background image

Details

The PDD-FT-3 board is a fire panel control interface. This board can be used to control DC 

output based on a fire alarm control panel. Two outputs switch state on alarm. 

Features

•  Non Latching or Latching mode

•  Universal 12VDC or 24VDC Operation

•  Reverse polarity protected

•  Normally ON & Normally OFF Output

•  Output LED’s indicate condition

•  Outputs can be Triggered with:

    1) N/O or N/C Switch with Supervised End of Line Resistor (EOL)

    2) N/C Switch with (OVR) over ride

    3) N/C Switch with (AUX-IN) auxiliary

    4) Ground on any trigger input when (GRN) Jumper is enabled

•  Form C DPDT Relay Indicates Trigger Status 

•  3 Amp Transfer Relay Contacts

•  Auto or manual reset by jumper selection

Installation Instructions

1.  Mount the PDD-FT-3 board in a suitable location in close proximity to the power supply. 

 

Note:

 

a)  Ground fault detection will only work if conductive stand offs are used and power 

    supply enclosure is properly grounded.

 

b)  As this device can be used to power multiple devices ensure that all wiring is of an 

    appropriate gauge for the devices being installed.

  c)  This RCI board is for use in a controlled indoor environment. The PDD-FT-3 and 

    all devices connected to or powered through the PDD-FT-3 shall be installed within 

    the same continuous building structure. Installation must be in accordance with 

    local building and fire codes. Check with Authority Having Jurisdiction (AHJ) for 

    details prior to installing.

  d)  All power limited wiring must be a minimum of .25” from non-power limited wiring.

  e)  Maximum torque of 7 in*lb for black input and output terminals.

2.  Connect “INPUT” terminals to output of DC supply, paying close attention to polarity of   

  DC output from power supply.

3.  Connect devices to be powered to output terminals of PDD-FT-3 control board, paying 

  close attention to polarity requirements. Minimum 22AWG and maximum distance of    

  6170ft. for field wiring.

4. Set jumpers (RST, OVR, AUX, and GRN) as required for proper installation.

2

Summary of Contents for PDD-FT-3

Page 1: ...Installation and Specifications Manual PDD FT 3 I n s t a l l a t i o n ISPSFPD 3 PCN16045 R12 17GR 2017 Rutherford Controls Int l dormakaba Group www rutherfordcontrols com Phone 1 800 265 6630 Fax 1 800 482 9795 E mail sales rutherfordcontrols com ...

Page 2: ...used and power supply enclosure is properly grounded b As this device can be used to power multiple devices ensure that all wiring is of an appropriate gauge for the devices being installed c This RCI board is for use in a controlled indoor environment The PDD FT 3 and all devices connected to or powered through the PDD FT 3 shall be installed within the same continuous building structure Installa...

Page 3: ... control board and test all connected devices Specifications For UL listed power supply UL 294 6e and ULC S319 Class 1 Access Control System Unit Access Control Levels Endurance Level 4 Line Security Level 1 Power Standby Level 1 Destructive Attack Level 1 Input Input Voltage 12 or 24VDC 10 Typical Current Draw with no Output Load 10mA 12VDC 15mA 24VDC Output Output Relay Rating 3A Monitor Inputs ...

Page 4: ...to an override switch When OVR is open unit will trigger Input Trigger AUX IN 2 position terminal block Will accept 12AWG wire This pair is normally closed and can be connected to an auxiliary device When AUX IN is open unit will trigger Reset 2 Position Terminal Block 2 position terminal block Will accept 12AWG wire When this pair is shorted input trig gers do not latch If pair is open the input ...

Page 5: ...he PDD FT 3 outputs will also reset N OFF N ON INPUT GRN EOL RESET AUX OVR RST AUX IN OVR C NO NC TRIGGERED 2 2 K PDD FT C NO NC TRIGGERED DC Input Trigger Output Ground Fault Jumper Reset Input End Of Line Override Input Auxilary Input Normally On Output Normally Off Output Output Led s BAT Output 24V 12V DC N OFF N ON INPUT GRN EOL RESET AUX OVR RST AUX IN OVR C NO NC TRIGGERED PDD FT C NO NC TR...

Page 6: ...only as long as the fire alarm relay is active When the fire alarm resets the PDD FT 3 outputs will also reset Connecting the EOL input of one board to the trigger relay of the next board as shown will allow for override and reset of multiple boards Note The RST jumper must be left in place on all boards for automatic reset operation Remarque La bretelle RST doit être laissée en place sur tous les...

Page 7: ...l both relays have been reset and the N O manual reset is triggered Note Ensure jumpers for RST OVR and AUX IN are removed to allow terminals to operate correctly Remarque Assurez vous que les bretelles RST OVR et AUX IN sont retirées afin de per mettre aux terminaux de fonctionner correctement BAT Output 24V 12V DC N OFF N ON INPUT GRN EOL RESET AUX OVR RST AUX IN OVR C NO NC TRIGGERED PDD FT C N...

Page 8: ...tput LED should be lit if output is active Check for proper wiring connections on trigger connections Ensure that 2 2K resistor is installed at End of Line position in the wiring Check devices connected to outputs for a short circuit PTC s may require short to be removed for several minutes before automatically resetting No DC output from terminals Trigger is active and will not reset Trouble outp...