RBI FUTERA XLF Series Installation And Operation Instructions Manual Download Page 26

F

d

b

b l

&

h

B l M

l

Finned copper tube gas boilers & water heaters – Boiler Manual

26

F

F

  The following start-up procedure assumes that all 

water piping, gas piping and electrical connections 

are correct as stated in this manual and the installation 
meets all State, Local, and City codes.

  See the Futera XLF Control IOM for troubleshooting 

information and control operation.

OPERATING INSTRUCTIONS 

Operating instructions

1.  If, at any time, the boiler will not operate properly, follow the 

instructions "TO TURN OFF GAS TO APPLIANCE," page 28, 
and call your service technician or gas supplier.

2.  Turn off  all electrical power to the boiler.
3.  Close main gas shut-off  valve (fi eld supplied), Figure 16, page 22.
4.  Purge the gas piping up to the boiler's manual gas valve (located 

ahead of the main gas valve). When the bleeding is complete, 
check all gas joints up to the gas valve for leaks.

5.  Wait fi ve (5) minutes to clear out any gas.

6.  Make sure all limits, pressures switches and safety device contacts 

are closed.

7.  Open the main gas shut-off  valve.

8.  Disable any external call for heat, such as from a building 

management system or remote operating controller.

9.  Toggle the remote/local switch (in control cabinet — see 

Figure 18) to 

REMOTE

.

10.  Turn on electrical power to the boiler.
11.  Turn the power switch on the front of the boiler control cabinet 

to 

ON

.

12. Th e HeatNet display will light up when the power is on. If all 

interlocks are properly closed, the display will say 

STANDBY

. If 

not, refer to the XLF HeatNet Control IOM for troubleshooting.

13.  Slide the HeatNet control's low fi re switch (on HeatNet control 

board) to the 

LOW FIRE

 position. 

14. Th e boiler will begin the start-up sequence.
15.  Allow the boiler to pre-purge and enter the pilot ignition cycle.
16. If pilot lights (indicated by a good fl ame signal 5.0 V DC) proceed 

to step 18. (See Honeywell R7800 literature for use of a meter to 
check fl ame signal if keypad readout is not available.) 

17.  If pilot is unstable (indicated by a low or erratic flame signal 

causing pilot fl ame failure), toggle the low fi re switch to 

DISABLE

then back to 

ENABLE

 to start another cycle (reset the Honeywell 

control if necessary). Repeat for one or two more times to ensure 
the pilot line is purged of all air. If pilot is still unstable, the pilot 
gas pressure may need to be increased. See step 18.

18.  Pilot pressure adjustment:

a.  Switch the Honeywell control to 

TEST

 position within the 

fi rst 10 seconds of the pilot ignition sequence. 

b.  Connect one side of a manometer or pressure gauge to the 

manometer pressure port (barbed) on the pressure test manifold 

(located inside control panel). See Figure 18. Leave the other 

side of the manometer open to the room. DO NOT connect 
it to the reference port (left  side of panel). 

Figure 18 

 Manometer connections to the test manifold (in 
control cabinet)

c.  Measure pilot gas pressure by pressing and holding the 

service valve marked 

PILOT GAS

d.  Set pilot gas pressure to 3.0 inches w.c. (± 0.5 inch) by 

adjusting the pilot gas pressure regulator, inside the air box. 

Access from the boiler top cover. See Figure 19.

Figure 19 

 Access to air trim adjustment and pilot regulator

e.  Check pilot air pressure using service valve marked 

PILOT 

AIR

 .

f.  Pilot air pressure should be 0.60 inches w.c. (± 0.10 inches).  

  Combustion readings must be in the range specifi ed 

in the following instructions. Adjust the boiler as 
necessary to ensure proper combustion.

Summary of Contents for FUTERA XLF Series

Page 1: ...use the boiler during construction Construction dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial...

Page 2: ...blocked air inlet 11 DP switch blocked flue 12 DP switch blower prov ing 13 DP switch pilot air prov ing 14 Ignitor 15 Pilot gas valve and pilot gas pressure regulator 16 Flow switch 17 Low water cut...

Page 3: ...he Commonwealth of Massachusetts you MUST FOLLOWtheadditionalinstructionscontainedinRBI sinstruction sheet MACODE 3 located in the back of this manual The owner should maintain a record of all service...

