INSTALLATION ENVIRONMENT

The unit should be installed in a location that does not exceed the maximum

operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.

The bezel should be cleaned only with a soft cloth and neutral soap product.

Do NOT use solvents. Continuous exposure to direct sunlight may accelerate
the aging process of the bezel.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the

keypad of the unit.

Installation

The CUB4 series of products meet NEMA 4X/IP65 requirements for indoor

use, when properly installed. The units are intended to be mounted into an
enclosed panel. The viewing window and reset button are factory sealed for a
washdown environment. A sponge rubber gasket and mounting clip are
provided for sealing the unit in the panel cut-out.

The following procedure assures proper installation:

1. Cut panel opening to specified dimensions. Remove burrs and clean around

panel opening.

2. Carefully remove the center section of the panel gasket and discard. 

Slide gasket over rear of the unit to the back of the bezel.

3. Assemble nut fastener first and then mounting screw onto both sides of

mounting clip. Tip of screw should not project from hole in mounting clip.

4. Install CUB4 unit through the panel cut-out until front bezel flange contacts

the panel-mounted gasket.

5. Slide the mounting clip over the rear of the unit until the mounting clip is

against the back of the panel. The mounting clip has latching features which
engage into mating features on the CUB4 housing.

Note: It is necessary to hold the unit in place when sliding mounting clip into

position.

6. Alternately tighten each screw to ensure uniform gasket pressure. Visually

inspect the front panel gasket. The gasket should be compressed about 75 to
80% of its original thickness. (Recommended torque is 28 to 36 in-oz.) If
not, gradually turn mounting screws to further compress gasket.

7. If gasket is not adequately compressed, and mounting screws can no longer

be turned, loosen mounting screws and check that mounting clip is latched
as close as possible to panel.
Repeat procedure for tightening mounting screws.

CUB4L8 & CUB4L8W: 15 msec min. pulse width 

(active low)

from 3.0 V

bipolar output or an open collector transistor or a switch contact to
common.

5. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature

: 0 to 60°C (above 50°C, derate backlight operating

voltage to 26 VDC max.).

Storage Temperature

: -30 to 85°C

Operating and Storage Humidity

: 85% max. (non-condensing) from 0°C to

50°C.

Vibration According to IEC 68-2-6:

5 to 500 Hz, in X, Y, Z direction for 1.5

hours, 5g’s.

Shock According to IEC 68-2-27:

Operational 30 g, 11 msec in 3 directions.

Altitude

: Up to 2000 meters

6. 

CERTIFICATIONS AND COMPLIANCES

:

SAFETY

UL Recognized Component, File # E179259, UL 61010-1, CSA C22.2 No.

61010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc. 

Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Certificate # US/9257/UL,

CB Scheme Test Report # E179259-V01-S02

Issued by Underwriters Laboratories, Inc.

IEC 61010-1, EN 61010-1: Safety requirements for electrical

equipment for measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529

ELECTROMAGNETIC COMPATIBILITY

Refer to the EMC Installation Guidelines section of this bulletin for

additional information.

7. 

CONSTRUCTION

:

This unit is rated for NEMA 4X/IP65 indoor use. Installation Category I,
Pollution Degree 2

8. 

WEIGHT

: 3 oz. 

(85 grams)

EMC INSTALLATION GUIDELINES

Although Red Lion Controls Products are designed with a high degree of

immunity to Electromagnetic Interference (EMI), proper installation and wiring
methods must be followed to ensure compatibility in each application. The type
of the electrical noise, source or coupling method into a unit may be different
for various installations. Cable length, routing, and shield termination are very
important and can mean the difference between a successful or troublesome
installation. Listed are some EMI guidelines for a successful installation in an
industrial environment.
1. Use shielded (screened) cables for all Signal and Control inputs. The shield

(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth

ground (protective earth).

b. Connect the shield to earth ground at both ends of the cable, usually when

the noise source frequency is above 1 MHz.

c. Connect the shield to common of the unit and leave the other end of the

shield unconnected and insulated from earth ground.

2. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.

3. Signal or Control cables within an enclosure should be routed as far away as

possible from contactors, control relays, transformers, and other noisy
components.

4. In extremely high EMI environments, the use of external EMI suppression

devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional protection.
Install line filters on the power input cable to the unit to suppress power line
interference. Install them near the power entry point of the enclosure. The
following EMI suppression devices (or equivalent) are recommended:

Ferrite Suppression Cores for signal and control cables

:

Fair-Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035-1330A
Steward #28B2029-0A0

Line Filters for input power cables

:

Schaffner # FN610-1/07 (RLC #LFIL0000)
Schaffner # FN670-1.8/07
Corcom #1VR3

Note:

Reference manufacturer’s instructions when installing a line filter.

5. Long cable runs are more susceptible to EMI pickup than short cable runs.

Therefore, keep cable runs as short as possible.

Immunity to EN 50082-2

Electrostatic discharge

EN 61000-4-2

Level 2; 4 Kv contact
Level 3; 8 Kv air

Electromagnetic RF fields

EN 61000-4-3

Level 3; 10 V/m
80 MHz - 1 GHz

Fast transients (burst)

EN 61000-4-4

Level 4; 2 Kv I/O
Level 3; 2 Kv power

RF conducted interference

EN 61000-4-6

Level 3; 10 V/rms 

Power frequency magnetic fields

EN 61000-4-8

Level 4; 30 A/m

150 KHz - 80 MHz

Simulation of cordless telephone

ENV 50204

Level 3; 10 V/m
900 MHz ± 5 MHz
200 Hz, 50% duty cycle

Emissions to EN 50081-2

RF interference

EN 55011

Class B

Summary of Contents for CUB4L

Page 1: ...tery life is dependent upon usage Count and reset contacts that remain closed for long periods of time will reduce battery life 3 BACKLIGHT POWER REQUIREMENTS 9 to 28 VDC 35 mA typical 50 mA max Above 26 VDC derate operating temperature to 50 C Must use the MLPS or a Class 2 or SELV rated power supply 4 INPUTS All Inputs VIL low 0 5 V max Low Speed Input CUB4L CUB4L8 30 Hz from switch contact or o...

Page 2: ... rating Face only IEC 529 ELECTROMAGNETIC COMPATIBILITY Refer to the EMC Installation Guidelines section of this bulletin for additional information 7 CONSTRUCTION This unit is rated for NEMA 4X IP65 indoor use Installation Category I Pollution Degree 2 8 WEIGHT 3 oz 85 grams EMC INSTALLATION GUIDELINES Although Red Lion Controls Products are designed with a high degree of immunity to Electromagne...

Page 3: ...ew until the wire is clamped tightly Each terminal can accept up to two 14 AWG wires Note The Reflective CUB4 will NOT have a screw terminal installed at the V terminal since it is NOT required for operation and is not internally connected Refer to the Ordering Information for the part number of a reflective model that will accommodate the MLPS Backlight Wiring Optional backlight versions of the C...

Page 4: ...lighting and a sensor WARNING When connecting the wiring for a backlit CUB4L8W measuring an AC input voltage the neutral of the single phase AC signal is connected to Terminal 1 COM and line hot is connected to Terminal 5 LS The DC supply for the backlighting is connected as shown in the drawing Three phase AC applications require an isolation transformer The H S CNT Input allows the CUB Counter t...

Reviews: