I N S T A L L A T I O N
8310/8320
Electromagnetic Locks
IS8310-20
PCN16047
R09/17GR
1. Mount the electromagnetic lock to the door frame as outlined
on the installation template included with the product.
NOTE: During installation of the armature plate to the door it
is essential that the armature plate remains movable. The
armature plate must be allowed to pivot on the center-mounting
bolt to allow proper alignment with the magnet surface. If the
plate is not aligned with the magnet surface, the lock may lose
holding force or not lock at all .
The head of the armature mounting bolt ships with a rubber
washer affixed to it. This washer should project slightly beyond
the surface of the armature plate. This is to allow the washer to
expand when power is removed and break the air vacuum
between the plate and the magnet surface. If this washer is
removed or trimmed the lock will appear to have some holding
force even when power is removed.
For added safety, thread locking compound has been provided for
the armature plate bolt and the four captive electromagnetic lock
mounting screws.
WARNING: Improper installation, maintenance, inspection or
usage of the product or any related accessories or parts may
cause the electromagnetic lock, armature plate and associated
hardware to disengage and fall, causing serious bodily injury and
property damage. Rutherford Controls Int’l Inc. and/or Rutherford
Controls Int’l Corp. will not be liable to the installer, purchaser,
end user or anyone else for damage or injury to person or
property due to improper installation, care, storage, handling,
maintenance, inspection, abuse, misuse or act of God or nature
involving this product or any related accessories or parts.
2. Route the power supply connecting wire through the door
frame and into the wire access hole in the top of the magnet
housing. Connecting wire should be of sufficient gauge for
the lock being installed and the distance being run. See table
for current draw specifications and wiring gauge chart.
Installation Instructions
Pre-Installation Instructions
1. This product must be installed according to all applicable
building and life safety codes.
2.
Due to the variety of mounting configurations available with
this product, a survey and assessment of the physical area
in which the product will be installed must be performed.
3. The door frame must be inspected and deemed structurally
sound prior to installation of the electromagnetic lock. The
structural integrity of the mounting surfaces must be strong
enough to meet or exceed the holding force of the product.
4. The product must be protected from potential damage due
to intruders or tampering.
5. The product should be installed in a location that will not
hinder or create a potential safety hazard to authorized
personnel accessing the protected area.
6. Because electromagnetic locks are used in a variety of
applications and different door frame configurations, an
experienced installer with knowledge of this product must
make a determination of the optimal mounting method for
this specific application.
7. The components, hardware, installation instructions and
mounting template included with this product are intended
for use on outswinging doors.
8. Do not install this product on the exterior of buildings.
9. Do not use as a doorstop. This will void warranty.
10. Separate accessories not included with this product must be
used in the following applications:
• Inswinging doors
• Narrow head jamb situations or center-hung doors
• Wherever there is insufficient space on the door
frame header to mount the lock
• Glass or Herculite doors that do not have a door frame
• Hollow metal or wood frames where the door stop is
not thick enough to allow the product to be installed
• Wherever an obstruction in the door prevents
installation of the armature plate at a proper height
• Doors that do not permit the armature plate to be
mounted low enough to meet the magnet surface
Refer to the Product Accessories Guide section of the
Installation Instructions for further information. Accessories
may impact holding force.
11. Installation of this product should be done by an experienced
installer with knowledge of this product.
NOTE: It is highly recommended that thread locking compound
be applied to all screws during installation to reduce chance of
screws loosening over extended time.
PleASe DelIveR All INSTAllATIoN INSTRuCTIoNS To
tHe eND-user upoN completIoN of tHe INstallatIoN.
© 2017 RutheRfoRd ContRols Int’l | dormakaba Group