1.   Mount the electromagnetic lock to the door frame as outlined 

on the installation template included with the product. 

NOTE: During installation of the armature plate to the door it

is essential that the armature plate remains movable. The

armature plate must be allowed to pivot on the center-mounting

bolt to allow proper alignment with the magnet surface. If the

plate is not aligned with the magnet surface, the lock may lose

holding force or not lock at all  . 

The head of the armature mounting bolt ships with a rubber

washer affixed to it. This washer should project slightly beyond

the surface of the armature plate. This is to allow the washer to

expand when power is removed and break the air vacuum

between the plate and the magnet surface. If this washer is

removed or trimmed the lock will appear to have some holding 

force even when power is removed.

For added safety, thread locking compound has been provided for

the armature plate bolt and the four captive electromagnetic lock

mounting screws.

WARNING: Improper installation, maintenance, inspection or 

usage of the product or any related accessories or parts may 
cause the electromagnetic lock, armature plate and associated 
hardware to disengage and fall, causing serious bodily injury and 
property damage. Rutherford Controls Int’l Inc. and/or  Rutherford 
Controls Int’l Corp. will not be liable to the installer, purchaser, 
end user or anyone else for damage or injury to person or 
property due to improper installation, care, storage, handling, 
maintenance, inspection, abuse, misuse or act of God or nature 
involving this product or any related accessories or parts.

2.   Route the power supply connecting wire through the door 

frame and into the wire access hole in the top of the magnet 

housing. Connecting wire should be of sufficient gauge for 

the lock being installed and the distance being run. See table 

for current draw specifications and wiring gauge chart.

Installation Instructions

Pre-Installation Instructions

1.   This product must be installed according to all applicable 

building and life safety codes. 

2. 

 

Due to the variety of mounting configurations available with 

this product, a survey and assessment of the physical area 

in which the product will be installed must be performed. 

3.   The door frame must be inspected and deemed structurally 

sound prior to installation of the electromagnetic lock. The 

structural integrity of the mounting surfaces must be strong 

enough to meet or exceed the holding force of the product. 

4.   The product must be protected from potential damage due 

to intruders or tampering. 

5.   The product should be installed in a location that will not 

hinder or create a potential safety hazard to authorized 

personnel accessing the protected area. 

6.   Because electromagnetic locks are used in a variety of 

applications and different door frame configurations, an 

experienced installer with knowledge of this product must 

make a determination of the optimal mounting method for 

this specific application. 

7.   The components, hardware, installation instructions and 

mounting template included with this product are intended 

for use on outswinging doors. 

8.   Do not install this product on the exterior of buildings. 

9.  Do not use as a doorstop. This will void warranty.

10.  Separate accessories not included with this product must be 

used in the following applications: 

 

   •  Inswinging doors 

 

   •  Narrow head jamb situations or center-hung doors 

 

   •  Wherever there is insufficient space on the door 

 

     frame header to mount the lock 

 

   •  Glass or Herculite doors that do not have a door frame 

 

   •  Hollow metal or wood frames where the door stop is  

     not thick enough to allow the product to be installed 

 

   •  Wherever an obstruction in the door prevents    

     installation of the armature plate at a proper height  

   •  Doors that do not permit the armature plate to be  

     mounted low enough to meet the magnet surface 

 

Refer to the Product Accessories Guide section of the 

Installation Instructions for further information. Accessories 

may impact holding force. 

11.   Installation of this product should be done by an experienced 

installer with knowledge of this product. 

NOTE: It is highly recommended that thread locking compound

be applied to all screws during installation to reduce chance of

screws loosening over extended time.

PleASe DelIveR All INSTAllATIoN INSTRuCTIoNS To  

tHe eND-user upoN completIoN of tHe INstallatIoN.

© 2017 RutheRfoRd ContRols Int’l | dormakaba Group

www.rutherfordcontrols.com • Phone: 1.800.265.6630 • fax: 1.800.482.9795 • e-mail: [email protected]

Summary of Contents for 8310

Page 1: ...rations available with this product a survey and assessment of the physical area in which the product will be installed must be performed 3 The door frame must be inspected and deemed structurally sound prior to installation of the electromagnetic lock The structural integrity of the mounting surfaces must be strong enough to meet or exceed the holding force of the product 4 The product must be pr...

Page 2: ...inal of the lock in Fig 2 Switching the negative power supply line will not allow the lock to release immediately RCI electromagnetic locks contain MOV s for surge suppression and do not require any additional suppression to be added during installation The installation of diodes across the lock input terminals will cause a delay in release Fig 2 Power Connections SWITCH INCORRECT CORRECT SWITCH F...

Page 3: ... at the bolt There should be no movement to the mounting bracket or housing of the electromagnetic lock For added safety thread locking compound has been provided for the armature plate bolt and the four captive electromagnetic lock mounting screws WARNING Improper installation maintenance inspection or usage of the product or any related accessories or parts may cause the electromagnetic lock arm...

Page 4: ...cted releasing devices lock terminals and lock circuit board to magnet core Check delayed relock wiring and time setting Check that the momentary switch does not include a shunted light option Lock has enough holding force to lightly hold a screwdriver or set of pliers but door will not lock Check to see that armature plate is correctly aligned with the electromagnetic lock If there is improper al...

Page 5: ...ere there is insufficient frame depth to mount the lock Available in several different sizes and finishes L Bracket Required wherever there is insufficient space on the frame header to mount the lock The lock mounts to the underside of the L bracket and the L bracket then gets mounted to the doorframe Available in several finishes Glass Door Bracket Allows an armature plate to be mounted to a glas...

Page 6: ...ide extra mounting space in a hollow metal or wood frame where the door stop of the frame is not thick enough to allow a lock to be installed Available in several different heights and widths Spacer Bars For use when an obstruction in the door prevents the installation of the armature plate at a proper height If the armature plate needs to be lowered then a spacer bar can be used to lower the lock...

Page 7: ...10 1000 14 10 10 1500 12 10 Total One Way Length of 1 4A 1 2A 3 4A 1A 1 1 4A 1 1 2A 2A 3A Wire Run ft 100 20 18 16 14 14 12 12 10 150 18 16 14 12 12 12 10 200 16 14 12 12 10 10 250 16 14 12 10 10 10 300 16 12 12 10 10 400 14 12 10 500 14 10 10 750 12 10 1000 10 1500 10 Load Current 24V Load Current 12V Wire Gauge Chart courtesy of Electronic Locking Devices by John L Schum WIRE GAUGE SELECTIONS 7 ...

Page 8: ...CATION DATE NOTES INITIAL 8310 8320 Electromagnetic Lock Installation Instructions Continued 2017 Rutherford Controls Int l dormakaba Group www rutherfordcontrols com Phone 1 800 265 6630 Fax 1 800 482 9795 E mail sales rutherfordcontrols com ...

Reviews: