RCNTEC RPCM Series Quick Install Manual Download Page 8

8. Requirements for Ambient Conditions During Use

Normal ambient conditions for use of Resilient Power Control Module (RPCM) are the following:

operation range of ambient temperature is 0-40°С;

operation range of relative humidity is 45-85% (non-condensing);

operation range of altitude is 0-2000m.

The surrounding environment is non-explosive, does not contain a considerable amount of 
conductive dust, vapors, aggressive gases in concentrations that harmfully affect RPCM components 
and materials.

WARNING!

 The maximum range of temperature fluctuation during storage is 20°C per hour. 

Storage temperature is from -20 to 60°C. Prior to activating RPCM, it is necessary to allow the 
device time of not less than 24 hours to adapt to the new conditions. Physical installation of RPCM 
may continue during this acclimatization period. If there is condensation even after the 24-hour 
period, it will be necessary to wait until the specified norms have been reached before you can 
activate the system.

During inspection of the exterior, the following are to be determined:

there are no defects on and damages to the external surfaces of the product;

there is a seal and it is intact.

The quality of the modules’ plug assembly must ensure reliable contact with connecting elements 
and eliminate inadvertent disconnection.
Electric connectors must ensure uninterrupted performance of technical support components and 
external connectors must allow peripheral devices to be turned off and connected during regular 
operation mode without loss in connection quality and ensure reliable electrical and mechanical 
contact.
The surface area of RPCM and slots used must be free of chips, scratches, dents, and other defects.

9. Inspection before Installing and Using

http://rpcm.pro
Tel: +7 (495) 009 87 87, +7 (800) 302 87 87
E-mail: [email protected]

Contacts:

Feedback: 

http://rcntec.com/feedback

Voltage < 240V. Frequency is 50-60Hz in a power grid.
Electric current level <16А for RPCM 1502,  <32А for RPCM 1532 and <63A for RPCM ME 1563.
Voltage supply requirements: 

for RPCM 1502 — two power cables with IEC-320-C19 connectors, 

for RPCM 1532  — two sockets for plugging the 2P+E 32A 250V connectors, 

for RPCM ME 1563 — one socket for plugging the 2P+E 63A 250V. 

NOTE

: if only one cable is connected, the RPCM 1502 or RPCM 1532 will function properly except 

for the ATS operation.

7. Power and Grounding Requirements

Summary of Contents for RPCM Series

Page 1: ...Resilient Power Control Module RPCM Quick Install Guide For models RPCM 1502 16 RPCM 1532 32 RPCM ME 1563 63A Mining Edition Version 201908210021...

Page 2: ...with great user experience We have paid a lot of attention to craft the device the way we would want it to be for ourselves In many ways physically ergonomically architecturally electrically it is de...

Page 3: ...pping current of the upstream circuit breakers must be chosen so that the tripping does not occur at the fault current measured at the point connect the consumer To ensure complete selectivity the use...

Page 4: ...CM 1502 16A and RPCM 1532 32A Fig 5 Elements on the rear panel of RPCM 1502 model 16A Designation 13 Inputs indicators 1 2 of RPCM 1532 14 One input indicator of RPCM ME 1563 15 One input of RPCM ME 1...

Page 5: ...press the third time RPCM will switch over to IP address display mode When you press the fourth time the MAC address will be displayed Receiving an IP address IP address is obtained by default via DH...

Page 6: ...er Firefox version 56 0 and higher Opera version 48 0 2685 32 and higher After going to the specified webpage the authentication window will open up where you can enter username and password as well a...

Page 7: ...o get suggestions SuperGeroy 192 168 xx yy 0 rpcmadmin 6 Connecting via SSH To connect via SSH protocol in UNIX based systems it will be sufficient to indicate from within the terminal s emulator the...

Page 8: ...and damages to the external surfaces of the product there is a seal and it is intact The quality of the modules plug assembly must ensure reliable contact with connecting elements and eliminate inadv...