Page 4: ...er water heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure see GENERAL VENTING GUIDELINES 6 NEVER place this boiler water h...

Page 5: ...have a minimum mesh size of 1 4 inch 6 4 mm If the free area through a louver or grill is not known ducts should be sized per Table 2 Canadian installations must comply with CSA B149 1 when air suppl...

Page 6: ...d windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appliance...

Page 7: ...the vent system manufacturer s instructions Whenhorizontalventrunsexceed5ft 1 5mtheymustbesupported at 3 ft 0 9 m intervals with overhead hangers The vent system must be pitched down toward the vent...

Page 8: ...ntal combustion air and venting for single or multiple units exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to preva...

Page 9: ...0 feet each See Table 3 or 4 for min pipe diameters Locate exhaust terminal downwind from air intake to reduce potential for flue gas recirculation Failure to complycouldresultinsevere personal injury...

Page 10: ...nry chimneys should not be used unless properly lined to prevent condensation and draft problems Table 4 lists the equivalent breeching and flue sizes required for the boiler water heater Vent connect...

Page 11: ...UP TO 100 FEET MAXIMUM In this configuration the boiler water heater blower is used to push the flue products horizontally to the outdoors see Figure 7 The air for combustion is taken from the space...

Page 12: ...ORY II CHIMNEY INSPECTION SIZING Masonry chimneys when used must be lined with a metal liner certified for Category IV venting A thorough inspection of the masonry chimney must be performedtoensuretha...

Page 13: ...designed using accepted engineering practices and the design calculations prove there is no need for barometric dampers the barometric dampers may be omitted When required by applicable codes install...

Page 14: ...e Pipe the discharge of the pressure relief valve as shown in Figure 9 page 15 Never install any type of valve between the boiler waterheaterandthereliefvalveoranexplosioncausing extensive property da...

Page 15: ...eriseoutsideoftherangelistedinTable7 willresultindamagetotheheatexchanger voidingthe warranty The maximum allowable temperature rise through the boiler is 35o F 19 4o C The maximum allowable flow rate...

Page 16: ...umps orsystemsthathaveexcessiveflowratesorreturnwatertemperatures lessthan140o F 60o Cmustbeisolatedfromthesesystemstoprotect the boiler Variable water flows Figure 10 shows a typical primary secondar...

Page 17: ...iler design flow requirements 3 All boilers furnished with factory mounted outlet water temperature gauge 4 Boiler pump purging required Use termi nals supplied These drawings show suggested piping co...

Page 18: ...actory mounted outlet water temperature gauge 4 Boiler pump purging required Use terminals supplied 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow through all units F...

Page 19: ...F water heater is 260 GPM 16 4 L when equipped with coppertubes Thecupronickelheatexchangerallowsfor 315 GPM 19 9 L s See Table 9 page 20 RBI water heaters are designed to run scale free Due to the ex...

Page 20: ...itional precautions must be observed due to unusual characteristics of the local water supply Call the nearest RBI representative for details To properly size the pump a grain hardness andpHtestmustbe...

Page 21: ...l 6 90o elbows full pipe size 5 CAUTION MEASURE WATER HARDNESS AND pH AT JOB SITE 6 The pH and water hardness must be measured before selecting heat exchanger and pump Consult the Heat Exchanger Graph...

Page 22: ...assupplypipinghasthecapacitytomeetthedemand Figure 16 depicts the proper way to connect the boiler water heatertothegassupplypiping Themanualshut offvalveMUSTbe installedinthesupplypiping Itshouldbein...

Page 23: ...size Fitting or valve 90o elbow Tee branch flow Gate valve Gas cock 2 5 2 10 3 1 2 3 0 2 6 2 12 3 1 4 3 5 3 7 7 15 3 1 8 4 5 4 10 1 20 2 2 4 6 0 5 12 6 25 2 2 9 7 3 6 15 2 30 4 3 5 13 4 Equivalent le...

Page 24: ...lose the make up water valve and check and clean the strainers and make up water pressure reducing valve Open the make up water valve and adjust the system pressure if necessary The system should be c...

Page 25: ...at minimum ignition setting See the calibration section in the HeatNet Control IOM to enter the calibration menus 2 The ignition transformer is energized The pilot solenoid valve opens for the 10 sec...

Page 26: ...tNet control board to the LOW FIRE position 14 The boiler will begin the start up sequence 15 Allow the boiler to pre purge and enter the pilot ignition cycle 16 Ifpilotlights indicatedbyagoodflamesig...

Page 27: ...y combustion readings Leave the manometer connected to the test manifold It will be needed for high fire operation testing Verify high fire operation 1 Jumper the AA terminals on the HeatNet board and...

Page 28: ...ion and control methods Reference the XLF HeatNet Control IOM TO TURN OFF GAS TO APPLIANCE 1 Set the operating control to its lowest setting 2 Turn off all electric power to the boiler if service is t...

Page 29: ...is firing at full rate Low gas pressure could indicate undersized gas line or insufficient gas supply 2 Staticandoperatinggaspressurerequiredatthegasvalveinletis listed in the Table above If the gas...

Page 30: ...y lines and turn off electrical power to the boiler water heater 2 RemoveburnerfollowingtheinstructionsintheBurnerRemoval section 3 Remove the front jacket panel and combustion chamber door 4 Inspect...

Page 31: ...ied service technician to have it inspected NEVERtrytocleanorrepairthereliefvalve Ifthevalve fails to operate properly have it replaced 5 Theaquastathighlimitcontrolsthemaximumwatertemperature in the...

Page 32: ...F d b b l h B l M l Finned copper tube gas boilers water heaters Boiler Manual 32 F F Figure 23 Futera XLF pressure sensor hose routing...

Page 33: ...F d b b l h B l M l Finned copper tube gas boilers water heaters Boiler Manual 33 F F Figure 24 Exploded view REPAIR PARTS...

Page 34: ...F d b b l h B l M l Finned copper tube gas boilers water heaters Boiler Manual 34 F F REPAIR PARTS CONTINUED Figure 25 Figure 20 Electrical components...

Page 35: ...1 1 1 1 12 Bottom Corner 04 0542 4 4 4 4 13 Base Legs Left Side 04 1018 1 1 1 1 Base Legs Right Side 04 1022 1 1 1 1 15 Burner 10 0322 1 10 0297 1 10 0323 1 10 0300 1 15a Burner O ring 06 0006 1 1 1 1...

Page 36: ...Assembly 70 3510 1 1 1 1 30 Lower Rear Jacket Panel 03 3786 1 03 3787 1 03 3788 1 03 3789 1 NS Rear Panel Outdoor 03 3810 1 03 3811 1 1 1 NS Left Hand Rear Panel Outdoor 70 4113 1 70 4115 1 1 1 31 Upp...

Page 37: ...1 1 1 1 NS Latch 20 0045 2 2 2 2 41 Drain Valve Assembly MB 70 2562 1 1 1 1 Drain Valve Assembly MW 70 2564 1 1 1 1 NS Drain Valve Gaskets 06 0084 1 1 1 1 43 External Pilot Train Assembly 1 70 3655 1...

Page 38: ...0104 1 2 2 2 NS Alarm Button 48 0003 1 1 1 1 NS Alarm Toggle Bracket 03 3754 1 1 1 1 NS Terminal Block 6P 48 0157 1 1 1 1 NS Terminal Block 18P 48 0159 1 1 1 1 NS Relay 2P 24V optional 15 0121 1 1 1 1...

Page 39: ...71 Pump Contactor 3PH 15 0211 1 1 1 1 72 Relay Overload 5 5 8 Amp 15 0214 1 1 1 1 Relay Overload 9 13 Amp 15 0215 1 1 1 1 Relay Overload 2 5 4 Amp 15 0216 1 1 1 1 Relay Overload 4 6 Amp 15 0217 1 1 1...

Page 40: ...om right of the electrical panel on the main HeatNet board Also locate the manometer test manifold in the bottom of the electrical panel 1 Disable any external call for heat and toggle the remote loca...

Page 41: ...60o C Operating atlowerreturntemperaturesislikelytocausecondensationintheprimaryheatexchanger resultingincorrosionandpossible failure of the heat exchanger COMMISSIONING THE BOILER WATER HEATER UNIT C...

Page 42: ...ith the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GASVENTDIRECTLYBELOW KEEPCL...

Page 43: ...ty Excessive pitting and erosion on the inside of the heat exchanger tubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty See Installation Instructio...

Page 44: ...ht 2008 Mestek Inc 260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782 www rbiwaterhe...

Reviews: