13
ENGLISH
PARAMETERS
Name:
each MT 7308 can be named.
Local Bus Host:
system unit (MU 7100EN), to which the MT 7308 is linked.
MU 7100 pilot settings:
the pilot tone is generated by the MU 7100EN unit and can
be activated by selecting ‘Active’ on each output channel.
Pilot tone levels are important settings to get accurate monitoring results.
Default pilot tone level is –24 dB.
For a trial, each pilot tone can be adjusted by moving it cursor and then clicking the
‘Update Pilot Settings’ button. Yet, new pilot tone levels are not stored to memory.
To get a new default configuration, its file with proper settings must be loaded to the
system.
Important: a too high pilot tone level can damage external power amplifiers or/and
loudspeakers.
A proper pilot tone level range is from – 30 dB to –10 dB.
Address:
MT 7308 digital address setting, each unit shall have its own address.
Monitoring Interval:
monitor interval time (seconds).
Monitoring Active:
it enables the selected MT 7308 monitoring (note: the system
overall monitoring is to be activated as well).
Tolerance:
monitoring tolerance. The value 0 means no monitoring, any other value
activates the respective channel monitoring. Recommended monitoring tolerance is 10 ÷
30%.
If needed, the spare amplifier (line 8 input) can be monitored too.
Recommended tolerance for the spare amplifier is 80‐100%.
DSP OUTPUT SETTINGS
It is recommended to set a low-pass filter with cutoff frequency of 15 kHz for every
channel monitored by MT 7308 units.
A second or even a third low-pass filter (f: 15 kHz) can be inserted if necessary.
UPLOAD THE CONFIGURATION
Finally, upload the configuration from the PC to the system.