MODBUS COMMUNICATIONS
HeatNet Control V3
Page 120
MODBUS Input Variables (Read Only)
Address
Name
Raw Data
Type
Scale
Description
Valid Values/Range
30010
Day
8 bit unsigned
---
Real time clock day.
1
– 31
30011
Year
8 bit unsigned
---
Real time clock year.
0
– 99
30012
Hour
8 bit unsigned
---
Real time clock hour.
0
– 23
30013
Minute
8 bit unsigned
---
Real time clock minute.
0
– 59
30014
Second
8 bit unsigned
---
Real time clock second.
0
– 59
30015
Weekday
8 bit unsigned
---
Real time clock weekday.
1 (Monday)
– 7 (Sunday)
30016
Boiler01Status1
16 bit unsigned
---
Boiler (1
– 16) status flags. These bits
indicate the state of the 24VAC
interlocks, ignition circuit, and various
other conditions. See the values
column for a list of conditions.
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
See the “BoilerStatus1” and
“BoilerStatus2” Tables
below.
30017
Boiler01Status2
30018
Boiler02Status1
30019
Boiler02Status2
30020
Boiler03Status1
30021
Boiler03Status2
30022
Boiler04Status1
30023
Boiler04Status2
30024
Boiler05Status1
30025
Boiler05Status2
30026
Boiler06Status1
30027
Boiler06Status2
30028
Boiler07Status1
30029
Boiler07Status2
30030
Boiler08Status1
30031
Boiler08Status2
30032
Boiler09Status1
30033
Boiler09Status2
30034
Boiler10Status1
30035
Boiler10Status2
30036
Boiler11Status1
30037
Boiler11Status2
30038
Boiler12Status1
30039
Boiler12Status2
30040
Boiler13Status1
30041
Boiler13Status2
30042
Boiler14Status1
30043
Boiler14Status2
30044
Boiler15Status1
30045
Boiler15Status2
30046
Boiler16Status1
30047
Boiler16Status2
30048
Boiler01RuntimeHigh16 16 bit unsigned
---
0
– 4294967295 seconds