background image

REC Installation Manual - N-Peak - IEC 61215 /61730
Rev C - 07.19 

Ref: NE-06-22

5

ELECTRICaL INSTaLLaTION 

ElECtriCal rEquirEMENts
i)  application Class

REC solar panels are rated for use in electrical application Class a, Protection Safety Class II; at hazardous levels of voltage (>35V), current(>8a) 

and power (>240W) where general contact access is anticipated (panels qualified for safety through IEC 61730-1 and -2).

ii)  system requirements 

REC solar panels are only for use where they meet the specific technical requirements of the complete system. Ensure other components will not 

cause mechanical or electrical damage to the panels. Only panels of the same type and power class should be connected.

iii)  string configuration

When connecting panels in a string, plan and execute according to the inverter manufacturer’s instructions. The number of panels connected to an 

inverter not exceed the voltage limits and operating range permitted by the manufacturer, nor under any circumstance exceed the maximum system 

voltage as stated in the technical specifications for the product at the rear of this manual. The maximum system fuse rating (overcurrent protection 

rating) and the maximum reverse current for each panel can be found in the technical specifications for the product at the rear of this manual.
The maximum number of panels in a string can be calculated by dividing the maximum system voltage of the panel by its V

OC

 accounting for the lowest 

ambient temperature at site, e.g.: for a 1000V system, if the lowest ambient temperature is 15°C, the panel has a V

OC

 of 40.8 V and a temperature coefficient 

of V

OC

 of -0.27%/°C, the maximum panels per string is 23 (∆T°C = 25° - 15° = 10°; 10° x 0.27 = 2.7%; 40.8 + 2.7% = 41.9; 1000 V / 40.4 = 23.9, so a total 

of 23 panels or 974 V). Qualified system designers can make exact calculations that account for specific project requirements and site conditions.

iv)  string connection

Panels connected in series must have the same ampere rating. The maximum number of panels that can be connected in series or parallel depends upon 

system design, inverter type and environmental conditions. String configuration must correspond to the specifications of other system components e.g., 

inverter. Refer to the reverse current rating of the panel indicated in the technical characteristics at the rear of this manual or on the panel datasheet.

v)  Wiring layout

To minimize voltage surges (e.g., indirect lightning strikes), cables of the same string must be bundled together so loops are as small as possible. 

String configurations must be checked before commissioning. If open circuit voltage (V

oc

) and short circuit current (I

sc

) deviate from specification, 

this may indicate a configuration fault. Correct DC polarity must be observed at all times.

vi)  Electrical ratings

Electrical ratings are within a specific tolerance of measured values at Standard Test Conditions (STC) as given in the technical characteristics for each 

panel at the rear of this manual. allow for increased panel output as a result of conditions different to STC by multiplying the I

SC

 and V

OC

 values by a 

factor of 1.25 (or according to local regulations) when determining component voltage ratings, conductor ampacities, overcurrent device ratings and 

size of controls connected to the PV output.

MECHaNICaL INSTaLLaTION

firE guidEliNEs

REC solar panels have a Class C fire classification. Utilize the following fire safety guidelines when installing REC solar panels: 

• 

Check with all relevant local authorities for fire safety requirements for any building or structure on to which the panels will be installed,

• 

The system design must ensure that it can be easily accessed in the event of a building fire,

• 

Check with relevant authorities for applicable regulations concerning setbacks or other placement restrictions that may apply for roof-mounted arrays,

• 

The use of DC ground fault interrupters is recommended. This may also be required by local and national codes,

• 

all electrical appliances are a fire risk. The panel must be mounted over a fire retardant roof covering rated for the application and a distance 

of 

60

 mm between the panel and the mounting surface, allowing free circulation of air beneath the panels must be respected at all times.

oriENtatioN

The optimal mounting position of panels results in the sun’s rays falling perpendicular (i.e., at 90°) to the surface. To maximize system output, panels should 

be installed at the optimum orientation and tilt angle. The specifics of this depend on location and can be calculated by a qualified system designer. all 

panels in a string should, wherever possible, have the same orientation and tilt to ensure the system does not underperform due to mismatched outputs.

