SPECIFICATIONS

1. 

DISPLAY:

4 or 5-digit, 0.56" (14.2 mm) high LED, display. (APLPT)

2. 

POWER REQUIREMENTS:

APLPT

AC Operation

: Available in two voltage ranges. 115 VAC (±10%) or 230

VAC (±10%), 50/60 Hz, 14 VA.

DC Operation

: 11 to 14 VDC @ 0.6A max.

PBLPT

AC Operation

: Switch selected via the LDD power supply board, 115/230

(±10%), 50/60 Hz, 10 VA for 4-digit, 15 VA for 6-digit 

(including LDD)

.

3. 

SENSOR POWER:

+12 VDC, ±25% @ 100 mA max.

4. 

OPERATING FREQUENCY RANGE:

0.05 pulse/sec. to 10,000 pulse/sec.

Note: When the value to be displayed exceeds the full scale display capacity,

all dashes are displayed. If input rate is too low, the unit will display a zero.

5. 

ACCURACY AND REPEATABILITY:

0.02%

6. 

DISPLAY MULTIPLIER INCREMENT TOTAL, SELECTION RANGE:

From 1 to 16,383.

7. 

SCALE MULTIPLIER VALUES:

1, 10, 100, 1000.

8.

DISPLAY UPDATE TIME:

The display will update every 0.65 sec. plus one

input pulse when the input pulse rate is 1.54 PPS or higher. When the input
pulse rate is below 1.54 PPS, the display will update on every input pulse.

Note: When the input pulse rate is 3 PPS or lower, the unit will utilize, if

selected, a technique known as a “moving window average”. (This
continually averages the last eight input pulses.)

9. 

MAXIMUM INPUT VOLTAGE AND CURRENT: 

When the “SIG. IN”

(Terminal 5) is driven from external signal voltages, maximum allowable
voltage swing is ±50 V peak. Input voltage can be dropped by an external
series resistance that limits input current to ±5 mA. (These ratings are for 
S3 “OFF”.)

10. 

INPUT IMPEDANCE:

When S1 and S3 “OFF”, the resistive input

impedance exceeds 1 megohm as long as the “SIG. IN” (Terminal 5) input
voltage is between zero and +12 VDC. Beyond these levels, the high and low
clamping diode will start to conduct, thus decreasing the input impedance.
With S3 “ON” the maximum input voltage to Terminal 5 must be limited to
28 VDC.

11. 

PARALLELING WITH APOLLO TOTALIZER INPUTS (RLC

standard count input):

Apollo Process Time Indicators may be parallel

connected with counters having the RLC standard count input circuitry. These
can operate from a common current sink or source sensor by connecting the
appropriate terminals in common. S3 on the APLPT/PBLPT should be turned
“OFF” since pull-up or pull-down resistors are already present in the counter.
The unit will not add appreciable sensor load with this arrangement.

Note: The APLPT/PBLPT cannot be operated in parallel with standard input

counters when 2-wire proximity sensors are used.

12. 

INPUT AND POWER CONNECTIONS:

There is a plug-in, compression-type, barrier strip located at the rear of the
unit. This strip can be removed from the rear of the unit for ease of wiring.
After wiring is complete, the connector can be plugged back onto the unit.

13. 

CERTIFICATIONS AND COMPLIANCES:

SAFETY

IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment for

measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529
Type 4 Enclosure rating (Face only), UL50

ELECTROMAGNETIC COMPATIBILITY

Notes for APLPT only:

1. Metal bezel of unit connected to earth ground (protective earth) at the

mounting panel.

2. EMI filter placed on the DC power supply, when DC powered: Corcom

#1VB3 or Schaffner #FN610-1/07 (RLC #LFIL0000).

Refer to the EMC Installation Guidelines section of this bulletin for

additional information.

14. 

ENVIRONMENTAL CONDITIONS:

Operating Temperature Range

: 0 to 50°C

Storage Temperature Range

: -40 to 70°C

Operating and Storage Humidity

: 85% max. relative humidity (non-

condensing) from 0°C to 50°C.

Altitude

: Up to 2000 meters

15. 

CONSTRUCTION:

Die-cast metal front bezel with black, high impact

plastic insert. Front panel meets NEMA 4/IP65 requirements for indoor use
when properly installed. Installation Category II, Pollution Degree 2. (Panel
gasket and mounting clips included with unit.)

16. 

WEIGHT:

APLPT

: 1.5 lbs. (0.8 Kg)

PBLPT

: 0.4 lbs (0.18 Kg)

Power mains class A

Enclosure class A

EN 55011

RF interference

Emissions to EN 50081-2

Level 3; 10 V/m

ENV 50204

150 KHz - 80 MHz

Level 3; 10 V/rms 

EN 61000-4-6

RF conducted interference

Level 3; 2 Kv power

Level 4; 2 Kv I/O

2

EN 61000-4-4

Fast transients (burst)

80 MHz - 1 GHz

Level 3; 10 V/m 

EN 61000-4-3

Electromagnetic RF fields

Level 3; 8 Kv air

Level 2; 4 Kv contact

1

EN 61000-4-2

Electrostatic discharge

Level 4; 10 A/m

EN 61000-4-8

Power frequency magnetic fields

200 Hz, 50% duty cycle

Immunity to EN 50082-2

900 MHz ± 5 MHz

Simulation of cordless telephone

BLOCK DIAGRAM

Summary of Contents for APLPT

Page 1: ...l DIP switch The units can accommodate magnetic pickups logic sensors and NPN open collector sensors as well as switch contact closure sensors These units have a self test feature which checks all the...

Page 2: ...n current sink or source sensor by connecting the appropriate terminals in common S3 on the APLPT PBLPT should be turned OFF since pull up or pull down resistors are already present in the counter The...

Page 3: ...PT4 PBLPT4 the proper DIP switches must be selected before the unit is powered up To change a decimal point location the unit must be powered down the DIP switches changed then powered up The decimal...

Page 4: ...ction Install line filters on the power input cable to the unit to suppress power line interference Install them near the power entry point of the enclosure The following EMI suppression devices or eq...

Page 5: ...stort and not provide a water tight seal Recommended minimum panel thickness is 1 8 After the panel cut out has been completed and deburred carefully slide the panel gasket over the rear of the unit t...

Page 6: ...basic formula applies to all units However for the APLPT5 PBLPT5 the D R must be converted to a base unit of measurement DMIT D R x P P S DMIT Display Multiplier Increment Total DR Desired Reading In...

Page 7: ...talog or contact your local RLC distributor APLPT DESCRIPTION MODEL NO PART NUMBERS FOR AVAILABLE SUPPLY VOLTAGES ORDERING INFORMATION PBLPT500 PBLPT400 115 230 VAC Apollo 5 Digit Process Time Module...

Page 8: ...or products containing components manufactured by RLC and based upon personal injuries deaths property damage lost profits and other matters which Buyer its employees or sub contractors are or may be...

Reviews: