Thermostat Info Screen
Setup Button (not labeled on screen)
To setup the thermostat to work
with your HVAC system, press and hold the “Setup”
button. This will take you to the installation setup screen. See installation instructions for
proper settings.
Status Button (not labeled on screen)
Press and hold this button. A system status screen will show the output status of the
thermostat relays.
Done Button
Press Done to exit the thermostat Info screen back to the main menu.
Thermostat Operation
Minimum Run Time (MRT)
The thermostat has a Minimum Run Time after the start of any heating or cooling call.
This minimum run time assures even heating and cooling cycles. The MRT delay will keep
the system on even if reaches setpoint or you change the setpoint to a temperature that
would satisfy the call, until the MRT expires. Changing the Mode to OFF will cancel the
MRT and the system will turn off immediately. The MRT can be adjusted in the Installer
Settings menu of the thermostat.
Note: The MRT status is shown in the thermostat System Status on-screen labels
.
Minimum Off Time (MOT)
The thermostat has a Minimum Off Time after any heating or cooling call is finished. This
delay prevents rapid heating/cooling cycles and also provides “short cycle protection” for
compressor calls. This delay may be noticeable when you change a setpoint and it does
not respond immediately due to another call that has recently completed and the MOT
delay timer is preventing the system from restarting. The MOT delay time can be adjusted
in the Installer Settings menu of the thermostat. There is a minimum of 5 minutes delay to
assure compressor protection.
Note: The MOT status is shown in the thermostat System Status on-screen labels.
Press and Hold
Setup
button
to go to the HVAC system
setup screen
Done
Setup
TZ45R Ver 02.02.29
ZVER: 2.16 ZNID: 001
ZHID: 00.00.07.76
System Type: Standard
Fan Type: Gas
Thermostat Info
Status