SenSmart 3000 User's Manual
Document: UM-1003
Revision Level B
27
(16 bit status words; bit assignment for each channel)
ALARM1_BELOW
BIT0
ALARM2_BELOW
BIT1
ALARM3_BELOW
BIT2
ALARM1_LATCH
BIT3
ALARM2_LATCH
BIT4
ALARM3_LATCH
BIT5
ALARM3_ACTIVE
BIT6
CHANNEL_DISABLED
BIT7
CHANNEL_CAL
BIT8
CHANNEL_LINEARIZE
BIT9
FAULT_RELAY_LATCH
BIT10
DISPLAY_NEGATIVE
BIT11
TRANSMIT SENSOR LIFE ENABLED BIT12
Alarm Status Word
31007
4
NA
(16 bit status word; bit assignment for system status)
CH1_ALM1
BIT0
CH1_ALM2
BIT1
CH1_FAULT
BIT2
CH2_ALAM1
BIT4
CH2_ALM2
BIT5
CH2_FAULT
BIT6
K1_STATUS
BIT8
K2_STATUS
BIT9
K3_STATUS
BIT10
Transmitter Status Word
31008
4
NA
(16 bit status word; bit assignment for system status)
CHAN_1_ACTIVE
BIT0
CHAN_2_ACTIVE
BIT1
SECURE_LEVEL
BIT2
MARKER Tx LED
BIT3
K1_FAILSAFE
BIT12
K2_FAILSAFE
BIT13
K2_ACK
BIT14
LOCK
BIT15
Chan 1 Sensor Life
31009
4
NA
Chan 2 Sensor Life
31010
4
NA
(16 bit signed integer ranging from
–1 to 100 where -1 indicates Cal Required)
Chan 1 Sensor Temperature
31011
4
NA
Chan 2 Sensor Temperature
31012
4
NA
(16 bit integer ranging from 1 to 4095 scaled for
–55 to +125 degrees C)
Memory Floating Point:
Note:
Returned as 15bit plus sign 2s complement with +/- 5% over/under range applied.
Consider over/under range when scaling values to be displayed at the workstation. The following
equation may be used to determine a value for display.
Display Value = MODBUS Value [ (Span Value -Zero Value) 1.1] + {Zero Value - [(Span Value - Zero Value)
.05]}
32767
FP Value Chan 1
33001
4
NA
FP Value Chan 2
33002
4
NA