5. Connect fire alarm control panel to EOL input terminals, ensure the 2.2K resistor is
installed at the terminals in the fire alarm panel.
a) See fire alarm control panel installation and operation manual for details about
signaling requirements.
b) Fig’s 2-6 in this installation guide will provide details on wiring to the fire alarm
control panel.
6. Connect any required monitoring equipment to the trigger relays using
appropriate cabling.
7. This unit is to be powered from a 10 Series RCI Power Supply or a UL listed
power supply.
8. Apply power to power supply to activate control board and test all connected devices.
Specifications
• For UL listed power supply
• UL 294 6e and ULC S319 Class 1 Access Control System Unit
Access Control Levels:
Endurance: Level 4 Line Security: Level 1
Power Standby: Level 1 Destructive Attack: Level 1
Input
• Input Voltage: 12 or 24VDC ± 10%
• Typical Current Draw with no Output Load: 10mA @ 12VDC
15mA
@ 24VDC
Output
• Output Relay Rating: 3A
Monitor Inputs
• EOL (End of Line) Trigger: Trigger at + or – 50% of 2.2K
• OVR Trigger
• AUX Trigger
• Reset Input
• Ground Fault Trigger (see note 1a)
Monitor Outputs
• Trigger Relay Rating: 1A DPDT
Environmental
• Use in a controlled indoor environment
Warning: Improper wiring connections may result in damage to this product.
Mise en garde: Un mauvais raccordement des c
â
bles risque d’endommager ce produit.