Dependent on local conditions, a lower angle of installation will potentially increase the requirement for regular cleaning.

The solar panels must not be exposed to artificially concentrated light.

ENviroNMENtal faCtors

REC solar panels are designed to provide decades of durable and stable output in installations up to 2000 m above sea level. ambient operating 

temperatures must be between -40° and +85°C. 

For further information regarding installations on water platforms, e.g., floating pontoons, see Annex 1 at the rear of this manual.

The panels are not suitable for installation in potentially hazardous locations nor should they be installed in the following locations: 

• 

Near sources of flammable gas or vapor e.g., gas stations, gas containers or spray paint facilities,

• 

Near open flames,

• 

Under water or in water features,

• 

Where exposed to sulfur e.g., near sulfur springs or volcanoes,

• 

Where the panels may be exposed to harmful chemicals.

Ensure panels are not exposed to direct contact with salt water/spray.

Summary of Contents for ALPHA BLACK Series

Page 1: ...rec N Peak Series for all REC N Peak solar panels certified according to IEC 61215 IEC 61730 Installation instructions ...

Page 2: ...S 13 Technical Properties REC N Peak Series 13 Technical Properties REC N Peak Black Series 14 ANNEX 1 INSTALLATIONS ON WATER PLATFORMS 15 ANNEX 2 INSTALLATIONS using Module level power electronics 16 EC DECLARATION OF CONFORMITY 17 DOCUMENT HISTORY 18 List of figures Fig 1 Clamp specifications End and mid clamps 6 Fig 2 Clamping of panels with rails parallel to the short side 7 Fig 3 Clamping zon...

Page 3: ... and effective installation and operation of the photovoltaic system and for adhering to all applicable local and national standards and regulations Prior to installation check all current regulations and permits concerning solar installations and ensure all local directives are observed Furthermore installers are responsible for the following points Ensuring the REC panels are in a suitable condi...

Page 4: ...ic shocks Exercise extreme caution when wiring panels and look out for damaged or dirty cables etc Never insert metallic or other conductive objects into plugs or sockets Ensure that all electrical connections are completely dry before assembly Keep all materials tools and working conditions dry and tidy Use appropriate safety equipment e g non slip footwear insulated gloves and insulated tools So...

Page 5: ...ctrical Ratings ElectricalratingsarewithinaspecifictoleranceofmeasuredvaluesatStandardTestConditions STC asgiveninthetechnicalcharacteristicsforeach panel at the rear of this manual Allow for increased panel output as a result of conditions different to STC by multiplying the ISC and VOC values by a factor of 1 25 or according to local regulations when determining component voltage ratings conduct...

Page 6: ...tem Rails must be suitable for the intended installation and able to withstand anticipated snow and wind loads When using mounting rails ensure they run underneath the panel to provide support to the frame The positioning of the rail must ensure that the minimum clamp grip length and the central point of the fixation e g the bolt is fully within the required clamping zone as indicated on the follo...

Page 7: ...panelaspertheexamplesshowninfig 2 theclampingzonesshowninfig 3aretobefollowed Thepositioningofthe rails must ensure that the minimum grip length of the clamp and the central point of the fixation e g the bolt is fully within the required clamping zone as indicated in fig 3 Each panel must be clamped in a minimum of four separate zones with one clamping point in each quarter of the panel fig 3 Fig ...

Page 8: ...ad Site specific factors such as high winds or snow levels must be taken into consideration to ensure this limit is not exceeded These instructions must be followed for each clamping method used Clampsmustbepositionedsothatboththeminimumgriplengthandthecenterpointofeachclamparelocatedintherequiredclampingzone Follow the clamp manufacturer s instructions to install the clamps including the recommen...

