background image

RM-216 C.10 Easy Line Documentation  

RDN 10000029 

15 

13.05.2014 

9   Details on the equipment function 

Differential pressure controlled cleaning 

The cleaning is controlled by means of two 

p switch points which can be set independently of one 

another. It starts when the value 

p-MAX is reached. All connected solenoid valves are controlled using 

the preset values for the pulse time and the interval time, starting with the interval time. If the differential 

pressure reaches the value 

p-MIN, cleaning stops. To monitor the filter, a 

p alarm switch point (

alarm) can be set. 
Cleaning starts at the first valve. If cleaning is interrupted using the 

p controller or the start/stop input 

D1, D2, the controller sequence is continued with the next cleaning process. The cleaning then starts at 

the valve following the last valve activated. 
If the control is reactivated following a mains voltage failure, a restart is carried out.  

 

 

 

Input  E1, E2 “Down time cleaning”

 (terminals 10, 11)

 

If the control is working in DTC mode 1 or DTC mode 2 (Down-Time-Cleaning mode. See also section 

6.3), the control must be switched on and off via input E1, E2. The input should be operated in isolation. 

Ideally, the auxiliary contact of the fan contactor should be connected here. 

  Closing the contact on input E1, E2 switches on the control unit. 

  In DTC mode 1, opening the contact on input E1, E2 executes the down time cleaning cycles and then 

switches the device off. In DTC mode 2, the same function is only carried out if differential pressure 

exceeded the value 

p DTC max during the last operating period. 

  In DTC mode 3, the down-time cleaning cycles are activated if differential pressure exceeded the value 

p DTC max during the last operating period and then fell below the value 

p DTC min. 

 

 

 

Relay output S1, S2 to control extractor elements 

(terminals 8, 9) 

If automatic components for dust removal (extractor elements) are fitted, these need to be in operation 

during cleaning and during down time cleaning. Connect the cut-out for controlling these drive units to the 

isolated output S1, S2. 
 

 

 

“Alarm” relay output A1, A2, A3

 (terminals 5, 6, 7) 

As soon as the supply voltage is present on the RM-216 C, relay contact A1, A2 closes (terminals 5, 6) 

and contact A2, A3 opens (terminals 6, 7). In the following situations, relay contact A1, A2 opens and 

contact A2, A3 closes: 

  Supply voltage failure 

  Failure of a voltage internal to the equipment 

  Fault in a connected I/O module 

  Total number of valves is set incorrectly (parameter P06) 

  The 

p alarm switching point has been exceeded. 

Summary of Contents for EasyLine RM-216 C

Page 1: ...Operating and Installation Instructions Filter control system RM 216 C EasyLine ...

Page 2: ...ters 7 5 3 Parameter list 9 6 Operating modes 10 6 1 Test mode 10 6 2 p Mode differential pressure controlled cleaning 10 6 3 Down time cleaning modes 10 6 4 Cleaning via start stop input external p switch 12 7 Troubleshooting 13 8 Text messages on the display 14 9 Details on the equipment function 15 10 Glossary 16 11 Technical specifications 18 Regulations VDE 0160 EN 60 439 Part 500 EN 50178 20...

Page 3: ...ers may only be performed by authorized expert staff when disconnected and whilst observing the local safety and accident prevention regulations The RM 216 C may only be operated in the permitted operating area Switch off the mains supply before replacing the filter control or any components connected to it Otherwise the equipment may be damaged 2 Equipment specification The RM 216 C is used to co...

Page 4: ...ction A separate power supply unit is recommended for the operation of the filter controller with extra low voltage The unit can be operated with a supply voltage of 24 V DC if no expansion modules are connected and if the electric cables minimum cross section 0 75 mm to the solenoid valves are shorter than 10 meters long ...

Page 5: ...Use shielded cable for all bus lines The shielding must be connected unilaterally to the protective earthing PE Signal cables must not be laid parallel to power cables Tighten all cable glands in use so the cables are properly enclosed and water cannot penetrate Cable glands that are not in use must be closed or replaced by blind plugs ...

Page 6: ...connections Connecting differential pressure measurement cables Use hoses with 4 mm inner and 6 mm outer diameters Connect the connection marked with 3 lines black screw cap to the crude gas side and the other connection blue screw cap to the pure gas side of the filter ...

Page 7: ...on to call up all following parameters P01 P20 in sequence The parameters already displayed can be accessed by repeatedly pressing the button To change the value of a displayed parameter press the ENTER button for at least one second The program then changes from parameter selection mode to parameter setting mode Press the button to increase the parameter value displayed in increments Press the bu...

Page 8: ...RM 216 C 10 Easy Line Documentation RDN 10000029 8 13 05 2014 ...

Page 9: ...t 3 7 For manufacturer purposes only Off 0 0 7 P15 dP range p range 0 5000 Pa 0 1000 Pa to 0 5000 Pa 2 P16 Servic Run Hours Service operating hours P17 Ser Run Hours AL Service operating hours alarm 0 h 3 0 25000 h 3 P18 Ser Run Hou Code Service operating hours code 0 P19 DP Mode Differential pressure mode On On Off P20 Setting Lock Parameter setting lock On On Off 1 Number of all valves connected...

Page 10: ... the text display Test modes 3 7 For manufacturer purposes only Test mode 0 test mode off Test mode is switched off 6 2 p Mode differential pressure controlled cleaning There are two options for switching the differential pressure controlled cleaning on the RM 216 C on and off By setting the parameter P19 DP Mode to the value On or Off By pressing the ENTER button for around 3 seconds If different...

Page 11: ...act connected on input E1 and E2 If the fan is switched off the contact on E1 E2 must open DTC mode 2 The down time cleaning is only started via the contact connected to input E1 and E2 if the differential pressure has exceeded the value p DTC max during operation If the fan is switched off the contact on E1 E2 must open ...

Page 12: ... If the cleaning is controlled via an external p switch the isolated contact on the p switch must be connected to the start stop input D1 D2 terminals 12 13 The function of the RM 216 C is given in the following table If the setting is p mode OFF Contact input D1 D2 Cleaning open ON closed OFF If the setting is p mode ON Contact input D1 D2 Differential pressure p Cleaning open p p MAX ON closed p...

Page 13: ...m the valve controller DTC modes 1 2 Activate signal to input I1 I2 Cleaning ineffective Interval time too long Set parameter P04 Interval time to a lower value Pressure too low Set pressure to 6 8 bar min 5 bar Set parameter P04 Interval time to a higher value Valve faulty Check replace valves Pulse time too short Set parameter P03 Pulse time to a higher value Cycle often interrupted Check differ...

Page 14: ...ng point has been exceeded Cleaning On XXXX Pa alternating with DP Max Alarm XXXX Pa Controller is enabled through inputs I1 and I2 and the Max p switching point has not yet been reached with inputs D1 and D2 bridged Extern Clean ON XXXX Pa Controller is enabled through inputs I1 and I2 and the Max p switching point has been exceeded with inputs D1 and D2 bridged Extern Clean OFF XXXX Pa p mode sw...

Page 15: ...ation Ideally the auxiliary contact of the fan contactor should be connected here Closing the contact on input E1 E2 switches on the control unit In DTC mode 1 opening the contact on input E1 E2 executes the down time cleaning cycles and then switches the device off In DTC mode 2 the same function is only carried out if differential pressure exceeded the value p DTC max during the last operating p...

Page 16: ...216 C equipment With the outputs on the main equipment this makes a maximum of 128 valve outputs available Extractor element Device for extracting the filter casing from the dust deposited E g cellular wheel sluice through conveyor worm Extractor element contactor Contactor which switches an extractor element drive unit on and off I O module Input output module module for the input and output of c...

Page 17: ...ves Number of all valves connected to the RM 216 C and to the expansion modules p alarm Differential pressure value at which an alarm is issued p MAX Differential pressure value at which the cleaning is started p MIN Differential pressure value at which the cleaning is stopped p mode Operating mode of the filter control in which the cleaning of the filter elements depends on the differential press...

Page 18: ...ts Measurement sensor piezoresistant excessive pressure safe up to 120 kPa Fuses 230 V T 0 4 A 250 V 5 x 20 mm 110 V T 0 8 A 250 V 5 x 20 mm Extra low voltage Fusing via PTC resistor Temperature range 20 C to 60 C Degree of protection Casing IP 66 NEMA 4 Dimensions See chapter 3 Assembly Weight approx 0 8 kg Installation height max 3000 m above M S L The unit can be operated with a supply voltage ...

Reviews: