5.  Connect fire alarm control panel to EOL input terminals, ensure the 2.2K resistor is 

  installed at the terminals in the fire alarm panel. 

  a)  See fire alarm control panel installation and operation manual for details about 

    signaling requirements. 

 

  b)  Fig’s 2-6 in this installation guide will provide details on wiring to the fire alarm 

    control panel.

6.  Connect any required monitoring equipment to the trigger relays using 

  appropriate cabling. 

7.  This unit is to be powered from a 10 Series RCI Power Supply or a UL listed  

 

  power supply.

8.  Apply power to power supply to activate control board and test all connected devices.

Specifications

•  For UL listed power supply
•  UL 294 6e and ULC S319 Class 1 Access Control System Unit 
  Access Control Levels:

  Endurance: Level 4            Line Security: Level 1

  Power Standby: Level 1     Destructive Attack: Level 1

Input

•  Input Voltage: 12 or 24VDC ± 10%

•  Typical Current Draw with no Output Load: 10mA @ 12VDC

   

15mA

 

@ 24VDC

Output

•  Output Relay Rating: 3A

Monitor Inputs

 

•  EOL (End of Line) Trigger: Trigger at + or – 50% of 2.2K

•  OVR Trigger

•  AUX Trigger

•  Reset Input

•  Ground Fault Trigger (see note 1a)

Monitor Outputs

•  Trigger Relay Rating: 1A DPDT

Environmental

•  Use in a controlled indoor environment

Warning: Improper wiring connections may result in damage to this product.
Mise en garde: Un mauvais raccordement des c

â

bles risque d’endommager ce produit.

3

Summary of Contents for PDD-FT-3

Page 1: ...Installation and Specifications Manual PDD FT 3 I n s t a l l a t i o n ISPSFPD 3 PCN16045 R12 17GR 2017 Rutherford Controls Int l dormakaba Group www rutherfordcontrols com Phone 1 800 265 6630 Fax 1 800 482 9795 E mail sales rutherfordcontrols com ...

Page 2: ...used and power supply enclosure is properly grounded b As this device can be used to power multiple devices ensure that all wiring is of an appropriate gauge for the devices being installed c This RCI board is for use in a controlled indoor environment The PDD FT 3 and all devices connected to or powered through the PDD FT 3 shall be installed within the same continuous building structure Installa...

Page 3: ... control board and test all connected devices Specifications For UL listed power supply UL 294 6e and ULC S319 Class 1 Access Control System Unit Access Control Levels Endurance Level 4 Line Security Level 1 Power Standby Level 1 Destructive Attack Level 1 Input Input Voltage 12 or 24VDC 10 Typical Current Draw with no Output Load 10mA 12VDC 15mA 24VDC Output Output Relay Rating 3A Monitor Inputs ...

Page 4: ...to an override switch When OVR is open unit will trigger Input Trigger AUX IN 2 position terminal block Will accept 12AWG wire This pair is normally closed and can be connected to an auxiliary device When AUX IN is open unit will trigger Reset 2 Position Terminal Block 2 position terminal block Will accept 12AWG wire When this pair is shorted input trig gers do not latch If pair is open the input ...

Page 5: ...he PDD FT 3 outputs will also reset N OFF N ON INPUT GRN EOL RESET AUX OVR RST AUX IN OVR C NO NC TRIGGERED 2 2 K PDD FT C NO NC TRIGGERED DC Input Trigger Output Ground Fault Jumper Reset Input End Of Line Override Input Auxilary Input Normally On Output Normally Off Output Output Led s BAT Output 24V 12V DC N OFF N ON INPUT GRN EOL RESET AUX OVR RST AUX IN OVR C NO NC TRIGGERED PDD FT C NO NC TR...

Page 6: ...only as long as the fire alarm relay is active When the fire alarm resets the PDD FT 3 outputs will also reset Connecting the EOL input of one board to the trigger relay of the next board as shown will allow for override and reset of multiple boards Note The RST jumper must be left in place on all boards for automatic reset operation Remarque La bretelle RST doit être laissée en place sur tous les...

Page 7: ...l both relays have been reset and the N O manual reset is triggered Note Ensure jumpers for RST OVR and AUX IN are removed to allow terminals to operate correctly Remarque Assurez vous que les bretelles RST OVR et AUX IN sont retirées afin de per mettre aux terminaux de fonctionner correctement BAT Output 24V 12V DC N OFF N ON INPUT GRN EOL RESET AUX OVR RST AUX IN OVR C NO NC TRIGGERED PDD FT C N...

Page 8: ...tput LED should be lit if output is active Check for proper wiring connections on trigger connections Ensure that 2 2K resistor is installed at End of Line position in the wiring Check devices connected to outputs for a short circuit PTC s may require short to be removed for several minutes before automatically resetting No DC output from terminals Trigger is active and will not reset Trouble outp...

Reviews: