background image

 

  

Gas Detector Installation and Power-up

1

2

www.rcsystemsco.com

GETTING STARTED

 

 Installation of Gas Detector

 

Remove windowed lid from unit.

 

1. 

AL Enclosure - 

  

a.

  

Loosen lid set screw

  

b.

  

Rotate lid clockwise and remove

  

c.

  

Loosen thumb screws on display to remove 

 

 

 

display and access terminals

 

2

PY Enclosure - 

  

a.

 

Unscrew lid screws (4) to access terminals.

 

 

What you need (not included)

 

1.

 

Small Flathead Screwdriver

 

2

Phillips Screwdriver (for poly enclosure)

 

3

. Wire 

(RC Systems recommends: Belden 3124A 

 

 

Multi-Conductor wire or equivalent.) 

 

  

Summary of Contents for SenSmart 6000

Page 1: ...on Guide Flammable Toxic Gas Detectors Smart Alarm Controllers Fire Gas System Engineering Technical Service Support Warning Read understand contents of this manual prior to operation Failure to do so could result in serious injury or death ...

Page 2: ...oosen lid set screw b Rotate lid clockwise and remove c Loosen thumb screws on display to remove display and access terminals 2 PY Enclosure a Unscrew lid screws 4 to access terminals What you need not included 1 Small Flathead Screwdriver 2 Phillips Screwdriver for poly enclosure 3 Wire RC Systems recommends Belden 3124A Multi Conductor wire or equivalent ...

Page 3: ...TB1 4 See Figure 1 FOR ANALOG OUTPUT 3 Connect signal lead to TB1 2 Channel 1 and or TB1 3 Channel 2 4 20mA Out See Figure 1 FOR ETHERNET OUTPUT 4 Connect Ethernet cable to J3 Ethernet output See Figure 1 optional By default DHCP is enabled on the transmitter allowing the device to be discovered by its IP address Figure 1 ...

Page 4: ...nect to the shared power supply TB1 1 Figure 2 4 Connect 10 30VDC Ground GND TB1 2 wires to power terminal COM TB2 2 Figure 2 5 Locate the 10 0388 relay board This board is piggybacked behind the 10 0387 SenSmart 6000 CPU Display Board 6 Connect Modbus Terminal A TB1 3 from the remote sensor board to terminal A1 on the Relay Board TB1 1 Figure 2 7 Connect Modbus Terminal B TB1 4 from the remote se...

Page 5: ...sor board J2 and the sensor transmitter TR1 by lifting and repositioning If using two remote sensors on a single comm port daisy chained the remote sensor installed closeest to the transmitter should have the terminating resistor jumper in position B and the remote sensor furthest from the transmiter should have the terminating resistor jumper in position A REMOTE SENSOR INSTALLATION 5 ...

Page 6: ... Figure 2 Remote Sensor Power Up www rcsystemsco com ...

Page 7: ......

Page 8: ... configuring a remote sensor for the SenSmart 6900 DUAL transmitter be sure to configure Channel 2 first 1 Highlight Set Remote ID on transmitter 2 Swipe next until you reach the third digit Swipe edit set to 1 by swiping up and down buttons Swipe Edit to save Remote ID settings Remote ID 2 for Channel 2 and Remote ID for channel 1 3 Highlight Assign to Channel 4 Swipe Edit to enter Channel Assign...

Page 9: ... Board warning will appear this will modify channel config Swipe edit to select OK 7 Highlight Exit Program Mode 8 Swipe Edit to exit program mode If using two Remote Sensor Option Boards repeat the above configuration steps for Channel 1 Figure 3 Configuration Mode ...

Page 10: ...rews 2 Replace enclsoure lid 3 Apply power to unit and observe power up screen 4 After the warm up period observe gas type and gas concentration on screen 5 Using the magnet wand swipe Down Key on the display Follow on screen prompts to perform calibration www rcsystemsco com 8 ...

Page 11: ... ...

Page 12: ...technical support from experts right here in our local facility If you are in need of any assistance during the setup of this product you may contact our main office and your call will be directed appropriately At R C Systems we are proud to supply quality products and are happy to help if you have any questions or concerns ...

Reviews: