red lion APLPT Manual Download Page 4

For Sales and Support, Contact Walker EMD • Toll-free: (800) 876-4444 • Tel: (203) 426-7700 • Fax: (203) 426-7800 • www.walkeremd.com

4

EMC INSTALLATION GUIDELINES

Although this unit is designed with a high degree of immunity to

ElectroMagnetic Interference (EMI), proper installation and wiring methods
must be followed to ensure compatibility in each application. The type of the
electrical noise, source or coupling method into the unit may be different for
various installations. In extremely high EMI environments, additional measures
may be needed. Cable length, routing and shield termination are very important
and can mean the difference between a successful installation or a troublesome
installation. Listed below are some EMC guidelines for successful installation
in an industrial environment.

1. The unit should be mounted in a metal enclosure, that is properly connected

to protective earth.
a. If the bezel is exposed to high Electro-Static Discharge (ESD) levels, above

4 Kv, it should be connected to protective earth. This can be done by making
sure the metal bezel makes proper contact to the panel cut-out or connecting
the bezel screw with a spade terminal and wire to protective earth.

2. Use shielded 

(screened)

cables for all Signal and Control inputs. The shield

(screen)

pigtail connection should be made as short as possible. The

connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth

ground 

(protective earth)

.

b. Connect the shield to earth ground at both ends of the cable, usually when

the noise source frequency is above 1 MHz.

c. Connect the shield to common of the unit and leave the other end of the

shield unconnected and insulated from earth ground.

3. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.

4. Signal or Control cables within an enclosure should be routed as far away as

possible from contactors, control relays, transformers, and other noisy
components.

5. In extremely high EMI environments, the use of external EMI suppression

devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional protection.
Install line filters on the power input cable to the unit to suppress power line
interference. Install them near the power entry point of the enclosure. The
following EMI suppression devices 

(or equivalent)

are recommended:

Ferrite Suppression Cores for signal and control cables:

Fair-Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035-1330A
Steward #28B2029-0A0

Line Filters for input power cables:

Schaffner # FN610-1/07 (RLC #LFIL0000)
Schaffner # FN670-1.8/07
Corcom #1VB3
Corcom #1VR3

Note:

Reference manufacturer’s instructions when installing a line filter.

6. Long cable runs are more susceptible to EMI pickup than short cable runs.

Therefore, keep cable runs as short as possible.

WIRING CONNECTIONS

As depicted in the drawing showing the rear view of the Apollo Process Time

Indicator, there is a terminal block where all wiring connections are made. All
conductors should meet voltage and current ratings for each terminal. Also
cabling should conform to appropriate standards of good installation, local
codes and regulations. It is recommended that power supplied to the unit (AC
or DC) be protected by a fuse or circuit breaker. Remove the block for easy
access to the terminal screws. To remove the block, pull from the back of the
block until it slides clear of the terminal block shroud.

Enclosed with the PBLPT module is an adhesive backed label(s) showing the

terminal block pin-out. This label is for wiring reference only, do not use for
specifications. This label should be applied to the appropriate location by the user.

CAUTION: The terminal block should NOT be removed with power

applied to the unit. The module should not be removed from the
LDD with power applied to the LDD or the module.

INPUT & POWER CONNECTIONS

Primary AC power is connected to Terminals 1 and 2 

(marked A.C. Power,

located on the left-hand side of the block)

. For best results, the AC power should

be relatively “clean” and within the specified ±10% variation limit. Drawing
power from heavily loaded circuits or from circuits that also power loads that
cycle on and off should be avoided.

Terminal 3 is the 

“DC” (+12 V)

terminal. This terminal is for sensor supply

and can provide up to 100 mA of current. An ex11 V to +14 VDC can
also be applied to this terminal to power the unit in the absence of A.C. power.
Terminal 4 is the 

“COMM.” (common)

terminal, which is the common line to

which the sensor and other input commons are connected. Terminal 5 is the

“SIG. IN” (signal in)

terminal. When the signal at this terminal goes low, a

count will be registered in the unit. 

(See “Input Ratings” under

“Specifications” section.)

REAR PANEL DIP SWITCHES

As can be seen from the rear of the unit, there is a row of 14 DIP switches

located beside the input and power terminal block. All of these DIP switches are
Display Multiplier Increment Total 

(DMIT)

switches. When the switch is 

“ON”

,

it will multiply the measured time between input pulses by the display multiplier
it represents.

Summary of Contents for APLPT

Page 1: ...l DIP switch The units can accommodate magnetic pickups logic sensors and NPN open collector sensors as well as switch contact closure sensors These units have a self test feature which checks all the...

Page 2: ...n current sink or source sensor by connecting the appropriate terminals in common S3 on the APLPT PBLPT should be turned OFF since pull up or pull down resistors are already present in the counter The...

Page 3: ...PT4 PBLPT4 the proper DIP switches must be selected before the unit is powered up To change a decimal point location the unit must be powered down the DIP switches changed then powered up The decimal...

Page 4: ...ction Install line filters on the power input cable to the unit to suppress power line interference Install them near the power entry point of the enclosure The following EMI suppression devices or eq...

Page 5: ...stort and not provide a water tight seal Recommended minimum panel thickness is 1 8 After the panel cut out has been completed and deburred carefully slide the panel gasket over the rear of the unit t...

Page 6: ...basic formula applies to all units However for the APLPT5 PBLPT5 the D R must be converted to a base unit of measurement DMIT D R x P P S DMIT Display Multiplier Increment Total DR Desired Reading In...

Page 7: ...talog or contact your local RLC distributor APLPT DESCRIPTION MODEL NO PART NUMBERS FOR AVAILABLE SUPPLY VOLTAGES ORDERING INFORMATION PBLPT500 PBLPT400 115 230 VAC Apollo 5 Digit Process Time Module...

Page 8: ...or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be...

Reviews: