7 - INSTALLATION - IB boiler water connections
Figure 7-3 Water side head loss of the heater
7.2.4 - Local boiler pump
and CH pump
This boiler must be
fi
tted with a local
pump. To connect the local pump to
the boiler see Figures 7-4 and 7-5
and electrically connect the pump on
terminals as shown on Figure 8-2.
A
fi
eld supplied pump relay must be
installed if the pump current draw is
grater than 3 amps.
The water resistance to size the
local pump to supply
fl
ow through
the heating system at the boiler
connections is shown in graph form in
Figure 7-3.
CAUTION!!!
It is up to the
installer to ensure the minimum
system fl ow is not less than 4
GPM at any time. If the fl ow is
lower, the boiler automatically
stops the burner.
To connect an heating pump (CH
pump) on the secondary loop see
Figures 7-4 and 7-5 and electrically
connect the pump on terminals as
shown on Figure 10-4. A
fi
eld supplied
pump relay must be installed if the
pump current draw is grater than 3
amps.
7.2.5 - Sizing heating
system
Size the pump, piping and system
components required in the space
heating system, using recognized
design methods.
7.2.6 - Domestic Hot
Water system Piping
when using an indirect
water heater
See Figures 7-4 and 7-5, for
recommended piping to an indirect
water heater. This recommended
piping con
fi
guration ensures priority is
given to the production and recovery
of DHW. Refer to Figure 10-4 to wire
the indirect water heater pump (DHW
pump)
Anti-scald mixing valve: Field
supplied. An anti-scald mixing valve is
mandatory on the domestic hot water
outlet of the indirect water heater
WARNING!!!
Install an anti
scald mixing valve downstream
domestic hot water piping.
Failure to comply with this
provision can result in scalding
of individuals and animals
causing, severe personal injury
or death!
199
500
399
750
1000
Summary of Contents for Boiler
Page 3: ...3 SAFETY INSTRUCTIONS ...
Page 5: ...5 SAFETY INSTRUCTIONS ...
Page 122: ...122 15 MAINTENANCE ...
Page 126: ...126 17 SPARE PARTS Spare parts ...
Page 129: ...129 17 SPARE PARTS 50 48 50 49 53 56 57 55 54 58 47 52 48 52 51 55 52 020010 03 006 199 ...
Page 152: ...20 SEQUENCE OF OPERATION for BOILER ...