Page 9: ...esign load upwards pressure stated design loads DL apply a safety factor of 1 5 to the test load e g 5400 Pa 1 5 3600 Pa Part Name Material Rail 6105 T5 aluminum extrusion Bolt M6 x 25 drop inT stud kit Nut M6 flanged hex locking nut Fig 6 Mounting holes REC N Peak Fig 7 Mounting hole specifications REC N Peak Fig 8 Mountingholeinstallationexample RECN Peak 1000 39 1200 47 Scale 1 1 57 11 mm 0 2 0...

Page 10: ...e panel on both the long side and the short side asshowninfig 9 to aid in grounding Thesecanbefurther identified by the grounding symbol stamped in the frame next to it on the long side The support bars across the rear of REC N Peak solar panels are connected to the frame via specially designed grounding clips and do not need to be individually grounded Check all applicable requirements before beg...

Page 11: ...d Any other connector Some countries and or regions have specific regulations regarding the mating of connectors Installers are responsible for ensuring the compliancy of the system with such local regulations The cutting of cables is only permitted in order to replace a factory installed connector with another brand of connector to ensure like for like mating when connected to a non REC external ...

Page 12: ...rmationSheetwhichisavailabletodownloadfromtheonlineREC Download Center www recgroup com downloads If in doubt at any time when cleaning the panels stop and obtain professional advice System inspection The system should be inspected regularly to ensure that Fasteners are secure tight and free from corrosion Electrical connections are secure tight clean and free of corrosion The mechanical integrity...

Page 13: ...713 kg m Design load wind 1600 Pa 163 kg m Maximum test load 2400 Pa 245 kg m Max series fuse rating 25 A Max reverse current 25 A Calculated using a safety factor of 1 5 See installation manual for mounting instructions certifications Measurements in mm in Nominal Module Operating Temperature 44 C 2 C Temperature coefficient of PMPP 0 35 C Temperature coefficient of VOC 0 27 C Temperature coeffic...

Page 14: ...ximum test load 7000 Pa 713 kg m Design load wind 1600 Pa 163 kg m Maximum test load 2400 Pa 245 kg m Max series fuse rating 25 A Max reverse current 25 A Calculated using a safety factor of 1 5 See installation manual for mounting instructions certifications Measurements in mm in Nominal Module Operating Temperature 44 C 2 C Temperature coefficient of PMPP 0 35 C Temperature coefficient of VOC 0 ...

Page 15: ...el during normal operation This will help to shield the panel from direct water spray Installation Instructions i System installation All cables used for the installation must have sufficient length and slack to prevent damage due to water level changes and wave motions Negative system grounding is required for REC solar panels installed on a floating platform ii Mounting panels Installation of RE...

Page 16: ...he conformity of the product with the requirements of the above mentioned EC Directive and its conformity with the safety requirements of the EC Low Voltage Directive 2014 35 EU DIN EN 61215 VDE 0126 31 2006 02 EN 61215 2005 DIN EN 61730 1 VDE 0126 Teil 30 1 2007 10 EN 61730 1 2007 05 DIN EN 61730 1 A1 VDE 0126 30 1 A1 2012 09 EN 61730 1 2007 A1 2012 DIN EN 61730 1 A2 VDE 0126 30 1 A2 2014 01 EN 6...

Page 17: ...nual N Peak IEC 61215 61730 Rev C 07 19 Ref NE 06 22 17 DOCUMENTHISTORY Date Revision Reason 07 2018 A First release 01 2019 B Update to warranty conditions addition of REC N Peak Black Series 08 2019 C Updated Datasheets ...

Page 18: ...RECSolarPte Ltd 20TuasSouthAvenue14 Singapore637312 Singapore Tel 6564959228 Mail post recgroup com www recgroup com 18 REC Installation Manual N Peak IEC 61215 61730 Rev C 07 19 Ref NE 06 22 ...

Page 19: ...e panel frame Follow MLPE manufacturer instructions to ensure optimum mounting of MLPE device and prevent any slippage during operation MLPE devices may also be attached to the mounting construction In such cases refer to the instructions provided by the manufacturer Wherever possible the installation of the MLPE device should not cover the product label on the rear of the panel MLPE devices may o...

Reviews: