

ANALOG/DIGITAL

 INPUT

DIGITAL OUTPUT

+ -

POWER INPUT

Summary of Contents for FlexEdge DA50A

Page 1: ...led Sled Holder Installation Guide SAFETY SUMMARY All safety related regulations local codes as well as instructions that appear in this document or on equipment must be observed to ensure personal sa...

Page 2: ...inimum VDC 0 4 VDC open circuit 6 DIGITAL INPUT DIN Configuration Unisolated level detection reference to ground Active level 2 5 VDC to 30 VDC Inactive level 0 VDC to 1 3 VDC Absolute Minimum VDC 0 3...

Page 3: ...place a diode across the inductive load Most Red Lion products with solid state outputs have internal zener diode protection However external diode protection at the load is always a good design prac...

Page 4: ...harges The chassis ground is not connected to signal common of the unit Maintaining isolation between earth ground and signal common is not required to operate your unit But other equipment connected...

Page 5: ...for either master or slave protocols The serial port has a pair of LEDs to indicate transmit and receive activity The pinout is shown to the right RS485 422 COMMS PORT The RS485 port of the DA50A can...

Page 6: ...www redlion net Inside US 1 877 432 9908 Outside US 1 717 767 6511 Red Lion Controls Inc 20 Willow Springs Circle York PA 17406 microSD Card Orientation Note Removal of the microSD while power is app...

Page 7: ...Mixed Serial Protocol Gateway DA50A 0BNN00 00030 Group 3 FlexEdge 1 Sled Mixed Serial Adv IIoT Gateway DA50A 0BNN00 00040 Group 4 FlexEdge 1 Sled Mixed Serial Adv Automation Controller Accessories PAR...

Page 8: ...SE Customer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or federal law b The Company shall not be liab...

Reviews: