FUTERA FUSION INSTALLATION AND OPERATION INSTRUCTIONS
10
Figure 7A – Outdoor Venting
Figure 7B – Multiple Outdoor Units
RIOM-60 REV. A
2 FT
(0.62 M)
3 FT
(1 M)
OUTDOOR VENTING
When installed outdoors the Futera Fusion must be fi tted
with the factory supplied outdoor hood, air intake adapter
with fi lter and exhaust terminal, see Figure 7A. Multiple
units must be spaced per Figure 7B.
The boiler/heater must be at least
2 ft
,
.62 m
from any
door, window or gravity air inlet into any building and at
least
3 ft,
1 m
from any overhang unless local codes dictate
differently.
Avoid locations where wind defl ection off of adjacent walls,
buildings or shrubbery might cause a downdraft. The
unit(s) shouild be located at least
3 ft
,
1 m
from structures.
Outdoor installations are not recommended in areas where
the danger of snow blockage exists.
CAUTION: Do not place the boiler/water heater in a
location that would subject it to runoff from adjacent
buildings or damage may occur voiding the warranty!
Outdoor Installations
WARNING: The Futera Boiler is certified for
outside installations in temperate climates
only.
1. The condensate traps located under the secondary
heat exchanger and the vent pipe must be wrapped
with heat tape to ensure the traps never drop below
32°F.
2. The vent pipe must be insulated to prevent freezing of
condensate in the pipe.
3. The boiler and system must be fi lled with an ethylene
glycol/water antifreeze mixture not to exceed 50% glycol
by volume.
4. All water piping exposed to low temperatures must be
insulated.