Chapter 2
Intelligent Field Panel
Integra32
™
Hardware Guide
RBH Access Technologies Inc.
18
Elevator Control
Integra32™ Elevator Control uses a modified URC2000 board with ELC firmware.
Up to four ELC-08 relays boards may be connect (strung) together for a maximum of
thirty-two dry contact outputs per Elevator Control panel. These contacts are
programmed as “on state de-energized” so that the release of the fire signal or power will
place the outputs in the ON state. There are red LEDs (one for each relay) that turn on
as each relay is energized therefore indicating an off state.
The green LED next to the data input connector flash when communications is lost.
Another green LED next to the Fire Signal connector indicates the presence of a Fire
Signal or Fire Signal Bypass.